 "manufacturer": "Mitsubishi Electric",
 "manufacturer_slug": "mitsubishi-electric",
 "model": "Procon MelcoRETAIL MINI controller for Air-To-Air split units",
 "model_slug": "melcoretail-mini",
 "short_model": "MelcoRETAIL MINI",
 "aliases": [
  "MelcoRETAIL MINI",
  "Procon MelcoRETAIL MINI"
 ],
 "equipment_type": "VRF / split AC gateway (retail controller)",
 "applies_to": "Procon MelcoRETAIL MINI on the CN105/CN92 connector of Mitsubishi Electric M, S and P series Air-To-Air indoor units, installation manual v1.0.6, firmware 1.0.3.",
 "summary": "Small Procon controller that plugs into one Mitsubishi Electric split indoor unit and adds retail-style local I/O (status relays, force/lock inputs, analogue mode, fan, setpoint and occupancy inputs) plus a Modbus RTU slave on RS-485. Over Modbus it exposes mode, setpoint, fan, vane, on/off, room temperature and fault code, occupancy-based setpoints, setpoint limits, deadband settings and relay overrides.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": null,
  "baud": null,
  "parity": null,
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "Modicon",
  "note": "Every table prints a 0-based 'Address' next to the Modicon address (40001 = holding 0, 30001 = input 0, 10001 = discrete input 0, 00001 = coil 0). The 0-based address is the wire address."
 },
 "default_word_order": "CDAB",
 "firmware": "1.0.3",
 "source": {
  "title": "Procon MelcoRETAIL MINI Installation Manual",
  "doc_number": "Manual version 1.0.6",
  "revision_date": "2018-02-08",
  "url": "https://library.mitsubishielectric.co.uk/pdf/download_full/3632",
  "pages": "pp. 8-10 (DIP switches), pp. 35-41 (Modbus register tables)"
 },
 "notes": [
  "Input and coil values are mirrored as holding registers (marked read only) for BMSs that only read holding registers.",
  "The four analogue input readings (inputs 11-18) are 32-bit values split over two registers; the manual labels the lower address 'least significant register' and the higher 'most significant register', so they are listed as UINT32 low word first (CDAB). Signedness is not stated; the values are mV (0-10 V inputs) or ohm, so they never reach the sign bit.",
  "Rows that the manual describes as 'temperature value in °C multiplied by 10' use scale 0.1; rows described as 'temperature in °C' (virtual setpoint, deadband, limits, occupancy setpoints, relay offsets) are whole degrees.",
  "Holding 44/45 repeat the names of 18/19 (deadband cooling / heating setpoint) with the same defaults; both are listed as printed.",
  "Discrete input 9 is printed with Modicon number 10000; it sits between 10009 and 10011, so it is listed at address 9.",
  "Holding 20-31 and 47-50 are not printed. Inputs 2, 4, 6 and 7 are not printed; input 9 is printed as 'Unused' and left out.",
  "Fault codes other than 8000 / 0x8000 and 6999 / 0x6999 are the indoor unit's own codes.",
  "Discrete input 8 (DIP 1-6): the register table gives 0 = fixed 9600 / no parity and 1 = software settings, the opposite of the DIP switch section (OFF = software, ON = 9600). Only the switch position (0 = OFF, 1 = ON) is listed."
 ],
 "registers": [
  {
   "table": "coil",
   "address": 0,
   "documented": "00001",
   "name": "Drive On/Off",
   "description": "Same as holding register 7.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Drive off",
    "1": "Drive on"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 0,
   "documented": "10001",
   "name": "Force ON input state",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Input off (open)",
    "1": "Input on (closed)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 1,
   "documented": "10002",
   "name": "Force OFF input state",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Input off (open)",
    "1": "Input on (closed)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 2,
   "documented": "10003",
   "name": "Lock/Auto input state",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Input off (open)",
    "1": "Input on (closed)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 3,
   "documented": "10004",
   "name": "External fault input state",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Input off (open)",
    "1": "Input on (closed)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 4,
   "documented": "10005",
   "name": "Running status relay state",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Relay de-energised",
    "1": "Relay energised"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 5,
   "documented": "10006",
   "name": "Heating status relay state",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Relay de-energised",
    "1": "Relay energised"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 6,
   "documented": "10007",
   "name": "Cooling status relay state",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Relay de-energised",
    "1": "Relay energised"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 7,
   "documented": "10008",
   "name": "Fault relay state",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Relay de-energised",
    "1": "Relay energised"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 8,
   "documented": "10009",
   "name": "Comms settings switch (DIP 1-6)",
   "description": "Reports the switch position; the table's meaning text is the reverse of the DIP section.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "DIP 1-6 OFF",
    "1": "DIP 1-6 ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 9,
   "documented": "9 / 10000",
   "name": "Protocol selection switch (DIP 1-7)",
   "description": "Modicon number printed as 10000 in the manual.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Reserved",
    "1": "Modbus RTU"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 10,
   "documented": "10011",
   "name": "Auto/Lock mode selection switch (DIP 1-8)",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Auto mode",
    "1": "Lock mode"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 11,
   "documented": "10012",
   "name": "Deadband switch (DIP 2-1)",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 12,
   "documented": "10013",
   "name": "Setpoint limiting switch (DIP 2-2)",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 13,
   "documented": "10014",
   "name": "Timeout switch (DIP 2-3)",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 14,
   "documented": "10015",
   "name": "Analogue input type switch (DIP 2-4)",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Voltage",
    "1": "Resistance"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 0,
   "documented": "30001",
   "name": "Room temperature",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1,
   "documented": "30002",
   "name": "Fault code (hex)",
   "description": "0x8000 = no error, 0x6999 = no comms with indoor unit.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "32768": "No error",
    "27033": "Bad communication with indoor unit"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3,
   "documented": "30004",
   "name": "Firmware version",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 5,
   "documented": "30006",
   "name": "Modbus comms counter",
   "description": "Counts valid Modbus commands; wraps after 65535.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 8,
   "documented": "30009",
   "name": "Fault code (decimal)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "8000": "No error",
    "6999": "Bad communication with indoor unit"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 10,
   "documented": "30011",
   "name": "Current DIP switch values",
   "description": "Raw DIP switch value (bit layout not given).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 11,
   "documented": "30012 / 30013",
   "name": "Occupancy mode input value",
   "description": "mV (voltage inputs) or ohm (resistance inputs).",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "mV / ohm",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 13,
   "documented": "30014 / 30015",
   "name": "Fan speed input value",
   "description": "mV (voltage inputs) or ohm (resistance inputs).",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "mV / ohm",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 15,
   "documented": "30016 / 30017",
   "name": "Mode input value",
   "description": "mV (voltage inputs) or ohm (resistance inputs).",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "mV / ohm",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 17,
   "documented": "30018 / 30019",
   "name": "Setpoint input value",
   "description": "mV (voltage inputs) or ohm (resistance inputs).",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "mV / ohm",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 0,
   "documented": "40001",
   "name": "Drive mode",
   "description": "i-see codes are read only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Heating",
    "2": "Humidity reduction",
    "3": "Cooling",
    "7": "Ventilation / clean air",
    "8": "Auto",
    "9": "i-see heating (read only)",
    "10": "i-see humidity reduction (read only)",
    "11": "i-see cooling (read only)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1,
   "documented": "40002",
   "name": "Temperature setpoint",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "40003",
   "name": "Fan speed",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Auto",
    "2": "Quiet",
    "3": "Weak",
    "5": "Strong",
    "6": "Very strong (SH i)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3,
   "documented": "40004",
   "name": "Air direction",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Auto",
    "1": "Position 1",
    "2": "Position 2",
    "3": "Position 3",
    "4": "Position 4",
    "5": "Position 5",
    "7": "Swing"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4,
   "documented": "40005",
   "name": "Modbus slave ID",
   "description": "1-247; used when DIP 1-1 to 1-5 are all ON.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5,
   "documented": "40006",
   "name": "RS-485 baud rate",
   "description": "Used when DIP 1-6 is OFF.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "9600",
    "1": "1200",
    "2": "2400",
    "3": "4800",
    "4": "9600",
    "5": "14400",
    "6": "19200",
    "7": "28800",
    "8": "38400",
    "9": "56000",
    "10": "57600",
    "11": "115200"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6,
   "documented": "40007",
   "name": "RS-485 parity",
   "description": "Used when DIP 1-6 is OFF.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "None",
    "1": "Even",
    "2": "Odd"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 7,
   "documented": "40008",
   "name": "Drive On/Off",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Drive off",
    "1": "Drive on"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8,
   "documented": "40009",
   "name": "Room temperature",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9,
   "documented": "40010",
   "name": "Fault code (hex)",
   "description": "0x8000 = no error.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "32768": "No error",
    "27033": "Bad communication with indoor unit"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10,
   "documented": "40011",
   "name": "Firmware version",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11,
   "documented": "40012",
   "name": "Modbus comms counter",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 12,
   "documented": "40013",
   "name": "Fault code (decimal)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "8000": "No error",
    "6999": "Bad communication with indoor unit"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 13,
   "documented": "40014",
   "name": "System type detected",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Air-to-air",
    "1": "Air-to-water"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14,
   "documented": "40015",
   "name": "Deadband enabled state",
   "description": "Value text in the manual says 'DIP switch 8'; deadband is DIP 2-1 on this unit.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 15,
   "documented": "40016",
   "name": "BMS room temperature (signed)",
   "description": "Room reading from the BMS for the setpoint offset feature.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16,
   "documented": "40017",
   "name": "BMS room temperature",
   "description": "Unsigned version, 0-50 °C.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 17,
   "documented": "40018",
   "name": "BMS virtual setpoint",
   "description": "Whole degrees.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 18,
   "documented": "40019",
   "name": "Deadband heating setpoint",
   "description": "At least 2 °C below the deadband cooling setpoint. Default 19 °C.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 19,
   "documented": "40020",
   "name": "Deadband cooling setpoint",
   "description": "At least 2 °C above the deadband heating setpoint. Default 23 °C.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 32,
   "documented": "40033",
   "name": "Auto mode setpoint high limit",
   "description": "Default 30 °C.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 33,
   "documented": "40034",
   "name": "Auto mode setpoint low limit",
   "description": "Default 16 °C.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 34,
   "documented": "40035",
   "name": "Cooling mode setpoint high limit",
   "description": "Default 30 °C.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 35,
   "documented": "40036",
   "name": "Cooling mode setpoint low limit",
   "description": "Default 16 °C.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 36,
   "documented": "40037",
   "name": "Heating mode setpoint high limit",
   "description": "Default 30 °C.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 37,
   "documented": "40038",
   "name": "Heating mode setpoint low limit",
   "description": "Default 16 °C.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 38,
   "documented": "40039",
   "name": "In-occupancy cooling setpoint",
   "description": "Occupancy mode. Default 23 °C.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 39,
   "documented": "40040",
   "name": "In-occupancy heating setpoint",
   "description": "Occupancy mode. Default 21 °C.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 40,
   "documented": "40041",
   "name": "Staff-in cooling setpoint",
   "description": "Occupancy mode. Default 24 °C.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 41,
   "documented": "40042",
   "name": "Staff-in heating setpoint",
   "description": "Occupancy mode. Default 18 °C.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 42,
   "documented": "40043",
   "name": "Unoccupied cooling setpoint",
   "description": "Occupancy mode. Default 26 °C.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 43,
   "documented": "40044",
   "name": "Unoccupied heating setpoint",
   "description": "Occupancy mode. Default 16 °C.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 44,
   "documented": "40045",
   "name": "Deadband cooling setpoint (2)",
   "description": "Second deadband cooling row in the manual. Default 23 °C.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 45,
   "documented": "40046",
   "name": "Deadband heating setpoint (2)",
   "description": "Second deadband heating row in the manual. Default 19 °C.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 46,
   "documented": "40047",
   "name": "Auto mode timeout",
   "description": "Time in auto mode before the unit drops to fan mode. Default 300 s.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 51,
   "documented": "40052",
   "name": "Relay manual override start/stop",
   "description": "1 = allow override via 52-55; times out after 20 minutes.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "End override",
    "1": "Start override"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 52,
   "documented": "40053",
   "name": "Relay 1 override (ON/OFF)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "De-energise relay",
    "1": "Energise relay"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 53,
   "documented": "40054",
   "name": "Relay 2 override (HEATING)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "De-energise relay",
    "1": "Energise relay"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 54,
   "documented": "40055",
   "name": "Relay 3 override (COOLING)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "De-energise relay",
    "1": "Energise relay"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 55,
   "documented": "40056",
   "name": "Relay 4 override (FAULT)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "De-energise relay",
    "1": "Energise relay"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 56,
   "documented": "40057",
   "name": "Auto mode timeout override",
   "description": "Write a number of seconds to shorten the current Auto Mode run.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 57,
   "documented": "40058",
   "name": "Heating relay temperature offset",
   "description": "Drop below setpoint before the heating relay energises.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 58,
   "documented": "40059",
   "name": "Cooling relay temperature offset",
   "description": "Rise above setpoint before the cooling relay energises.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 59,
   "documented": "40060",
   "name": "Relay switching delay",
   "description": "Delay before the on/off, heating and cooling relays change.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Set DIP 1-7 ON (Modbus RTU), pick the slave ID on DIP 1-1 to 1-5 and use DIP 1-6 ON for 9600 / no parity. Then write mode, setpoint, fan and on/off at holding 0-3 and 7 and poll room temperature (8) and fault code (12).",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 7,
    "why": "On/off"
   },
   {
    "table": "holding_register",
    "address": 0,
    "why": "Mode"
   },
   {
    "table": "holding_register",
    "address": 1,
    "why": "Setpoint (x10)"
   },
   {
    "table": "holding_register",
    "address": 2,
    "why": "Fan speed"
   },
   {
    "table": "holding_register",
    "address": 8,
    "why": "Room temperature (x10)"
   },
   {
    "table": "holding_register",
    "address": 12,
    "why": "Fault code (8000 = none)"
   },
   {
    "table": "discrete_input",
    "address": 7,
    "why": "Fault relay state"
   }
  ],
  "enable": "DIP CONFIG 1-7 ON selects Modbus RTU (OFF is reserved). Power-cycle after any DIP change.",
  "watchdog": null,
  "quirks": [
   "Slave ID from DIP 1-1 to 1-5 (1-30); all ON means the ID comes from holding 4; all OFF is invalid.",
   "DIP 1-6 ON fixes 9600 baud, no parity; OFF uses holding 5 and 6. Data bits 8 and stop bits 1 are fixed.",
   "Writing 0 to the BMS room temperature (15/16) turns the setpoint offset feature off."
  ],
  "setup": [
   "Plug the flying lead into CN105/CN92 on the indoor unit PCB; the unit is powered from there.",
   "RS-485 needs A, B and GND, shielded cable, daisy chain only; shield to GND at one end.",
   "Cannot be used together with a MAC-397IF / MAC-333IF interface (same connector)."
  ],
  "gotchas": [
   "Relay manual override (51) times out after 20 minutes.",
   "Setpoint limits and deadband settings depend on the matching DIP features (2-2 setpoint limiting, 2-1 deadband)."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/mitsubishi-electric/melcoretail-mini",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}