 "manufacturer": "Measurlogic",
 "manufacturer_slug": "measurlogic",
 "model": "DTS family energy sub-meters (DTS 101/105/305/310/SMX/SKT/DC)",
 "model_slug": "dts",
 "short_model": "DTS",
 "aliases": [
  "DTS 101",
  "DTS 105",
  "DTS 305",
  "DTS 310",
  "DTS SMX",
  "DTS SKT",
  "DTS DC"
 ],
 "equipment_type": "Energy meter",
 "applies_to": "Measurlogic DTS AC and DC sub-meters and transducers with Modbus RTU or Modbus TCP, per DTS Modbus Map version 2.7U (Oct 2012). Registers depend on model and wiring.",
 "summary": "The DTS family are compact DIN-rail, panel and socket energy sub-meters and transducers for single-phase, three-phase and DC circuits. Every value is a signed 32-bit integer in two holding registers, low word first. This map covers voltages, currents, frequency, power, power factor, unbalance, nett and split energy counters, identity and CT/PT ratio registers, and the RS-485 settings.",
 "transport": [
  "RTU",
  "TCP"
 ],
 "defaults": {
  "unit_id": 100,
  "baud": null,
  "parity": null,
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "1-based",
  "note": "Section 2.1.1 says the published addresses are 1-based in the 4x region; subtract 1 for the wire address (Voltage_LN_1 11001 -> 11000). Some masters want the 4 prefix (411001)."
 },
 "default_word_order": "CDAB",
 "firmware": null,
 "source": {
  "title": "DTS Modbus Map",
  "doc_number": "Version 2.7U",
  "revision_date": "2012-10-17",
  "url": "https://cdn.logic-control.com/docs/measurlogic/Measurlogic%20DTS%20Modbus%20Map%20V2.7U.pdf",
  "pages": "pp. 3-4 (registers, word order, power/energy resolution), pp. 5-9 (measurement and other registers)",
  "unofficial": true
 },
 "notes": [
  "Measurlogic does not host this map publicly that we could find; this copy is on a distributor's document CDN and is the unaltered Measurlogic document (Measurlogic header and footer on every page).",
  "All registers are signed 32-bit values with the LO register at the listed address and the HI register next (CDAB).",
  "Power, demand and energy registers have a variable resolution: engineering value in W / VA / var / Wh = raw x EnerPowDivider (register 16045) x 0.001. Their scale is therefore left at 1 and units blank; read 16045 once and apply the formula.",
  "Energy registers roll over after 999,999,999 counts.",
  "Min/max registers (116xx / 122xx), single-cycle currents, I/O channel status/coils (15301+), the output command register 40001 and the SunSpec map at 50001 are left out.",
  "Default Modbus address is 100 (on Modbus TCP it is always 100).",
  "Power factor registers (11100-11107) are left out: the manual marks their format 'Special' without defining it."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 10002,
   "documented": "10003",
   "name": "DTS_SerialNumber",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10008,
   "documented": "10009",
   "name": "DTS_FW_Version",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.0001,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10014,
   "documented": "10015",
   "name": "DTS_Model_ID",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11000,
   "documented": "11001",
   "name": "Voltage_LN_1",
   "description": "On DTS DC meters 11001 is Voltage_DC.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11002,
   "documented": "11003",
   "name": "Voltage_LN_2",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11004,
   "documented": "11005",
   "name": "Voltage_LN_3",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11006,
   "documented": "11007",
   "name": "Voltage_LN_Average",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11008,
   "documented": "11009",
   "name": "Voltage_LL_12",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11010,
   "documented": "11011",
   "name": "Voltage_LL_23",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11012,
   "documented": "11013",
   "name": "Voltage_LL_31",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11014,
   "documented": "11015",
   "name": "Voltage_LL_Average",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11024,
   "documented": "11025",
   "name": "Current_1",
   "description": "On DTS DC meters 11025 is Current_DC.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.001,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11026,
   "documented": "11027",
   "name": "Current_2",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.001,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11028,
   "documented": "11029",
   "name": "Current_3",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.001,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11030,
   "documented": "11031",
   "name": "Current_Average",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.001,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11032,
   "documented": "11033",
   "name": "Current_Total",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.001,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11034,
   "documented": "11035",
   "name": "Current_Neutral",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.001,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11040,
   "documented": "11041",
   "name": "Frequency_1",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.01,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11042,
   "documented": "11043",
   "name": "Frequency_2",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.01,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11044,
   "documented": "11045",
   "name": "Frequency_3",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.01,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11046,
   "documented": "11047",
   "name": "Frequency_Average",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.01,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11048,
   "documented": "11049",
   "name": "PowerP_1",
   "description": "Raw; multiply by EnerPowDivider (16045) x 0.001 to get W (11049 is Power_DC on DC meters).",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11050,
   "documented": "11051",
   "name": "PowerP_2",
   "description": "Raw; multiply by EnerPowDivider (16045) x 0.001 to get W.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11052,
   "documented": "11053",
   "name": "PowerP_3",
   "description": "Raw; multiply by EnerPowDivider (16045) x 0.001 to get W.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11054,
   "documented": "11055",
   "name": "PowerP_Total",
   "description": "Raw; multiply by EnerPowDivider (16045) x 0.001 to get W.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11056,
   "documented": "11057",
   "name": "PowerS_1",
   "description": "Raw; multiply by EnerPowDivider (16045) x 0.001 to get VA.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11058,
   "documented": "11059",
   "name": "PowerS_2",
   "description": "Raw; multiply by EnerPowDivider (16045) x 0.001 to get VA.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11060,
   "documented": "11061",
   "name": "PowerS_3",
   "description": "Raw; multiply by EnerPowDivider (16045) x 0.001 to get VA.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11062,
   "documented": "11063",
   "name": "PowerS_Total",
   "description": "Raw; multiply by EnerPowDivider (16045) x 0.001 to get VA.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11064,
   "documented": "11065",
   "name": "PowerQ_1",
   "description": "Raw; multiply by EnerPowDivider (16045) x 0.001 to get var.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11066,
   "documented": "11067",
   "name": "PowerQ_2",
   "description": "Raw; multiply by EnerPowDivider (16045) x 0.001 to get var.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11068,
   "documented": "11069",
   "name": "PowerQ_3",
   "description": "Raw; multiply by EnerPowDivider (16045) x 0.001 to get var.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11070,
   "documented": "11071",
   "name": "PowerQ_Total",
   "description": "Raw; multiply by EnerPowDivider (16045) x 0.001 to get var.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11124,
   "documented": "11125",
   "name": "ACosPF_1",
   "description": "Power factor angle.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.1,
   "units": "°",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11126,
   "documented": "11127",
   "name": "ACosPF_2",
   "description": "Power factor angle.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.1,
   "units": "°",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11128,
   "documented": "11129",
   "name": "ACosPF_3",
   "description": "Power factor angle.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.1,
   "units": "°",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11130,
   "documented": "11131",
   "name": "ACosPF_Overall",
   "description": "Power factor angle.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.1,
   "units": "°",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11140,
   "documented": "11141",
   "name": "Voltage_Unbalance_LN_1",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.01,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11142,
   "documented": "11143",
   "name": "Voltage_Unbalance_LN_2",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.01,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11144,
   "documented": "11145",
   "name": "Voltage_Unbalance_LN_3",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.01,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11146,
   "documented": "11147",
   "name": "Voltage_Unbalance_LN_Worst",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.01,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11148,
   "documented": "11149",
   "name": "Voltage_Unbalance_LL_12",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.01,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11150,
   "documented": "11151",
   "name": "Voltage_Unbalance_LL_23",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.01,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11152,
   "documented": "11153",
   "name": "Voltage_Unbalance_LL_31",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.01,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11154,
   "documented": "11155",
   "name": "Voltage_Unbalance_LL_Worst",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.01,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11156,
   "documented": "11157",
   "name": "Current_Unbalance_1",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.01,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11158,
   "documented": "11159",
   "name": "Current_Unbalance_2",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.01,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11160,
   "documented": "11161",
   "name": "Current_Unbalance_3",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.01,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11162,
   "documented": "11163",
   "name": "Current_Unbalance_Worst",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.01,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11256,
   "documented": "11257",
   "name": "DemandP_Total",
   "description": "Raw; multiply by EnerPowDivider (16045) x 0.001 to get W.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14000,
   "documented": "14001",
   "name": "EnergyP_1",
   "description": "Raw; multiply by EnerPowDivider (16045) x 0.001 to get Wh; nett counters are signed (export negative).",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14002,
   "documented": "14003",
   "name": "EnergyP_2",
   "description": "Raw; multiply by EnerPowDivider (16045) x 0.001 to get Wh; nett counters are signed (export negative).",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14004,
   "documented": "14005",
   "name": "EnergyP_3",
   "description": "Raw; multiply by EnerPowDivider (16045) x 0.001 to get Wh; nett counters are signed (export negative).",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14006,
   "documented": "14007",
   "name": "EnergyP_Total",
   "description": "Raw; multiply by EnerPowDivider (16045) x 0.001 to get Wh; nett counters are signed (export negative).",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14008,
   "documented": "14009",
   "name": "EnergyS_1",
   "description": "Raw; multiply by EnerPowDivider (16045) x 0.001 to get VAh; nett counters are signed (export negative).",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14010,
   "documented": "14011",
   "name": "EnergyS_2",
   "description": "Raw; multiply by EnerPowDivider (16045) x 0.001 to get VAh; nett counters are signed (export negative).",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14012,
   "documented": "14013",
   "name": "EnergyS_3",
   "description": "Raw; multiply by EnerPowDivider (16045) x 0.001 to get VAh; nett counters are signed (export negative).",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14014,
   "documented": "14015",
   "name": "EnergyS_Total",
   "description": "Raw; multiply by EnerPowDivider (16045) x 0.001 to get VAh; nett counters are signed (export negative).",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14016,
   "documented": "14017",
   "name": "EnergyQ_1",
   "description": "Raw; multiply by EnerPowDivider (16045) x 0.001 to get varh; nett counters are signed (export negative).",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14018,
   "documented": "14019",
   "name": "EnergyQ_2",
   "description": "Raw; multiply by EnerPowDivider (16045) x 0.001 to get varh; nett counters are signed (export negative).",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14020,
   "documented": "14021",
   "name": "EnergyQ_3",
   "description": "Raw; multiply by EnerPowDivider (16045) x 0.001 to get varh; nett counters are signed (export negative).",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14022,
   "documented": "14023",
   "name": "EnergyQ_Total",
   "description": "Raw; multiply by EnerPowDivider (16045) x 0.001 to get varh; nett counters are signed (export negative).",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14024,
   "documented": "14025",
   "name": "EnergyP_Total_Imp",
   "description": "Raw; multiply by EnerPowDivider (16045) x 0.001 to get Wh.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14026,
   "documented": "14027",
   "name": "EnergyP_Total_Exp",
   "description": "Raw; multiply by EnerPowDivider (16045) x 0.001 to get Wh.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14028,
   "documented": "14029",
   "name": "EnergyQ_Total_Imp",
   "description": "Raw; multiply by EnerPowDivider (16045) x 0.001 to get varh.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14030,
   "documented": "14031",
   "name": "EnergyQ_Total_Exp",
   "description": "Raw; multiply by EnerPowDivider (16045) x 0.001 to get varh.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14080,
   "documented": "14081",
   "name": "GeneralCounter1",
   "description": "General input pulse counter.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14082,
   "documented": "14083",
   "name": "GeneralCounter2",
   "description": "General input pulse counter.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14084,
   "documented": "14085",
   "name": "GeneralCounter3",
   "description": "General input pulse counter.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14086,
   "documented": "14087",
   "name": "GeneralCounter4",
   "description": "General input pulse counter.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16000,
   "documented": "16001",
   "name": "VoltagePrimary",
   "description": "PT primary.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.1,
   "units": "V",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16002,
   "documented": "16003",
   "name": "VoltageSecondary",
   "description": "PT secondary.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.1,
   "units": "V",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16008,
   "documented": "16009",
   "name": "CurrentPrimary",
   "description": "CT primary.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.001,
   "units": "A",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16010,
   "documented": "16011",
   "name": "CurrentSecondary",
   "description": "CT secondary.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.001,
   "units": "A",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16044,
   "documented": "16045",
   "name": "EnerPowDivider",
   "description": "Power/energy resolution divider; default 100 = 0.1 W.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16118,
   "documented": "16119",
   "name": "Rem_Baudrate",
   "description": "RS-485 baud rate (9600 or 19200).",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16120,
   "documented": "16121",
   "name": "Rem_Parity/DataBits/StopBits",
   "description": "Packed bytes: parity (0 none, 1 odd, 2 even), data bits, stop bits, reserved.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16122,
   "documented": "16123",
   "name": "Rem_Address",
   "description": "RS-485 slave address 1-247.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Read holding registers in CDAB 32-bit pairs at address 100 (default). Read EnerPowDivider (16045) first and scale power and energy with raw x divider x 0.001.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 11000,
    "why": "Voltage L1-N"
   },
   {
    "table": "holding_register",
    "address": 11024,
    "why": "Current 1"
   },
   {
    "table": "holding_register",
    "address": 11054,
    "why": "Total active power (raw)"
   },
   {
    "table": "holding_register",
    "address": 14006,
    "why": "Total nett active energy (raw)"
   },
   {
    "table": "holding_register",
    "address": 16044,
    "why": "EnerPowDivider"
   }
  ],
  "enable": "Modbus is built in (RS-485 RTU or Ethernet TCP depending on model). Communication parameters and address are normally set with Measurlogic's DTSConfig software.",
  "watchdog": null,
  "quirks": [
   "Every value is 32-bit signed, low word first (CDAB).",
   "Published addresses are 1-based.",
   "Power/energy resolution depends on EnerPowDivider."
  ],
  "setup": [
   "Default slave address 100.",
   "RS-485 baud rate 9600 or 19200; change it with DTSConfig rather than by writing registers.",
   "Do not change the RS-485 registers on Ethernet models."
  ],
  "gotchas": [
   "Writing wrong values to 16119-16123 can make the meter unreachable.",
   "Not every register is used on every model or wiring; only connected channels and the Total/Average registers carry valid data."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/measurlogic/dts",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}