 "manufacturer": "Marvair",
 "manufacturer_slug": "marvair",
 "model": "MAH / MGH wall-mount air conditioner control board (Modbus RTU)",
 "model_slug": "mah-mgh-wall-mount-ac-control-board",
 "short_model": "MAH/MGH wall-mount AC",
 "aliases": [
  "MAH1018A",
  "MAH1024A",
  "MAH1030A",
  "MAH1036A",
  "MAH1042A",
  "MAH1048A",
  "MAH1060A",
  "MGH1072A",
  "MAH2024A",
  "MAH2030A",
  "MAH2036A",
  "MAH2042A",
  "MAH2048A",
  "MAH2060A",
  "MGH2072A",
  "Marvair MAH",
  "Marvair MGH"
 ],
 "equipment_type": "Rooftop unit / packaged wall-mount air conditioner",
 "applies_to": "Marvair MAH1018A-1060A, MGH1072A, MAH2024A-2060A and MGH2072A wall-mount air conditioners with the electronic control board (I&O manual rev. 7).",
 "summary": "Marvair MAH and MGH packaged wall-mount air conditioners (electronic equipment shelters and process control rooms) carry an electronic control board with two RJ11 Modbus RTU ports. Over Modbus the board accepts thermostat calls, reports switch, relay and sensor states and an alarm word, and exposes fan-speed, economizer and calibration settings.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": 1,
  "baud": 19200,
  "parity": "None",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "0-based",
  "note": "The map prints a zero-based packet ID next to a one-based reference ID (1, 2, 3...). The zero-based ID is the wire address."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "MAH1018A-1060A, MGH1072A, MAH2024A-2060A & MGH2072A Wall-Mount AC Installation & Operation Manual",
  "doc_number": "Rev. 7",
  "revision_date": "2026-05",
  "url": "https://marvair.com/doc/25/MAH1018A-1060A%20MGH1072A%20MAH2024A-2060A%20%20MGH2072A%20Wall-Mount%20AC%20Manual%20Rev%207",
  "pages": "Appendix A, pp. 61-63; configuration items 22-26 in the control board section"
 },
 "notes": [
  "The manual prints two columns: a zero-based 'packet register ID' (used as the address here) and a one-based reference ID. Coils and registers each start at zero-based ID 0.",
  "Bit points: the board reads all of them with function 02 and writes the RW ones with function 05 (single coil only, no function 15). Coils and discrete inputs share one address space. RW bits are listed as coils, read-only bits as discrete inputs.",
  "Registers: the board reads them with function 04 and writes RW ones with function 06 (single register only, no function 16). RW registers are listed as holding registers so they can be written; the manual only documents reading them with function 04 at the same address. Whether function 01/03 reads work is not stated.",
  "Writes to read-only points return an error.",
  "Calibration registers hold 0-18 with 9 = no correction; the applied correction is the value minus 9.",
  "Heat and cool set points (registers 0-1) are writable but marked 'not currently used, for future use'.",
  "Anti-short-cycle timers count in 0.5 s steps (scale 0.5).",
  "This AC manual adds registers 39-41 (head pressure cutout, fan-only speed, heating outdoor fan speed) and gives the IFM Y1/Y2 speeds as 40-100 (default 60) instead of 0-1023; its alarm bit 0 reads 'freeze sensor fault'. The MAH heat pump manual prints a slightly different table (see the separate heat pump file).",
  "The configuration section gives the Modbus ID range as 1-99 in the table and 1-36161 in the text; the default is 1."
 ],
 "registers": [
  {
   "table": "coil",
   "address": 0,
   "documented": "0",
   "name": "Y1 compressor call",
   "description": "Stage 1 cooling request",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No call",
    "1": "Call"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 1,
   "documented": "1",
   "name": "Y2 compressor call",
   "description": "Stage 2 cooling request",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No call",
    "1": "Call"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 2,
   "documented": "2",
   "name": "Humidity call",
   "description": "Dehumidification request",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No call",
    "1": "Call"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 3,
   "documented": "3",
   "name": "G fan call",
   "description": "Fan-only request",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No call",
    "1": "Call"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 4,
   "documented": "4",
   "name": "W2 electric heat call",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No call",
    "1": "Call"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 17,
   "documented": "17",
   "name": "Communicating thermostat mode",
   "description": "Same as parameter P22: take calls from Modbus instead of hardware inputs",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Hardware calls (H)",
    "1": "Comm/Modbus calls (C)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 18,
   "documented": "18",
   "name": "Read hardware call inputs",
   "description": "1 = still read hardware thermostat inputs while P22 = C",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Normal (per P22)",
    "1": "Read hardware calls"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 24,
   "documented": "24",
   "name": "O reversing valve request",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No call",
    "1": "Call"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 26,
   "documented": "26",
   "name": "Emergency ventilation request",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 27,
   "documented": "27",
   "name": "Pulse reheat",
   "description": "Default on",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 5,
   "documented": "5",
   "name": "FCC call",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No call",
    "1": "Call"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 6,
   "documented": "6",
   "name": "High pressure switch 1",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Open",
    "1": "Closed"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 7,
   "documented": "7",
   "name": "High pressure switch 2",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Open",
    "1": "Closed"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 8,
   "documented": "8",
   "name": "Low pressure switch 1",
   "description": "AC manual labels it the HPS2 hardware input",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Open",
    "1": "Closed"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 9,
   "documented": "9",
   "name": "Low pressure switch 2",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Open",
    "1": "Closed"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 10,
   "documented": "10",
   "name": "OFM mode selection",
   "description": "Outdoor fan motor signal type",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "PWM",
    "1": "0-10 V"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 11,
   "documented": "11",
   "name": "IFM mode selection",
   "description": "Indoor fan motor signal type",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "PWM",
    "1": "0-10 V"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 12,
   "documented": "12",
   "name": "Technician speedup test mode",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Test mode"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 13,
   "documented": "13",
   "name": "Compressor 1 relay output",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "Energized"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 14,
   "documented": "14",
   "name": "Compressor 2 relay output",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "Energized"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 15,
   "documented": "15",
   "name": "RH relay output",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "Energized"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 16,
   "documented": "16",
   "name": "W2 relay output",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "Energized"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 19,
   "documented": "19",
   "name": "AC / HP",
   "description": "Unit type",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "AC",
    "1": "Heat pump"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 20,
   "documented": "20",
   "name": "EHDD",
   "description": "EHDD option setting",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 21,
   "documented": "21",
   "name": "SCKT",
   "description": "SCKT option setting",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 22,
   "documented": "22",
   "name": "Economizer enabled",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 23,
   "documented": "23",
   "name": "Economizer sensor type",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Dry bulb",
    "1": "Enthalpy"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 25,
   "documented": "25",
   "name": "RV output",
   "description": "Reversing valve output",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "Energized"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 28,
   "documented": "28",
   "name": "Emergency ventilation status",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 29,
   "documented": "29",
   "name": "EC relay output",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 9,
   "documented": "9",
   "name": "Current OFM speed",
   "description": "0-1023",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 10,
   "documented": "10",
   "name": "Current IFM speed",
   "description": "0-1023",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 11,
   "documented": "11",
   "name": "Anti-short-cycle compressor 1",
   "description": "0-360 counts of 0.5 s",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.5,
   "units": "s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 12,
   "documented": "12",
   "name": "Anti-short-cycle compressor 2",
   "description": "0-360 counts of 0.5 s",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.5,
   "units": "s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 13,
   "documented": "13",
   "name": "Voltage reading",
   "description": "0-1023; 1023 = above 20 V, 965 = 18 V cutoff",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 14,
   "documented": "14",
   "name": "P1 temperature",
   "description": "0-160 °F; 255 = no sensor",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°F",
   "access": "R",
   "values": {
    "255": "No sensor"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 15,
   "documented": "15",
   "name": "P2 temperature",
   "description": "0-160 °F; 255 = no sensor",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°F",
   "access": "R",
   "values": {
    "255": "No sensor"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 16,
   "documented": "16",
   "name": "Freeze sensor 1 temperature",
   "description": "0-160 °F; 255 = no sensor",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°F",
   "access": "R",
   "values": {
    "255": "No sensor"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 17,
   "documented": "17",
   "name": "Freeze sensor 2 temperature",
   "description": "0-160 °F; 255 = no sensor",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°F",
   "access": "R",
   "values": {
    "255": "No sensor"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 18,
   "documented": "18",
   "name": "Alarm status",
   "description": "0 = no fault",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Freeze sensor fault",
    "1": "HPS1 fault",
    "2": "Low voltage",
    "6": "LPS1 fault",
    "14": "Y1 locked out",
    "15": "Y2 locked out"
   },
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 24,
   "documented": "24",
   "name": "Software version",
   "description": "Decimal",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 25,
   "documented": "25",
   "name": "Supply / mixed air temperature",
   "description": "0-160 °F",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°F",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 27,
   "documented": "27",
   "name": "Outdoor temperature",
   "description": "0-160 °F",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°F",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 29,
   "documented": "29",
   "name": "Suction line temperature (LPS1)",
   "description": "0-160 °F; 255 = open or shorted sensor",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°F",
   "access": "R",
   "values": {
    "255": "Sensor open/shorted"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 31,
   "documented": "31",
   "name": "Liquid line temperature (FCC1)",
   "description": "0-160 °F; 255 = open or shorted sensor",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°F",
   "access": "R",
   "values": {
    "255": "Sensor open/shorted"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 33,
   "documented": "33",
   "name": "Defrost sensor temperature",
   "description": "0-160 °F",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°F",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 38,
   "documented": "38",
   "name": "Economizer output",
   "description": "0 = off, 20-100",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 0,
   "documented": "0",
   "name": "Heat set point",
   "description": "Reserved for future use; 45-100 °F",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°F",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1,
   "documented": "1",
   "name": "Cool set point",
   "description": "Reserved for future use; 45-100 °F",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°F",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "2",
   "name": "Temperature calibration",
   "description": "0-18, default 9; correction = value - 9",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3,
   "documented": "3",
   "name": "W2 speed multiplier",
   "description": "Percent of Y2 fan speed, 0-100, default 80",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4,
   "documented": "4",
   "name": "Dehumidification speed multiplier",
   "description": "Percent of Y2 fan speed, 0-100, default 80",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5,
   "documented": "5",
   "name": "OFM set speed",
   "description": "Outdoor fan speed, 0-1023",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6,
   "documented": "6",
   "name": "IFM Y1 set speed",
   "description": "Indoor fan speed for Y1, 40-100, default 60",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 7,
   "documented": "7",
   "name": "IFM Y2 set speed",
   "description": "Indoor fan speed for Y2, 40-100, default 60",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8,
   "documented": "8",
   "name": "Modbus timeout",
   "description": "Minutes without Modbus before reverting to hardware calls; 1-60, default 10",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 19,
   "documented": "19",
   "name": "Minimum position",
   "description": "Economizer minimum position: 20 = minimum, 20-100 = open %",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 20,
   "documented": "20",
   "name": "Economizer dry bulb set point",
   "description": "20-105 °F, default 70",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°F",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 21,
   "documented": "21",
   "name": "ODS set",
   "description": "0-70, default 50",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 22,
   "documented": "22",
   "name": "Fan purge",
   "description": "0 = no, 10-90 s, default 90",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": {
    "0": "No purge"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 23,
   "documented": "23",
   "name": "Defrost timer",
   "description": "30, 60 or 90 min (default 30)",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 26,
   "documented": "26",
   "name": "SAS/MAS calibration",
   "description": "0-18, default 9; correction = value - 9",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 28,
   "documented": "28",
   "name": "ODS calibration",
   "description": "0-18, default 9; correction = value - 9",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 30,
   "documented": "30",
   "name": "Suction line temp calibration",
   "description": "0-18, default 9; correction = value - 9",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 32,
   "documented": "32",
   "name": "Liquid line temp calibration",
   "description": "0-18, default 9; correction = value - 9",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 34,
   "documented": "34",
   "name": "DS calibration",
   "description": "0-18, default 9; correction = value - 9",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 35,
   "documented": "35",
   "name": "Dehumidifier set point",
   "description": "70-75 °F, default 72",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°F",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 36,
   "documented": "36",
   "name": "Pulse reheat differential",
   "description": "5-10 °F, default 5",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°F",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 37,
   "documented": "37",
   "name": "Economizer enthalpy set point",
   "description": "Modes A..E as 0..4, default 3 (D)",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "A",
    "1": "B",
    "2": "C",
    "3": "D",
    "4": "E"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 39,
   "documented": "39",
   "name": "Head pressure cutout temperature",
   "description": "75-95, default 85",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 40,
   "documented": "40",
   "name": "IFM G set speed",
   "description": "Indoor fan speed for fan-only, 30-100, default 60",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 41,
   "documented": "41",
   "name": "OFM speed heating",
   "description": "Outdoor fan speed in heating (heat pumps), 65-100, default 85",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Set coil 17 = 1 (communicating mode; the map says it mirrors parameter P22), then drive the unit with the Y1/Y2/G/W2/humidity/O call coils (0-4, 24). Read temperatures, relay states, pressure switches and the alarm word (input register 18) to monitor it.",
  "minimum_registers": [
   {
    "table": "coil",
    "address": 17,
    "why": "Communicating (Modbus) thermostat mode"
   },
   {
    "table": "coil",
    "address": 0,
    "why": "Y1 cooling call"
   },
   {
    "table": "coil",
    "address": 3,
    "why": "G fan call"
   },
   {
    "table": "discrete_input",
    "address": 13,
    "why": "Compressor 1 relay state"
   },
   {
    "table": "input_register",
    "address": 18,
    "why": "Alarm status bits"
   },
   {
    "table": "input_register",
    "address": 14,
    "why": "P1 temperature"
   },
   {
    "table": "input_register",
    "address": 27,
    "why": "Outdoor temperature"
   },
   {
    "table": "holding_register",
    "address": 8,
    "why": "Modbus timeout (minutes)"
   }
  ],
  "enable": "Set menu item 23 (T'STAT Select) to C for a communicating thermostat via Modbus, or write coil 17 = 1 (the Modbus map says coil 17 reads and changes 'P22', the thermostat-type setting). The Modbus ID (item 24, 1-99, default 1) and baud (item 25: 9.6 or 19 = 9600/19200) are set in the board configuration menu.",
  "watchdog": "Register 8 / configuration item 26 sets the Modbus timeout (1-60 min, default 10). After that long without Modbus traffic the board falls back to hardware thermostat calls.",
  "quirks": [
   "Only single-coil (05) and single-register (06) writes are accepted.",
   "Register reads are documented with function 04 only, including the writable ones.",
   "Temperature value 255 means no sensor or a failed sensor."
  ],
  "setup": [
   "Default slave ID 1, 19200 baud, 8 data bits, no parity, 1 stop bit.",
   "The board has two RJ11 Modbus ports wired in parallel; both carry the same bus."
  ],
  "gotchas": [
   "Until the thermostat type is C (menu item 23, or coil 17 = 1) the board keeps following its hardwired thermostat inputs.",
   "After the Modbus timeout with no traffic the board switches back to its hardware thermostat inputs, so poll faster than the timeout."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/marvair/mah-mgh-wall-mount-ac-control-board",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}