EV charger · Modbus register map
MENNEKES AMTRON 4You 300 / Compact 2.0s / Start 2.0s (Modbus RTU) Modbus register map
Updated 28 October 2026
These MENNEKES home wallboxes become a Modbus RTU slave ('satellite') on RS-485 when DIP switches S1-4 and S1-5 are on, so an energy manager can control them. Data can be read as holding or input registers. This map covers identity, EVSE and CP state, configured current limits, per-phase current, voltage and power, session and lifetime energy, error codes and the control registers: heartbeat, charging release, current limit, phase switching and lock.
This page lists 51 Modbus registers for the MENNEKES AMTRON 4You 300 / Compact 2.0s / Start 2.0s (Modbus RTU) — 7 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from MENNEKES’s own free documentation (linked below) and checked against it.
- Manufacturer
- MENNEKES
- Model
- AMTRON 4You 300 / Compact 2.0s / Start 2.0s (Modbus RTU)
- Equipment type
- EV charger
- Registers
- 51 (7 writable)
- Transport
- Modbus RTU
- Default unit ID
- 50
- Default serial
- 57600 baud, 8N2
- Documented addressing
- hexadecimal, 0-based
- 32-bit word order
- ABCD high word first (big-endian)
- Firmware
- Software 2023.21.11024 and later (Modbus register layout v01.03)
- Also known as
- AMTRON 4You 300, AMTRON 4You 310, AMTRON Compact 2.0s, AMTRON Start 2.0s
Integration notes: MENNEKES AMTRON 4You 300 / Compact 2.0s / Start 2.0s (Modbus RTU)
Every 10 s or faster, write 0x55AA to 0x0D00 (heartbeat); write 1 to 0x0D05 (release) and the current limit as a float to 0x0302 with function 16. Read 0x0100 (EVSE state), 0x0E00 (error), 0x0512 (power) and 0x0B02 (session energy).
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 3328 | Heartbeat energy manager | UINT16 | Heartbeat from the energy manager | Write |
| HR 3333 | Charging release energy manager | UINT16 | Charging release | Read/write |
| HR 770 | Charging current energy manager | FLOAT32 ABCD | Charging current limit | Read/write |
| HR 256 | EVSE state | UINT16 | EVSE state | Read |
| HR 3584 | Active error code | UINT16 | Active error code | Read |
| HR 1298 | Power overall | FLOAT32 ABCD | Total charging power | Read |
| HR 2818 | Charged energy session | FLOAT32 ABCD | Session energy | Read |
| HR 3332 | Requested phases | UINT16 | 1- or 3-phase request | Read/write |
Enable Modbus control & writes
Set DIP switches S1-4 and S1-5 to ON and reboot; the wallbox then runs as a Modbus satellite at address 50 (10-50 can be set with the MENNEKES configuration tool).
Communication loss & watchdog
The energy manager must write 0x55AA to 0x0D00 at least every 10 s. What happens when it stops depends on 0x030E: 0 keeps charging with the last values received, 1 pauses charging, 6-32 charges at that fallback current. With no fallback active and no EV connected, the wallbox goes to error state (code 200 = energy manager not available); 0x0E01 shows when the fallback is active.
Byte order & addressing
- 0x0302 = 0 means unlimited, not stop; to pause, write a value between 0.01 and 5.99 A.
- Floats and uint32 values need function 16 for writes; function 6 is only for single-register values.
- Requested Phases (0x0D04) is ignored unless 0x030C reads 2 (phase-switch capable hardware, 11 kW models).
Network setup
- RS-485: Modbus A = +, B = -.
- Default 57600 baud, 8 data bits, no parity, 2 stop bits; other rates from 9600 to 57600 baud and 8E1 / 8O1 framing can be chosen with the MENNEKES configuration tool.
Watch out for
- After a reboot or communication error the wallbox needs 0x0D00, 0x0D05 and 0x0302 written again before it returns to idle and charges.
- MENNEKES recommends changing the current no faster than every 5 s and avoiding frequent pauses; some EVs (e.g. Fiat 500e) need the current set to 0 before a phase change.
MENNEKES AMTRON 4You 300 / Compact 2.0s / Start 2.0s (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 0x0000 | Modbus version | Register layout version, e.g. 0x0103 = v01.03. | UINT16 | Read | ||||
| HR | 1doc 0x0001 | Firmware version | 16 ASCII characters. | STRING[16] | Read | ||||
| HR | 19doc 0x0013 | Serial number | 16 ASCII characters (layout v01.02+). | STRING[16] | Read | ||||
| HR | 27doc 0x001B | MENNEKES article number | Article number from the type plate (layout v01.03+). | STRING[16] | Read | ||||
| HR | 256doc 0x0100 | EVSE state | UINT16 | Read | 0 = Not initialized; 1 = Idle (no EV connected); 2 = EV connected (no current signalled); 3 = Preconditions valid, not charging yet; 4 = Ready to charge (current signalled); 5 = Charging; 6 = Error; 7 = Service mode | ||||
| HR | 257doc 0x0101 | Authorization status | RFID / energy-manager release state. | UINT16 | Read | 0 = Not used (idle); 1 = Authorized (charging released); 2 = Not authorized | |||
| HR | 258doc 0x0102 | Downgrade | State of the external downgrade input. | UINT16 | Read | 0 = Not relevant (no EV); 1 = Not downgraded; 2 = Downgraded | |||
| HR | 259doc 0x0103 | Phase rotation | Configured phase order, used for load management. | UINT16 | Read | 0 = L1-L2-L3; 1 = L2-L3-L1; 2 = L3-L1-L2 | |||
| HR | 264doc 0x0108 | CP state | Control-pilot state between wallbox and EV (layout v01.02+). | UINT16 | Read | 0 = Init; 10 = A1 (no EV); 11 = B1 (EV connected, not charging / paused); 12 = C1 (EV ready to charge); 13 = D1; 14 = E (error); 15 = F (error); 26 = A2 (current >= 6 A offered, EV disconnected); 27 = B2 (ready, current >= 6 A offered); 28 = C2 (charging, current >= 6 A offered); 29 = D2 | |||
| HR | 276doc 0x0114 - 0x0115 | Signaled current | Current offered to the EV on the CP line (layout v01.03+). | FLOAT32 | ABCD | A | Read | ||
| HR | 768doc 0x0300 - 0x0301 | Downgrade current | Current limit applied while the downgrade input is active. | FLOAT32 | ABCD | A | Read | ||
| HR | 770doc 0x0302 - 0x0303 | Charging current energy manager | EMS current limit: 0 = no limit, 0.01-5.99 = pause, 6+ = limit. | FLOAT32 | ABCD | A | Read/write | ||
| HR | 772doc 0x0304 - 0x0305 | Maximal current house (DIP) | Installation current set on DIP switches 6-8 of bank S2. | FLOAT32 | ABCD | A | Read | ||
| HR | 774doc 0x0306 - 0x0307 | Maximal EVSE current | Maximum wallbox current set at installation. | FLOAT32 | ABCD | A | Read | ||
| HR | 778doc 0x030A | Phase switching mode | Phase use of the internal solar algorithm. | UINT16 | Read | 0 = Solar only 1 phase; 1 = Solar only 3 phases; 2 = Solar dynamic 1 or 3 phases | |||
| HR | 780doc 0x030C | Phase options HW | Whether the hardware can switch between 1 and 3 phases. | UINT16 | Read | 0 = Only 1 phase; 1 = Only 3 phases; 2 = 1 or 3 phases (phase switch possible) | |||
| HR | 781doc 0x030D | Cable lock setting | Permanent cable lock. | UINT16 | Read | 0 = Not enabled or unavailable; 1 = Enabled | |||
| HR | 782doc 0x030E | Energy manager fallback current | Behaviour if the EMS heartbeat stops during a session; 6-32 = fallback amps. | UINT16 | Read | 0 = Fallback disabled, keep last EMS values; 1 = Fallback enabled, pause charging | |||
| HR | 783doc 0x030F | Grid imbalance | UINT16 | Read | 0 = Disabled; 1 = Enabled | ||||
| HR | 784doc 0x0310 | Grid imbalance threshold | UINT16 | A | Read | ||||
| HR | 785doc 0x0311 | Grid phases connected | UINT16 | Read | 0 = L1 connected; 2 = L1, L2, L3 connected | ||||
| HR | 786doc 0x0312 | Authorization | Whether authorization is required. | UINT16 | Read | 0 = Disabled; 1 = Enabled | |||
| HR | 787doc 0x0313 | Sunshine+ minimum current | Minimum current in solar-supported (Sunshine+) mode. | UINT16 | A | Read | |||
| HR | 788doc 0x0314 | Phase switching pause | Pause between a 1-to-3 or 3-to-1 phase switch. | UINT16 | s | Read | |||
| HR | 1280doc 0x0500 - 0x0501 | Current L1 | RMS output current. | FLOAT32 | ABCD | A | Read | ||
| HR | 1282doc 0x0502 - 0x0503 | Current L2 | RMS output current. | FLOAT32 | ABCD | A | Read | ||
| HR | 1284doc 0x0504 - 0x0505 | Current L3 | RMS output current. | FLOAT32 | ABCD | A | Read | ||
| HR | 1286doc 0x0506 - 0x0507 | Voltage L1 | RMS output voltage. | FLOAT32 | ABCD | V | Read | ||
| HR | 1288doc 0x0508 - 0x0509 | Voltage L2 | RMS output voltage. | FLOAT32 | ABCD | V | Read | ||
| HR | 1290doc 0x050A - 0x050B | Voltage L3 | RMS output voltage. | FLOAT32 | ABCD | V | Read | ||
| HR | 1292doc 0x050C - 0x050D | Power L1 | FLOAT32 | ABCD | W | Read | |||
| HR | 1294doc 0x050E - 0x050F | Power L2 | FLOAT32 | ABCD | W | Read | |||
| HR | 1296doc 0x0510 - 0x0511 | Power L3 | FLOAT32 | ABCD | W | Read | |||
| HR | 1298doc 0x0512 - 0x0513 | Power overall | Total power on all phases. | FLOAT32 | ABCD | W | Read | ||
| HR | 2304doc 0x0900 - 0x0901 | Temperature | Temperature inside the wallbox. | FLOAT32 | ABCD | °C | Read | ||
| HR | 2816doc 0x0B00 - 0x0B01 | Max current session | Highest current allowed for this session by static limits (cable, installation). | FLOAT32 | ABCD | A | Read | ||
| HR | 2818doc 0x0B02 - 0x0B03 | Charged energy session | Energy delivered in the current session. | FLOAT32 | ABCD | kWh | Read | ||
| HR | 2820doc 0x0B04 - 0x0B05 | Duration session | Length of the current session. | UINT32 | ABCD | s | Read | ||
| HR | 2822doc 0x0B06 | Detected EV phases | Most phases the EV drew during this session. | UINT16 | Read | 0 = Not initialized; 1 = 1 phase; 2 = 2 phases; 3 = 3 phases | |||
| HR | 3328doc 0x0D00 | Heartbeat energy manager | EMS must write 0x55AA (21930) at least every 10 s. | UINT16 | Write | ||||
| HR | 3330doc 0x0D02 | Cable lock status | UINT16 | Read | 0 = Unknown; 1 = Cable unlocked; 2 = Cable locked; 3 = Fixed cable | ||||
| HR | 3331doc 0x0D03 | Solar charging mode | Mode shown on the solar LEDs; also changed by the wallbox button. | UINT16 | Read/write | 0 = Solar mode not active; 1 = Fast charging (standard); 2 = Solar charging (Sunshine); 3 = Solar supported charging (Sunshine+) | |||
| HR | 3332doc 0x0D04 | Requested phases | Ask for 1-phase charging on phase-switch capable hardware. | UINT16 | Read/write | 0 = Charge on all available phases; 1 = Force 1-phase charging | |||
| HR | 3333doc 0x0D05 | Charging release energy manager | EMS release; 0 opens the relays. | UINT16 | Read/write | 0 = Charging not allowed; 1 = Charging allowed | |||
| HR | 3334doc 0x0D06 | Lock EVSE | Block charging at the wallbox. | UINT16 | Read/write | 0 = Not locked; 1 = Locked | |||
| HR | 3353doc 0x0D19 | System restart | Write 0xBB (187) once, only while idle (layout v01.03+). | UINT16 | Write | ||||
| HR | 3584doc 0x0E00 | Active error code | 0 = no error. | UINT16 | Read | 0 = No error; 200 = Energy manager not available (no heartbeat); 2011 = EV overcurrent; 2323 = Connected phases mismatch | |||
| HR | 3585doc 0x0E01 | Master lost fallback state | UINT16 | Read | 0 = Not active; 1 = Active (energy manager unavailable) | ||||
| HR | 3586doc 0x0E02 | Switched phases | Phases that will be used once the relays close. | UINT16 | Read | 0 = All available phases; 1 = 1 phase only | |||
| HR | 4096doc 0x1000 - 0x1001 | Charged energy total | Lifetime energy on the AC port; not for billing. | FLOAT32 | ABCD | kWh | Read | ||
| HR | 4098doc 0x1002 - 0x1003 | Charging sessions total | UINT32 | ABCD | Read |
Notes on this map
- The specification states 'Byte and Word Order: Big Endian', so float32 and uint32 values have the high word first (ABCD). Float values are in engineering units with no scaling.
- Each register lists the register-layout version that introduced it (v01.00-v01.03); registers added in a later layout may be missing on older firmware (0x0114, 0x0D19 and 0x001B arrived with v01.03).
- Charging current energy manager (0x0302): 0 means no limit and the wallbox signals its maximum (16 or 32 A); 0.01-5.99 A pauses charging; 6 A and up is a limit, clipped to the wallbox's own maximum.
- Error codes 2300-2305 (over/undervoltage on L1-L3, with voltage detection active) are also listed in the source alongside the codes given under values.
- Function codes per the source: read 0x03 or 0x04; write single register 0x06 only for 1-register values, write multiple 0x10 for floats (e.g. 0x0302).
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the MENNEKES AMTRON 4You 300 / Compact 2.0s / Start 2.0s (Modbus RTU)
What Modbus registers does the MENNEKES AMTRON 4You 300 / Compact 2.0s / Start 2.0s (Modbus RTU) have?
This map lists 51 registers: 51 holding registers. 7 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the MENNEKES AMTRON 4You 300 / Compact 2.0s / Start 2.0s (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Addresses are printed in hex and go on the wire unchanged. The specification gives no example frame, but its table starts at register 0x0000 (Modbus version), which cannot exist in 1-based numbering, so the printed numbers are protocol addresses. So 0x0302 is requested as 770 decimal.
What byte order does the MENNEKES AMTRON 4You 300 / Compact 2.0s / Start 2.0s (Modbus RTU) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the MENNEKES AMTRON 4You 300 / Compact 2.0s / Start 2.0s (Modbus RTU)?
Start with HR 3328 Heartbeat energy manager (Heartbeat from the energy manager); HR 3333 Charging release energy manager (Charging release); HR 770 Charging current energy manager (Charging current limit); HR 256 EVSE state (EVSE state); HR 3584 Active error code (Active error code); HR 1298 Power overall (Total charging power); HR 2818 Charged energy session (Session energy); HR 3332 Requested phases (1- or 3-phase request).
How do I enable Modbus control of the MENNEKES AMTRON 4You 300 / Compact 2.0s / Start 2.0s (Modbus RTU)?
Set DIP switches S1-4 and S1-5 to ON and reboot; the wallbox then runs as a Modbus satellite at address 50 (10-50 can be set with the MENNEKES configuration tool).
What happens when the MENNEKES AMTRON 4You 300 / Compact 2.0s / Start 2.0s (Modbus RTU) loses Modbus communication?
The energy manager must write 0x55AA to 0x0D00 at least every 10 s. What happens when it stops depends on 0x030E: 0 keeps charging with the last values received, 1 pauses charging, 6-32 charges at that fallback current. With no fallback active and no EV connected, the wallbox goes to error state (code 200 = energy manager not available); 0x0E01 shows when the fallback is active.
Where is the official MENNEKES AMTRON 4You 300 / Compact 2.0s / Start 2.0s (Modbus RTU) Modbus documentation?
The source is Modbus RTU Specification - AMTRON 4You 300, AMTRON Compact 2.0s, AMTRON Start 2.0s (v2.5), revision 2025-07-11, published free by MENNEKES at https://www.mennekes.de/fileadmin/MEN-Deutschland/emobility/01_documents/04_installer/Modbus_RTU_Specification_AMTRON_4You300_Compact_2.0s_Start_2.0s-v2.5.pdf.
Source: Modbus RTU Specification - AMTRON 4You 300, AMTRON Compact 2.0s, AMTRON Start 2.0s · v2.5 · rev. 2025-07-11. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.