 "manufacturer": "Mitsubishi Electric",
 "manufacturer_slug": "mitsubishi-electric",
 "model": "MelcoBEMS MINI (A1M+) gateway for Ecodan FTC4/FTC5/FTC6 air-to-water systems",
 "model_slug": "melcobems-mini-a1m-plus-atw-ftc",
 "short_model": "MelcoBEMS MINI ATW",
 "aliases": [
  "A1M+",
  "MelcoBEMS MINI",
  "Procon A1M+",
  "Ecodan FTC4",
  "Ecodan FTC5",
  "Ecodan FTC6"
 ],
 "equipment_type": "Heat pump (VRF / split AC gateway)",
 "applies_to": "Procon MelcoBEMS MINI (A1M+) firmware 4.1.0 connected to an Ecodan FTC4, FTC5 or FTC6 air-to-water controller; holding-register table only.",
 "summary": "The MelcoBEMS MINI (A1M+) is a Procon-built RS-485 Modbus RTU gateway for Mitsubishi Electric units, documented by Mitsubishi Electric UK. With an Ecodan FTC controller it exposes on/off, zone modes, tank and zone setpoints, temperatures, heater and pump states and energy totals. This map lists the holding registers that the register tables mark as applicable to FTC4, FTC5 or FTC6.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": null,
  "baud": null,
  "parity": null,
  "data_bits": null,
  "stop_bits": null,
  "tcp_port": null
 },
 "addressing": {
  "convention": "Modicon",
  "note": "Every row gives both a protocol 'Addr' and a Modicon address (e.g. Addr 4 = 40005). The Addr value is what goes on the wire, so Modicon 40005 is wire address 4."
 },
 "default_word_order": null,
 "firmware": "A1M+ firmware 4.1.0",
 "source": {
  "title": "MelcoBEMS MINI (A1M+) ATW Modbus Register Tables",
  "doc_number": "Document version 1.0.1",
  "revision_date": "2025-10-07",
  "url": "https://library.mitsubishielectric.co.uk/pdf/download_full/5537",
  "pages": "Holding registers pp. 6-31 (FTC4/FTC5/FTC6 applicability columns), notes * ** ^ ^^ and #1-#18 pp. 30-31"
 },
 "notes": [
  "Only holding registers ticked for FTC4, FTC5 or FTC6 are listed. Registers marked FTC5/FTC6 only (or read-only on FTC4) say so in their description. CAHV/CRHV/QAHV/EAHV-only registers (operating mode 40027, capacity control, outdoor temperature by BMS, setting water temperature, brine and condensing temperatures, electric energy 1-16) are left out.",
  "Most temperatures exist twice: a signed version (x100, 0x8000 = -327.68 °C) and an unsigned version at the next address that never returns a negative. Only the signed versions are listed; the unsigned twin is at address + 1.",
  "The gateway also exposes the same data as input registers, coils and discrete inputs; their read-only holding-register copies are what is listed here.",
  "Left out: 40073 Status Of Heating, 40270-40272 model profile/capacity rows and the slave heat-pump frequency/run-time rows, because the extracted table text for those rows runs together and could not be matched to a single register with certainty; also the FTC6-only block 40343-40430 (date/time, software version, hybrid boiler settings, error status 1-39).",
  "The register tables do not state the gateway's factory slave ID, baud rate or parity, so the defaults are left empty; they are set via registers 40005-40007 or the installation instructions.",
  "Note in the source: the MRC Prohibit command must not be written to Shizuoka-designed models."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 4,
   "documented": "40005",
   "name": "Modbus Slave ID",
   "description": "Gateway Modbus address, 1-247.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5,
   "documented": "40006",
   "name": "Modbus RS-485 Baud Rate",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "9600",
    "1": "1200",
    "2": "2400",
    "3": "4800",
    "4": "9600",
    "5": "14400",
    "6": "19200",
    "7": "28800",
    "8": "38400",
    "9": "56000",
    "10": "57600",
    "11": "115200"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6,
   "documented": "40007",
   "name": "RS-485 Parity Type",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "None",
    "1": "Even",
    "2": "Odd"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9,
   "documented": "40010",
   "name": "Fault/Error Code (hex)",
   "description": "0x8000 = no error, 0x6999 = no communication with the unit.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10,
   "documented": "40011",
   "name": "A1M+ Firmware Version",
   "description": "Gateway firmware version.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11,
   "documented": "40012",
   "name": "Modbus Comms Counter",
   "description": "Counts valid Modbus commands; wraps after 65535.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 12,
   "documented": "40013",
   "name": "Fault Code (decimal)",
   "description": "8000 = no error, 6999 = no communication with the unit.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 13,
   "documented": "40014",
   "name": "System Type Detected",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "ATA unit connected",
    "1": "ATW system connected",
    "2": "Lossnay system connected",
    "255": "Undetermined (no unit detected yet)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 25,
   "documented": "40026",
   "name": "System On/Off",
   "description": "Values 2 and 3 are reported only, not writable.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "System OFF",
    "1": "System ON",
    "2": "Emergency Run (read only)",
    "3": "Test Run (read only)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 27,
   "documented": "40028",
   "name": "Operating Mode (DHW)",
   "description": "FTC5 and FTC6 only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Normal",
    "1": "Eco"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 28,
   "documented": "40029",
   "name": "A/C Mode - Zone 1",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Heating Room Temp",
    "1": "Heating Flow Temp",
    "2": "Heating Heat Curve",
    "3": "Cooling Room Temp (not on 13K model)",
    "4": "Cooling Flow Temp",
    "5": "Floor Dryup"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 29,
   "documented": "40030",
   "name": "A/C Mode - Zone 2",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Heating Room Temp",
    "1": "Heating Flow Temp",
    "2": "Heating Heat Curve",
    "3": "Cooling Room Temp (not on 13K model)",
    "4": "Cooling Flow Temp",
    "5": "Floor Dryup"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 30,
   "documented": "40031",
   "name": "Set Tank Water Temperature (signed)",
   "description": "DHW tank setpoint, x100. Read-only on FTC4.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 32,
   "documented": "40033",
   "name": "H/C Thermostat Target Temperature - Zone 1 (signed)",
   "description": "x100.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 34,
   "documented": "40035",
   "name": "H/C Thermostat Target Temperature - Zone 2 (signed)",
   "description": "x100.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 36,
   "documented": "40037",
   "name": "MRC Prohibit",
   "description": "Locks functions on the main remote controller.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "System On/Off (0 = on, 1 = prohibit)",
    "1": "Running mode (0 = on, 1 = prohibit)",
    "2": "Setting temperature (0 = on, 1 = prohibit)",
    "4": "Function setting (0 = normal, 1 = function setting)"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 37,
   "documented": "40038",
   "name": "Force DHW",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Normal",
    "1": "Force DHW"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 38,
   "documented": "40039",
   "name": "Holiday",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Normal",
    "1": "Holiday"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 39,
   "documented": "40040",
   "name": "DHW On Prohibit",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "On",
    "1": "Prohibit"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 40,
   "documented": "40041",
   "name": "Heating On Prohibit - Zone 1",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "On",
    "1": "Prohibit"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 41,
   "documented": "40042",
   "name": "Cooling On Prohibit - Zone 1",
   "description": "Read-only on FTC4.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "On",
    "1": "Prohibit"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 42,
   "documented": "40043",
   "name": "Heating On Prohibit - Zone 2",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "On",
    "1": "Prohibit"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 43,
   "documented": "40044",
   "name": "Cooling On Prohibit - Zone 2",
   "description": "FTC5 and FTC6 only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "On",
    "1": "Prohibit"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 54,
   "documented": "40055",
   "name": "Thermostat Target Temperature - Zone 1 (signed)",
   "description": "x100.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 56,
   "documented": "40057",
   "name": "Thermostat Target Temperature - Zone 2 (signed)",
   "description": "x100.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 58,
   "documented": "40059",
   "name": "HC Control Type",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Heating",
    "1": "Cooling"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 66,
   "documented": "40067",
   "name": "Own Refrigerant Address",
   "description": "0-32.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 67,
   "documented": "40068",
   "name": "Defrost",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Standby",
    "2": "Defrost",
    "3": "Waiting Restart"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 68,
   "documented": "40069",
   "name": "Residual Heat Removal",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Prepared",
    "2": "Residual Heat Removal"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 69,
   "documented": "40070",
   "name": "Refrigerant Error Info",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Error (System)",
    "2": "Error (Startup)",
    "3": "Maintenance Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 70,
   "documented": "40071",
   "name": "7-Segment Error Code Digit 1",
   "description": "First character of the displayed error code.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "A",
    "1": "b",
    "2": "E",
    "3": "F",
    "4": "J",
    "5": "L",
    "6": "P",
    "7": "U"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 71,
   "documented": "40072",
   "name": "7-Segment Error Code Digit 2",
   "description": "Second character; 1-15 = 1-F.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "16": "O",
    "17": "H",
    "18": "J",
    "19": "L",
    "20": "P",
    "21": "U"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 73,
   "documented": "40074",
   "name": "Heat Pump Frequency - Master",
   "description": "Compressor frequency, 0-255 Hz.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 80,
   "documented": "40081",
   "name": "Heat Source Status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "H/P",
    "1": "IH",
    "2": "BH",
    "3": "IH + BH",
    "4": "Boiler"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 81,
   "documented": "40082",
   "name": "Temperature Setpoint - Zone 1 (signed)",
   "description": "x100.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 83,
   "documented": "40084",
   "name": "Temperature Setpoint - Zone 2 (signed)",
   "description": "x100.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 85,
   "documented": "40086",
   "name": "Flow Temperature Setpoint - Zone 1 (signed)",
   "description": "x100.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 87,
   "documented": "40088",
   "name": "Flow Temperature Setpoint - Zone 2 (signed)",
   "description": "x100.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 89,
   "documented": "40090",
   "name": "Legionella Temperature Setpoint (signed)",
   "description": "x100.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 91,
   "documented": "40092",
   "name": "DHW Temperature Drop (signed)",
   "description": "x10.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 93,
   "documented": "40094",
   "name": "Room Temperature - Zone 1 (signed)",
   "description": "x100.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 95,
   "documented": "40096",
   "name": "Room Temperature - Zone 2 (signed)",
   "description": "x100.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 97,
   "documented": "40098",
   "name": "Refrigerant Liquid Temperature (signed)",
   "description": "x100.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 99,
   "documented": "40100",
   "name": "Outdoor Ambient Temperature (signed)",
   "description": "x10.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 101,
   "documented": "40102",
   "name": "Flow Temperature (signed)",
   "description": "x100.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 103,
   "documented": "40104",
   "name": "Return Temperature (signed)",
   "description": "x100.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 105,
   "documented": "40106",
   "name": "Tank Water Temperature (signed)",
   "description": "x100.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 107,
   "documented": "40108",
   "name": "Flow Temperature - Zone 1 (signed)",
   "description": "x100.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 109,
   "documented": "40110",
   "name": "Return Temperature - Zone 1 (signed)",
   "description": "x100.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 111,
   "documented": "40112",
   "name": "Flow Temperature - Zone 2 (signed)",
   "description": "x100.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 113,
   "documented": "40114",
   "name": "Return Temperature - Zone 2 (signed)",
   "description": "x100.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 115,
   "documented": "40116",
   "name": "Boiler Flow Temperature (signed)",
   "description": "x100.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 117,
   "documented": "40118",
   "name": "Boiler Return Temperature (signed)",
   "description": "x100.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 119,
   "documented": "40120",
   "name": "Room Thermo 1 (IN1)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 120,
   "documented": "40121",
   "name": "Room Thermo 2 (IN6)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 121,
   "documented": "40122",
   "name": "Flow SW1 (IN2)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 122,
   "documented": "40123",
   "name": "Flow SW2 (IN3)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 123,
   "documented": "40124",
   "name": "Flow SW3 (IN7)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 124,
   "documented": "40125",
   "name": "Demand (IN4)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 125,
   "documented": "40126",
   "name": "Outdoor Thermo (IN5)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 127,
   "documented": "40128",
   "name": "Heat Pump Master ON/OFF",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Stop",
    "1": "Run"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 136,
   "documented": "40137",
   "name": "Heat Pump Run Time (hours)",
   "description": "Hours part, 0-99.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 137,
   "documented": "40138",
   "name": "Heat Pump Run Time (hours x100)",
   "description": "Hundreds-of-hours part.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 100,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 144,
   "documented": "40145",
   "name": "Boiler ON/OFF",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Stop",
    "1": "Run"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 145,
   "documented": "40146",
   "name": "Booster Heater 1 ON/OFF",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Stop",
    "1": "Run"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 146,
   "documented": "40147",
   "name": "Booster Heater 2 ON/OFF",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Stop",
    "1": "Run"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 147,
   "documented": "40148",
   "name": "Booster Heater 2+ ON/OFF",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Stop",
    "1": "Run"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 148,
   "documented": "40149",
   "name": "Immersion Heater ON/OFF",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Stop",
    "1": "Run"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 149,
   "documented": "40150",
   "name": "Water Pump 1 ON/OFF",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Stop",
    "1": "Run"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 150,
   "documented": "40151",
   "name": "Water Pump 2 ON/OFF",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Stop",
    "1": "Run"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 151,
   "documented": "40152",
   "name": "Water Pump 3 ON/OFF",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Stop",
    "1": "Run"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 152,
   "documented": "40153",
   "name": "3-Way Valve ON/OFF",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Stop",
    "1": "Run"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 153,
   "documented": "40154",
   "name": "2-Way Valve 2 ON/OFF",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Stop",
    "1": "Run"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 154,
   "documented": "40155",
   "name": "Mixing Valve Step",
   "description": "Step 0-10.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 282,
   "documented": "40283",
   "name": "Last Heating Energy Consumed - kWh part",
   "description": "FTC5/FTC6 only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 283,
   "documented": "40284",
   "name": "Last Heating Energy Consumed - Wh part",
   "description": "x10 Wh (0-99 = 0-990 Wh). FTC5/FTC6 only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 10,
   "units": "Wh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 286,
   "documented": "40287",
   "name": "Last DHW Energy Consumed - kWh part",
   "description": "FTC5/FTC6 only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 287,
   "documented": "40288",
   "name": "Last DHW Energy Consumed - Wh part",
   "description": "x10 Wh. FTC5/FTC6 only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 10,
   "units": "Wh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 288,
   "documented": "40289",
   "name": "Last Total Energy Consumed",
   "description": "FTC5/FTC6 only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 292,
   "documented": "40293",
   "name": "Last Heating Energy Produced - kWh part",
   "description": "FTC5/FTC6 only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 293,
   "documented": "40294",
   "name": "Last Heating Energy Produced - Wh part",
   "description": "x10 Wh. FTC5/FTC6 only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 10,
   "units": "Wh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 296,
   "documented": "40297",
   "name": "Last DHW Energy Produced - kWh part",
   "description": "FTC5/FTC6 only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 297,
   "documented": "40298",
   "name": "Last DHW Energy Produced - Wh part",
   "description": "x10 Wh. FTC5/FTC6 only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 10,
   "units": "Wh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 298,
   "documented": "40299",
   "name": "Last Total Energy Produced",
   "description": "FTC5/FTC6 only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 299,
   "documented": "40300",
   "name": "Flow Rate",
   "description": "FTC5/FTC6 only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "l/min",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Connect the A1M+ to the FTC controller as described in its installation instructions and to the BMS RS-485 line, then read 40014 to confirm an ATW system is detected and 40010 for faults. Switch the system with 40026, set the tank and zone targets at 40031/40055/40057, and poll flow, return, tank and room temperatures from 40094-40118.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 13,
    "why": "System type detected (1 = ATW)"
   },
   {
    "table": "holding_register",
    "address": 9,
    "why": "Fault code, 0x8000 = no error"
   },
   {
    "table": "holding_register",
    "address": 25,
    "why": "System on/off"
   },
   {
    "table": "holding_register",
    "address": 30,
    "why": "DHW tank setpoint"
   },
   {
    "table": "holding_register",
    "address": 54,
    "why": "Zone 1 thermostat target"
   },
   {
    "table": "holding_register",
    "address": 101,
    "why": "Flow temperature"
   },
   {
    "table": "holding_register",
    "address": 105,
    "why": "Tank water temperature"
   },
   {
    "table": "holding_register",
    "address": 93,
    "why": "Zone 1 room temperature"
   },
   {
    "table": "holding_register",
    "address": 99,
    "why": "Outdoor ambient temperature"
   },
   {
    "table": "holding_register",
    "address": 80,
    "why": "Heat source in use"
   }
  ],
  "enable": "No enable step is described in the register tables; the gateway answers once it is powered from the unit and its Modbus address, baud rate and parity (40005-40007) match the master. See the separate MelcoBEMS MINI installation instructions.",
  "watchdog": null,
  "quirks": [
   "Temperatures are x100 for most points but x10 for outdoor ambient (40100) and DHW temperature drop (40092).",
   "Each signed temperature has an unsigned twin one address higher for masters that cannot handle negative values.",
   "Baud-rate code 0 and code 4 both mean 9600 in the table.",
   "Holding registers support FC 03, FC 06 and FC 16; registers marked READ ONLY cannot be written."
  ],
  "setup": [
   "Set the Modbus address (1-247), baud rate and parity in 40005-40007 to match the BMS.",
   "Energy values (40283-40299) are reported as a kWh part plus a Wh part (x10 Wh); add them for the full reading."
  ],
  "gotchas": [
   "Value 0x6999 (hex register) or 6999 (decimal register) means the gateway cannot talk to the heat pump controller, not a heat pump fault.",
   "Operating mode register 40027 is not marked for FTC units; use the zone A/C mode registers 40029/40030 and DHW mode 40028 instead."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/mitsubishi-electric/melcobems-mini-a1m-plus-atw-ftc",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}