 "manufacturer": "Mitsubishi Electric",
 "manufacturer_slug": "mitsubishi-electric",
 "model": "MelcoBEMS MINI (A1M+ / A1M) gateway for Lossnay heat recovery ventilators (LGH and VL series)",
 "model_slug": "melcobems-mini-lossnay",
 "short_model": "A1M+ Lossnay",
 "aliases": [
  "A1M+ Lossnay",
  "MelcoBEMS MINI Lossnay",
  "Procon A1M+",
  "Procon A1M",
  "A1M",
  "Lossnay LGH-RVX Modbus",
  "LGH-15RVX-E1",
  "LGH-200RVX-E1",
  "LGH-150RVXT-E1",
  "LGH-250RVXT-E1",
  "VL-250CZPVU-R-E",
  "VL-500CZPVU-L-E",
  "Lossnay VL Vertical"
 ],
 "equipment_type": "Air handler (heat recovery ventilation unit)",
 "applies_to": "Procon MelcoBEMS MINI A1M+ (manual v1.0.3, firmware 4.1.1) on Lossnay LGH-15..200RVX-E1, LGH-150..250RVXT-E1 and VL-250..500CZPVU-R/L-E; the older A1M (manual v1.1.11) prints the identical Lossnay table.",
 "summary": "Small Procon protocol converter that plugs into a Mitsubishi Electric Lossnay energy-recovery ventilator and serves Modbus RTU on RS-485 or Modbus TCP. For Lossnay units it gives on/off, ventilation mode (heat recovery / bypass / auto) and fan speed control, plus outdoor and room temperature, filter and maintenance signs, fault code, energy use and actual fan speeds.",
 "transport": [
  "RTU",
  "TCP"
 ],
 "defaults": {
  "unit_id": null,
  "baud": null,
  "parity": null,
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": 502
 },
 "addressing": {
  "convention": "Modicon",
  "note": "Every row prints a 0-based 'Addr' next to its Modicon number (40001 = holding 0, 30001 = input 0, 10001 = discrete input 0, 00001 = coil 0). The 0-based Addr is the wire address."
 },
 "default_word_order": null,
 "firmware": "4.1.1",
 "source": {
  "title": "Procon MelcoBEMS MINI (A1M+) Installation Manual",
  "doc_number": "Manual version 1.0.3",
  "revision_date": "2025-09-18",
  "url": "https://library.mitsubishielectric.co.uk/pdf/download_full/5538",
  "pages": "pp. 15-17 (protocols, DIP switches), p. 52 (Modbus TCP), pp. 116-128 (Lossnay Modbus tables), p. 135 (Appendix C compatible Lossnay units)"
 },
 "notes": [
  "Only rows the manual ticks for the Lossnay LGH and/or VL series are listed. Every listed row is ticked for both series.",
  "Rows printed with no tick for either series are left out: operating mode (40302), temperature setpoint (40305), supply air temperature (40306 / 30175), CO2 level (40310 / 30179), thermo on/off, actual operation mode, auto fan speed availability, the 0.5 °C step / heat-cool / auto availability flags, the min/max setpoint limits, the temperature-control-unit flags and the supply-air and CO2 sensor flags.",
  "All input registers, discrete inputs and the coil are mirrored as read-only holding registers (power on/off is writable on both holding 300 and coil 3).",
  "Outdoor temperature comes twice: signed (two's complement, down to -56.0 °C) and an unsigned twin for BMSs that cannot handle negative values.",
  "Fan speed value 0 (Auto) is marked not supported on LGH and VL units.",
  "The older MelcoBEMS MINI (A1M) manual v1.1.11, section 13 (https://library.mitsubishielectric.co.uk/pdf/download_full/5186, pp. 37-49), prints the same Lossnay table, addresses and ticks; the A1M is RS-485 only (no Modbus TCP).",
  "DIP switches: 1-5 node address (all OFF = 1, all ON = holding 4), 6 ON = 9600 baud no parity (OFF = holding 5/6), 7 ON = Modbus RTU (OFF = BACnet). Data bits 8 and stop bits 1 are fixed."
 ],
 "registers": [
  {
   "table": "coil",
   "address": 3,
   "documented": "00004",
   "name": "Power on/off",
   "description": "Same as holding 300.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 82,
   "documented": "10083",
   "name": "Night purge",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal operation",
    "1": "Night purge running"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 83,
   "documented": "10084",
   "name": "Maintenance sign",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Inactive",
    "1": "Active"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 84,
   "documented": "10085",
   "name": "Filter sign",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Inactive",
    "1": "Active"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 85,
   "documented": "10086",
   "name": "Actual ventilation mode",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Lossnay ventilation",
    "1": "Bypass ventilation"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 90,
   "documented": "10091",
   "name": "Energy consumption data available",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Not available",
    "1": "Available"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 91,
   "documented": "10092",
   "name": "Bypass damper available",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Not available",
    "1": "Available"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 92,
   "documented": "10093",
   "name": "Auto ventilation mode available",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Not available",
    "1": "Available"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 94,
   "documented": "10095",
   "name": "Outdoor temperature sensor",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Not equipped",
    "1": "Equipped"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 95,
   "documented": "10096",
   "name": "Return air temperature sensor",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Not equipped",
    "1": "Equipped"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3,
   "documented": "30004",
   "name": "Gateway firmware version",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 5,
   "documented": "30006",
   "name": "Modbus comms counter",
   "description": "Counts valid Modbus commands; wraps to 0 after 65535.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 9,
   "documented": "30010",
   "name": "System type detected",
   "description": "2 means a Lossnay is connected.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Air-To-Air unit",
    "1": "Air-To-Water system",
    "2": "Lossnay system",
    "255": "Undetermined (no unit detected yet)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 175,
   "documented": "30176",
   "name": "Outdoor temperature (signed)",
   "description": "Signed °C x 10 (0xFDD0 = -56.0). 0x7FFE detecting, 0x7FFF no thermistor.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 176,
   "documented": "30177",
   "name": "Outdoor temperature (unsigned)",
   "description": "Unsigned twin of outdoor temperature, °C x 10. 0x7FFE detecting, 0x7FFF no thermistor.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 177,
   "documented": "30178",
   "name": "Room temperature",
   "description": "Return-air (room) temperature, °C x 10. Needs the return-air sensor.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 179,
   "documented": "30180",
   "name": "Fault code (hex)",
   "description": "Lossnay fault code in hex form.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "32768": "No error (0x8000)",
    "26985": "No communication with the unit (0x6999)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 180,
   "documented": "30181",
   "name": "Fault code (decimal)",
   "description": "Same fault code shown as decimal digits.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "8000": "No error",
    "6999": "No communication with the unit"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 181,
   "documented": "30182",
   "name": "Energy consumption",
   "description": "kWh x 10 (0-6553.5 kWh).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 183,
   "documented": "30184",
   "name": "Actual supply fan speed",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Stop",
    "1": "Speed 1",
    "2": "Speed 2",
    "3": "Speed 3",
    "4": "Speed 4"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 184,
   "documented": "30185",
   "name": "Actual extract fan speed",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Stop",
    "1": "Speed 1",
    "2": "Speed 2",
    "3": "Speed 3",
    "4": "Speed 4"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 191,
   "documented": "30192",
   "name": "Number of fan speeds",
   "description": "1-4.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4,
   "documented": "40005",
   "name": "Modbus slave ID",
   "description": "Used when DIP 1-5 are all ON; 1-247.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5,
   "documented": "40006",
   "name": "RS-485 baud rate",
   "description": "Used when DIP 6 is OFF.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "9600",
    "1": "1200",
    "2": "2400",
    "3": "4800",
    "4": "9600",
    "5": "14400",
    "6": "19200",
    "7": "28800",
    "8": "38400",
    "9": "56000",
    "10": "57600",
    "11": "115200"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6,
   "documented": "40007",
   "name": "RS-485 parity",
   "description": "Used when DIP 6 is OFF.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "None",
    "1": "Even",
    "2": "Odd"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9,
   "documented": "40010",
   "name": "Fault code (hex)",
   "description": "Read-only; other codes are in the Lossnay documentation.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "32768": "No error (0x8000)",
    "26985": "No communication with the unit (0x6999)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10,
   "documented": "40011",
   "name": "Gateway firmware version",
   "description": "Read-only copy of input register 3.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11,
   "documented": "40012",
   "name": "Modbus comms counter",
   "description": "Counts valid Modbus commands; wraps to 0 after 65535.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 13,
   "documented": "40014",
   "name": "System type detected",
   "description": "Read-only copy of input register 9.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Air-To-Air unit",
    "1": "Air-To-Water system",
    "2": "Lossnay system",
    "255": "Undetermined (no unit detected yet)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 300,
   "documented": "40301",
   "name": "Power on/off",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 302,
   "documented": "40303",
   "name": "Ventilation mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Lossnay (heat recovery) mode",
    "1": "Bypass mode",
    "2": "Auto mode"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 303,
   "documented": "40304",
   "name": "Fan speed",
   "description": "Auto (0) is not supported on LGH or VL units.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Auto",
    "1": "Speed 1",
    "2": "Speed 2",
    "3": "Speed 3",
    "4": "Speed 4"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 306,
   "documented": "40307",
   "name": "Outdoor temperature (signed)",
   "description": "Signed °C x 10 (0xFDD0 = -56.0). 0x7FFE detecting, 0x7FFF no thermistor.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 307,
   "documented": "40308",
   "name": "Outdoor temperature (unsigned)",
   "description": "Unsigned twin of outdoor temperature, °C x 10. 0x7FFE detecting, 0x7FFF no thermistor.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 308,
   "documented": "40309",
   "name": "Room temperature",
   "description": "Return-air (room) temperature, °C x 10. Needs the return-air sensor.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 310,
   "documented": "40311",
   "name": "Fault code (hex)",
   "description": "Lossnay fault code in hex form.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "32768": "No error (0x8000)",
    "26985": "No communication with the unit (0x6999)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 311,
   "documented": "40312",
   "name": "Fault code (decimal)",
   "description": "Same fault code shown as decimal digits.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "8000": "No error",
    "6999": "No communication with the unit"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 313,
   "documented": "40314",
   "name": "Energy consumption",
   "description": "kWh x 10 (0-6553.5 kWh).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 316,
   "documented": "40317",
   "name": "Night purge",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal operation",
    "1": "Night purge running"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 317,
   "documented": "40318",
   "name": "Maintenance sign",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Inactive",
    "1": "Active"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 318,
   "documented": "40319",
   "name": "Filter sign",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Inactive",
    "1": "Active"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 319,
   "documented": "40320",
   "name": "Actual ventilation mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Lossnay ventilation",
    "1": "Bypass ventilation"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 320,
   "documented": "40321",
   "name": "Actual supply fan speed",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Stop",
    "1": "Speed 1",
    "2": "Speed 2",
    "3": "Speed 3",
    "4": "Speed 4"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 321,
   "documented": "40322",
   "name": "Actual extract fan speed",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Stop",
    "1": "Speed 1",
    "2": "Speed 2",
    "3": "Speed 3",
    "4": "Speed 4"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 332,
   "documented": "40333",
   "name": "Energy consumption data available",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Not available",
    "1": "Available"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 333,
   "documented": "40334",
   "name": "Number of fan speeds",
   "description": "1-4.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 334,
   "documented": "40335",
   "name": "Bypass damper available",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Not available",
    "1": "Available"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 335,
   "documented": "40336",
   "name": "Auto ventilation mode available",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Not available",
    "1": "Available"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 338,
   "documented": "40339",
   "name": "Outdoor temperature sensor",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Not equipped",
    "1": "Equipped"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 339,
   "documented": "40340",
   "name": "Return air temperature sensor",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Not equipped",
    "1": "Equipped"
   },
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Set DIP 7 ON for Modbus RTU, set the node address on DIP 1-5 and DIP 6 ON for 9600 / no parity (or use Modbus TCP on port 502). Check input 9 reads 2, then switch the unit with holding 300, pick the ventilation mode at 302 and fan speed at 303, and poll the temperatures, filter sign and fault code.",
  "minimum_registers": [
   {
    "table": "input_register",
    "address": 9,
    "why": "Confirms a Lossnay is detected (2)"
   },
   {
    "table": "holding_register",
    "address": 300,
    "why": "Power on/off"
   },
   {
    "table": "holding_register",
    "address": 302,
    "why": "Ventilation mode"
   },
   {
    "table": "holding_register",
    "address": 303,
    "why": "Fan speed (1-4)"
   },
   {
    "table": "input_register",
    "address": 175,
    "why": "Outdoor temperature (signed, x10)"
   },
   {
    "table": "input_register",
    "address": 177,
    "why": "Room temperature (x10)"
   },
   {
    "table": "discrete_input",
    "address": 84,
    "why": "Filter sign"
   },
   {
    "table": "input_register",
    "address": 179,
    "why": "Fault code (0x8000 = none)"
   }
  ],
  "enable": "DIP switch 7 ON selects Modbus RTU on RS-485 (OFF = BACnet MS/TP and BACnet IP). The Ethernet port serves Modbus TCP on port 502.",
  "watchdog": null,
  "quirks": [
   "Fault code 0x8000 (decimal register: 8000) means no fault; 0x6999 / 6999 means the gateway cannot talk to the Lossnay.",
   "Temperatures read 0x7FFE while the sensor is being detected and 0x7FFF when no thermistor is fitted.",
   "Write fan speed 1-4 only; Auto (0) is not supported on LGH and VL units.",
   "Check holding 334 / 335 before writing bypass or auto ventilation mode: they say whether the unit has a bypass damper and auto mode."
  ],
  "setup": [
   "RS-485 A, B and GND must all be connected; shielded cable, daisy chain only.",
   "Factory IP address 192.168.92.114, Modbus TCP port 502.",
   "Node address 1-30 on DIP 1-5 in binary; each converter on the bus needs its own address."
  ],
  "gotchas": [
   "The gateway detects ATA, ATW or Lossnay by itself; the Lossnay map applies only when the system type reads 2.",
   "Outdoor and room temperatures only read correctly when the matching sensor flag (338 / 339) reads 1 (equipped)."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/mitsubishi-electric/melcobems-mini-lossnay",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}