 "manufacturer": "Mitsubishi Electric",
 "manufacturer_slug": "mitsubishi-electric",
 "model": "FR-A700 inverter (RS-485 terminals, Modbus RTU)",
 "model_slug": "fr-a700",
 "short_model": "FR-A700",
 "aliases": [
  "FR-A720",
  "FR-A740",
  "FR-A700 series"
 ],
 "equipment_type": "Variable frequency drive",
 "applies_to": "FR-A700 series inverters (FR-A720-0.4K to 90K, FR-A740-0.4K to 500K) using the RS-485 terminals with Pr.549 = 1 (Modbus-RTU); Instruction Manual (Applied) revision E.",
 "summary": "Mitsubishi Electric's previous-generation high-performance inverter. Its RS-485 terminal block can speak Modbus RTU, exposing system variables (control word, operation mode, frequency command) at 40002-40015, a real-time monitor block from 40201, fault history at 40501 and parameters 0-999 at 41000 + parameter number. This map covers control, status, monitors, fault codes and the communication parameters.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": null,
  "baud": 9600,
  "parity": "Even",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "Modicon",
  "note": "The manual prints Modicon-style register numbers (40002, 41004) and states: starting address = register number - 40001. Its example reads 41004 (Pr.4) with start address H03EB (1003)."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "FR-A700 Instruction Manual (Applied)",
  "doc_number": "IB(NA)-0600226ENG-E",
  "revision_date": "2012-02",
  "url": "https://dl.mitsubishielectric.com/dl/fa/document/manual/inv/ib0600226eng/ib0600226enge.pdf",
  "pages": "Printed pp. 347-358 (4.24.6 Modbus-RTU communication specifications, example p. 350, Modbus registers pp. 355-358 incl. fault code list p. 358); parameter list pp. 71 ff."
 },
 "notes": [
  "All registers are single 16-bit words.",
  "Left out because the increment depends on capacity (55K or lower / 75K or higher): output current 40202, current peak 40211, input power 40213, output power 40214, excitation current 40218 and motor output 40234. Motor load factor 40224 gives a size-independent current reading.",
  "Left out because the sign is not stated: motor torque 40207, torque command 40232, torque current command 40233 and PID deviation 40254. Vector-control position/orientation monitors (40219, 40222, 40235), option terminal monitors (40258-40260) and the version-dependent motor temperature 40246 are not listed.",
  "Frequency registers use 0.01 Hz; with Pr.37/Pr.144 speed display they switch to 1 unit. The 0.01 Hz unit for 40014/40015 comes from the same manual's computer-link set-frequency description.",
  "Fault history registers hold the fault code in the low byte; the values listed are the manual's fault code list.",
  "Parameters with a 9999 (function off) setting are listed with their normal increment; the manual does not say how the 9999 setting itself is encoded on the wire.",
  "Parameters 0-999 sit at 41000 + Pr. number; calibration parameters C2-C41 have their own registers and are not listed. Pr.7/Pr.8 are left out (increment depends on Pr.21)."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 1,
   "documented": "40002",
   "name": "Inverter reset",
   "description": "Write any value to reset the inverter.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "40003",
   "name": "Parameter clear",
   "description": "Write H965A.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3,
   "documented": "40004",
   "name": "All parameter clear",
   "description": "Write H99AA.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5,
   "documented": "40006",
   "name": "Parameter clear (keep comm settings)",
   "description": "Write H5A96; communication parameters are kept.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6,
   "documented": "40007",
   "name": "All parameter clear (keep comm settings)",
   "description": "Write HAA99; communication parameters are kept.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8,
   "documented": "40009",
   "name": "Inverter status / control input instruction",
   "description": "Write = control input, read = inverter status.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Write: stop command / Read: RUN (inverter running)",
    "1": "Write: forward rotation / Read: forward rotation",
    "2": "Write: reverse rotation / Read: reverse rotation",
    "3": "Write: RH (high speed) / Read: SU (up to frequency)",
    "4": "Write: RM (middle speed) / Read: OL (overload)",
    "5": "Write: RL (low speed) / Read: IPF (instantaneous power failure)",
    "6": "Write: JOG / Read: FU (frequency detection)",
    "7": "Write: RT (second function) / Read: ABC1 (fault)",
    "8": "Write: AU (current input selection) / Read: ABC2",
    "9": "Write: CS (automatic restart selection)",
    "10": "Write: MRS (output stop)",
    "11": "Write: STOP (start self-holding)",
    "12": "Write: RES (reset)",
    "15": "Read: fault occurrence"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9,
   "documented": "40010",
   "name": "Operation mode / inverter setting",
   "description": "Read = current mode; write H0010 EXT, H0011 PU, H0014 NET.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Read: EXT",
    "1": "Read: PU",
    "2": "Read: EXT JOG",
    "3": "Read: PU JOG",
    "4": "Read: NET",
    "5": "Read: PU + EXT",
    "16": "Write: EXT (H0010)",
    "17": "Write: PU (H0011)",
    "20": "Write: NET (H0014)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 13,
   "documented": "40014",
   "name": "Running frequency (RAM)",
   "description": "Frequency command, not stored in EEPROM.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "Hz",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14,
   "documented": "40015",
   "name": "Running frequency (EEPROM)",
   "description": "Frequency command, also stored in EEPROM.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "Hz",
   "access": "W",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 200,
   "documented": "40201",
   "name": "Output frequency / speed",
   "description": "0.01 Hz; 1 unit when Pr.37 = 1-9998 or Pr.144 = 2-10/102-110.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 202,
   "documented": "40203",
   "name": "Output voltage",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 204,
   "documented": "40205",
   "name": "Frequency setting value / speed setting",
   "description": "0.01 Hz; 1 unit with Pr.37/Pr.144 speed display.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 205,
   "documented": "40206",
   "name": "Running speed",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "r/min",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 207,
   "documented": "40208",
   "name": "Converter output voltage",
   "description": "DC bus voltage.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 208,
   "documented": "40209",
   "name": "Regenerative brake duty",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 209,
   "documented": "40210",
   "name": "Electronic thermal relay function load factor",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 211,
   "documented": "40212",
   "name": "Converter output voltage peak value",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 214,
   "documented": "40215",
   "name": "Input terminal status",
   "description": "1 = on.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "STF",
    "1": "STR",
    "2": "AU",
    "3": "RT",
    "4": "RL",
    "5": "RM",
    "6": "RH",
    "7": "JOG",
    "8": "MRS",
    "9": "STOP",
    "10": "RES",
    "11": "CS"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 215,
   "documented": "40216",
   "name": "Output terminal status",
   "description": "1 = on.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "RUN",
    "1": "SU",
    "2": "IPF",
    "3": "OL",
    "4": "FU",
    "5": "ABC1",
    "6": "ABC2"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 216,
   "documented": "40217",
   "name": "Load meter",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 219,
   "documented": "40220",
   "name": "Cumulative energization time",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 222,
   "documented": "40223",
   "name": "Actual operation time",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 223,
   "documented": "40224",
   "name": "Motor load factor",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 224,
   "documented": "40225",
   "name": "Cumulative power",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 251,
   "documented": "40252",
   "name": "PID set point",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 252,
   "documented": "40253",
   "name": "PID measured value",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 500,
   "documented": "40501",
   "name": "Fault record 1",
   "description": "Low byte = fault code (H00xx). Write any value to clear history.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No alarm",
    "16": "E.OC1",
    "17": "E.OC2",
    "18": "E.OC3",
    "32": "E.OV1",
    "33": "E.OV2",
    "34": "E.OV3",
    "48": "E.THT",
    "49": "E.THM",
    "64": "E.FIN",
    "80": "E.IPF",
    "81": "E.UVT",
    "82": "E.ILF",
    "96": "E.OLT",
    "112": "E.BE",
    "128": "E.GF",
    "129": "E.LF",
    "144": "E.OHT",
    "145": "E.PTC",
    "160": "E.OPT",
    "163": "E.OP3",
    "176": "E.PE",
    "177": "E.PUE",
    "178": "E.RET",
    "179": "E.PE2",
    "192": "E.CPU",
    "193": "E.CTE",
    "194": "E.P24",
    "196": "E.CDO",
    "197": "E.IOH",
    "198": "E.SER",
    "199": "E.AIE",
    "200": "E.USB",
    "208": "E.OS",
    "209": "E.OSD",
    "210": "E.ECT",
    "211": "E.OD",
    "213": "E.MB1",
    "214": "E.MB2",
    "215": "E.MB3",
    "216": "E.MB4",
    "217": "E.MB5",
    "218": "E.MB6",
    "219": "E.MB7",
    "220": "E.EP",
    "241": "E.1",
    "242": "E.2",
    "243": "E.3",
    "246": "E.6",
    "247": "E.7",
    "251": "E.11",
    "253": "E.13"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 501,
   "documented": "40502",
   "name": "Fault record 2",
   "description": "Low byte = fault code (H00xx).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No alarm",
    "16": "E.OC1",
    "17": "E.OC2",
    "18": "E.OC3",
    "32": "E.OV1",
    "33": "E.OV2",
    "34": "E.OV3",
    "48": "E.THT",
    "49": "E.THM",
    "64": "E.FIN",
    "80": "E.IPF",
    "81": "E.UVT",
    "82": "E.ILF",
    "96": "E.OLT",
    "112": "E.BE",
    "128": "E.GF",
    "129": "E.LF",
    "144": "E.OHT",
    "145": "E.PTC",
    "160": "E.OPT",
    "163": "E.OP3",
    "176": "E.PE",
    "177": "E.PUE",
    "178": "E.RET",
    "179": "E.PE2",
    "192": "E.CPU",
    "193": "E.CTE",
    "194": "E.P24",
    "196": "E.CDO",
    "197": "E.IOH",
    "198": "E.SER",
    "199": "E.AIE",
    "200": "E.USB",
    "208": "E.OS",
    "209": "E.OSD",
    "210": "E.ECT",
    "211": "E.OD",
    "213": "E.MB1",
    "214": "E.MB2",
    "215": "E.MB3",
    "216": "E.MB4",
    "217": "E.MB5",
    "218": "E.MB6",
    "219": "E.MB7",
    "220": "E.EP",
    "241": "E.1",
    "242": "E.2",
    "243": "E.3",
    "246": "E.6",
    "247": "E.7",
    "251": "E.11",
    "253": "E.13"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 502,
   "documented": "40503",
   "name": "Fault record 3",
   "description": "Low byte = fault code (H00xx).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No alarm",
    "16": "E.OC1",
    "17": "E.OC2",
    "18": "E.OC3",
    "32": "E.OV1",
    "33": "E.OV2",
    "34": "E.OV3",
    "48": "E.THT",
    "49": "E.THM",
    "64": "E.FIN",
    "80": "E.IPF",
    "81": "E.UVT",
    "82": "E.ILF",
    "96": "E.OLT",
    "112": "E.BE",
    "128": "E.GF",
    "129": "E.LF",
    "144": "E.OHT",
    "145": "E.PTC",
    "160": "E.OPT",
    "163": "E.OP3",
    "176": "E.PE",
    "177": "E.PUE",
    "178": "E.RET",
    "179": "E.PE2",
    "192": "E.CPU",
    "193": "E.CTE",
    "194": "E.P24",
    "196": "E.CDO",
    "197": "E.IOH",
    "198": "E.SER",
    "199": "E.AIE",
    "200": "E.USB",
    "208": "E.OS",
    "209": "E.OSD",
    "210": "E.ECT",
    "211": "E.OD",
    "213": "E.MB1",
    "214": "E.MB2",
    "215": "E.MB3",
    "216": "E.MB4",
    "217": "E.MB5",
    "218": "E.MB6",
    "219": "E.MB7",
    "220": "E.EP",
    "241": "E.1",
    "242": "E.2",
    "243": "E.3",
    "246": "E.6",
    "247": "E.7",
    "251": "E.11",
    "253": "E.13"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 503,
   "documented": "40504",
   "name": "Fault record 4",
   "description": "Low byte = fault code (H00xx).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No alarm",
    "16": "E.OC1",
    "17": "E.OC2",
    "18": "E.OC3",
    "32": "E.OV1",
    "33": "E.OV2",
    "34": "E.OV3",
    "48": "E.THT",
    "49": "E.THM",
    "64": "E.FIN",
    "80": "E.IPF",
    "81": "E.UVT",
    "82": "E.ILF",
    "96": "E.OLT",
    "112": "E.BE",
    "128": "E.GF",
    "129": "E.LF",
    "144": "E.OHT",
    "145": "E.PTC",
    "160": "E.OPT",
    "163": "E.OP3",
    "176": "E.PE",
    "177": "E.PUE",
    "178": "E.RET",
    "179": "E.PE2",
    "192": "E.CPU",
    "193": "E.CTE",
    "194": "E.P24",
    "196": "E.CDO",
    "197": "E.IOH",
    "198": "E.SER",
    "199": "E.AIE",
    "200": "E.USB",
    "208": "E.OS",
    "209": "E.OSD",
    "210": "E.ECT",
    "211": "E.OD",
    "213": "E.MB1",
    "214": "E.MB2",
    "215": "E.MB3",
    "216": "E.MB4",
    "217": "E.MB5",
    "218": "E.MB6",
    "219": "E.MB7",
    "220": "E.EP",
    "241": "E.1",
    "242": "E.2",
    "243": "E.3",
    "246": "E.6",
    "247": "E.7",
    "251": "E.11",
    "253": "E.13"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 504,
   "documented": "40505",
   "name": "Fault record 5",
   "description": "Low byte = fault code (H00xx).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No alarm",
    "16": "E.OC1",
    "17": "E.OC2",
    "18": "E.OC3",
    "32": "E.OV1",
    "33": "E.OV2",
    "34": "E.OV3",
    "48": "E.THT",
    "49": "E.THM",
    "64": "E.FIN",
    "80": "E.IPF",
    "81": "E.UVT",
    "82": "E.ILF",
    "96": "E.OLT",
    "112": "E.BE",
    "128": "E.GF",
    "129": "E.LF",
    "144": "E.OHT",
    "145": "E.PTC",
    "160": "E.OPT",
    "163": "E.OP3",
    "176": "E.PE",
    "177": "E.PUE",
    "178": "E.RET",
    "179": "E.PE2",
    "192": "E.CPU",
    "193": "E.CTE",
    "194": "E.P24",
    "196": "E.CDO",
    "197": "E.IOH",
    "198": "E.SER",
    "199": "E.AIE",
    "200": "E.USB",
    "208": "E.OS",
    "209": "E.OSD",
    "210": "E.ECT",
    "211": "E.OD",
    "213": "E.MB1",
    "214": "E.MB2",
    "215": "E.MB3",
    "216": "E.MB4",
    "217": "E.MB5",
    "218": "E.MB6",
    "219": "E.MB7",
    "220": "E.EP",
    "241": "E.1",
    "242": "E.2",
    "243": "E.3",
    "246": "E.6",
    "247": "E.7",
    "251": "E.11",
    "253": "E.13"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 505,
   "documented": "40506",
   "name": "Fault record 6",
   "description": "Low byte = fault code (H00xx).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No alarm",
    "16": "E.OC1",
    "17": "E.OC2",
    "18": "E.OC3",
    "32": "E.OV1",
    "33": "E.OV2",
    "34": "E.OV3",
    "48": "E.THT",
    "49": "E.THM",
    "64": "E.FIN",
    "80": "E.IPF",
    "81": "E.UVT",
    "82": "E.ILF",
    "96": "E.OLT",
    "112": "E.BE",
    "128": "E.GF",
    "129": "E.LF",
    "144": "E.OHT",
    "145": "E.PTC",
    "160": "E.OPT",
    "163": "E.OP3",
    "176": "E.PE",
    "177": "E.PUE",
    "178": "E.RET",
    "179": "E.PE2",
    "192": "E.CPU",
    "193": "E.CTE",
    "194": "E.P24",
    "196": "E.CDO",
    "197": "E.IOH",
    "198": "E.SER",
    "199": "E.AIE",
    "200": "E.USB",
    "208": "E.OS",
    "209": "E.OSD",
    "210": "E.ECT",
    "211": "E.OD",
    "213": "E.MB1",
    "214": "E.MB2",
    "215": "E.MB3",
    "216": "E.MB4",
    "217": "E.MB5",
    "218": "E.MB6",
    "219": "E.MB7",
    "220": "E.EP",
    "241": "E.1",
    "242": "E.2",
    "243": "E.3",
    "246": "E.6",
    "247": "E.7",
    "251": "E.11",
    "253": "E.13"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 506,
   "documented": "40507",
   "name": "Fault record 7",
   "description": "Low byte = fault code (H00xx).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No alarm",
    "16": "E.OC1",
    "17": "E.OC2",
    "18": "E.OC3",
    "32": "E.OV1",
    "33": "E.OV2",
    "34": "E.OV3",
    "48": "E.THT",
    "49": "E.THM",
    "64": "E.FIN",
    "80": "E.IPF",
    "81": "E.UVT",
    "82": "E.ILF",
    "96": "E.OLT",
    "112": "E.BE",
    "128": "E.GF",
    "129": "E.LF",
    "144": "E.OHT",
    "145": "E.PTC",
    "160": "E.OPT",
    "163": "E.OP3",
    "176": "E.PE",
    "177": "E.PUE",
    "178": "E.RET",
    "179": "E.PE2",
    "192": "E.CPU",
    "193": "E.CTE",
    "194": "E.P24",
    "196": "E.CDO",
    "197": "E.IOH",
    "198": "E.SER",
    "199": "E.AIE",
    "200": "E.USB",
    "208": "E.OS",
    "209": "E.OSD",
    "210": "E.ECT",
    "211": "E.OD",
    "213": "E.MB1",
    "214": "E.MB2",
    "215": "E.MB3",
    "216": "E.MB4",
    "217": "E.MB5",
    "218": "E.MB6",
    "219": "E.MB7",
    "220": "E.EP",
    "241": "E.1",
    "242": "E.2",
    "243": "E.3",
    "246": "E.6",
    "247": "E.7",
    "251": "E.11",
    "253": "E.13"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 507,
   "documented": "40508",
   "name": "Fault record 8",
   "description": "Low byte = fault code (H00xx).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No alarm",
    "16": "E.OC1",
    "17": "E.OC2",
    "18": "E.OC3",
    "32": "E.OV1",
    "33": "E.OV2",
    "34": "E.OV3",
    "48": "E.THT",
    "49": "E.THM",
    "64": "E.FIN",
    "80": "E.IPF",
    "81": "E.UVT",
    "82": "E.ILF",
    "96": "E.OLT",
    "112": "E.BE",
    "128": "E.GF",
    "129": "E.LF",
    "144": "E.OHT",
    "145": "E.PTC",
    "160": "E.OPT",
    "163": "E.OP3",
    "176": "E.PE",
    "177": "E.PUE",
    "178": "E.RET",
    "179": "E.PE2",
    "192": "E.CPU",
    "193": "E.CTE",
    "194": "E.P24",
    "196": "E.CDO",
    "197": "E.IOH",
    "198": "E.SER",
    "199": "E.AIE",
    "200": "E.USB",
    "208": "E.OS",
    "209": "E.OSD",
    "210": "E.ECT",
    "211": "E.OD",
    "213": "E.MB1",
    "214": "E.MB2",
    "215": "E.MB3",
    "216": "E.MB4",
    "217": "E.MB5",
    "218": "E.MB6",
    "219": "E.MB7",
    "220": "E.EP",
    "241": "E.1",
    "242": "E.2",
    "243": "E.3",
    "246": "E.6",
    "247": "E.7",
    "251": "E.11",
    "253": "E.13"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1000,
   "documented": "41001",
   "name": "Pr.1 Maximum frequency",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "Hz",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1001,
   "documented": "41002",
   "name": "Pr.2 Minimum frequency",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "Hz",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1003,
   "documented": "41004",
   "name": "Pr.4 Multi-speed setting (high speed)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "Hz",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1004,
   "documented": "41005",
   "name": "Pr.5 Multi-speed setting (middle speed)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "Hz",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1005,
   "documented": "41006",
   "name": "Pr.6 Multi-speed setting (low speed)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "Hz",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1078,
   "documented": "41079",
   "name": "Pr.79 Operation mode selection",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "External/PU switchover (External at power-on)",
    "1": "Fixed PU operation",
    "2": "Fixed External operation (NET switchable)",
    "3": "External/PU combined mode 1",
    "4": "External/PU combined mode 2",
    "6": "Switchover mode",
    "7": "External operation (PU interlock)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1330,
   "documented": "41331",
   "name": "Pr.331 RS-485 communication station number",
   "description": "0 = broadcast; set 1-247.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1331,
   "documented": "41332",
   "name": "Pr.332 RS-485 communication speed",
   "description": "Setting x 100 = bps (initial 96 = 9600).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1333,
   "documented": "41334",
   "name": "Pr.334 RS-485 communication parity check selection",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No parity, 2 stop bits",
    "1": "Odd parity, 1 stop bit",
    "2": "Even parity, 1 stop bit"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1342,
   "documented": "41343",
   "name": "Pr.343 Communication error count",
   "description": "Modbus RTU error count (RAM).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1538,
   "documented": "41539",
   "name": "Pr.539 Modbus-RTU communication check time interval",
   "description": "0 = Modbus works but the drive trips in NET mode; 9999 = no check.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1548,
   "documented": "41549",
   "name": "Pr.549 Protocol selection",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Mitsubishi inverter protocol (computer link)",
    "1": "Modbus-RTU"
   },
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Set Pr.549 = 1 and Pr.331 to 1-247 (initial 0 is broadcast) and reset, then switch to NET mode by writing H0014 to 40010. Write the frequency to 40014 (0.01 Hz) and the run bits to 40009, and poll 40009, 40201, 40224 and 40501.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 8,
    "why": "Run/stop command and inverter status"
   },
   {
    "table": "holding_register",
    "address": 9,
    "why": "Operation mode (write H0014 for NET)"
   },
   {
    "table": "holding_register",
    "address": 13,
    "why": "Frequency command (RAM)"
   },
   {
    "table": "holding_register",
    "address": 200,
    "why": "Output frequency"
   },
   {
    "table": "holding_register",
    "address": 223,
    "why": "Motor load factor"
   },
   {
    "table": "holding_register",
    "address": 500,
    "why": "Latest fault code"
   }
  ],
  "enable": "Pr.549 = 1 selects Modbus-RTU (RS-485 terminals only); set Pr.331, Pr.332 and Pr.334 and reset. Run/frequency commands need NET operation mode (write H0014 to 40010; allowed depending on Pr.79/Pr.340). With a communication option fitted and Pr.550 = 9999, RS-485 terminal commands are ignored.",
  "watchdog": "Pr.539 Modbus-RTU communication check time interval (0.1-999.8 s, same behaviour as Pr.122); 9999 (initial) = no check; 0 lets Modbus run but the drive trips in NET mode.",
  "quirks": [
   "Request address = register - 40001.",
   "Station 0 is broadcast and never replies.",
   "40009 means control input when written and inverter status when read."
  ],
  "setup": [
   "Pr.332 initial 96 = 9600 bps; Pr.334 initial 2 = even parity, 1 stop bit; data length fixed at 8 bits.",
   "Modbus-RTU cannot be used in PU operation mode."
  ],
  "gotchas": [
   "Current and power monitors change resolution at 75K, so check the drive size before scaling them."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/mitsubishi-electric/fr-a700",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}