 "manufacturer": "Moxa",
 "manufacturer_slug": "moxa",
 "model": "ioLogik R1240 RS-485 remote I/O",
 "model_slug": "iologik-r1240",
 "short_model": "ioLogik R1240",
 "aliases": [
  "ioLogik R1240",
  "R1240",
  "R1240-T"
 ],
 "equipment_type": "Sensor (remote I/O module)",
 "applies_to": "ioLogik R1240 per the ioLogik R1200 Series User's Manual, Edition 3.4 (April 2021).",
 "summary": "The ioLogik R1240 is a Moxa RS-485 Modbus RTU remote I/O module with 8 analog inputs (0-10 V, 0-20 mA, 4-20 mA). It supports a repeater or dual RS-485 mode and a Modbus host-connection watchdog. This map covers the shared system registers (model, watchdog, serial settings) and the analog input raw values, min/max, status and range.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": null,
  "baud": 9600,
  "parity": "None",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "hex 0-based",
  "note": "Each row prints the hex protocol address and a 1-based reference number (0x0000 = 00001/10001/30001/40001). The hex address is sent on the wire; the table (coil, discrete input, input or holding) is set by the function code column."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "ioLogik R1200 Series User's Manual",
  "doc_number": "Edition 3.4",
  "revision_date": "2021-04",
  "url": "https://cdn11.bigcommerce.com/s-hltjsp5jm3/content/pdfs/moxa-iologik-r1200-series-manual.pdf",
  "pages": "pp. 2-4 to 2-5 (device ID, serial settings, Initial/Run and Dual/Repeater switches), Appendix A pp. A-2 to A-37 (Modbus mapping), Appendix B (factory defaults)",
  "unofficial": true
 },
 "notes": [
  "Moxa does not appear to offer this manual on a public URL found in this pass; the link is an unaltered copy of the Moxa user's manual on a reseller's file host.",
  "Each table row gives the hex wire address, the 1-based decimal reference (e.g. 0x0000 = 40001; system registers use six digits, 0x7530 = 330001), access, size and function code.",
  "Left out: system strings and multi-word values whose format is not described (firmware version and release date, serial number, server name/location, password, vendor name).",
  "Left out: the 32-bit engineering values (current, min, max) and burnout values at 0x0320-0x03AF and 0x02E0-0x02EF (holding), because the table does not say whether they are integers or floats or how they are scaled. Raw values are listed with no scaling."
 ],
 "registers": [
  {
   "table": "coil",
   "address": 704,
   "documented": "0x02C0",
   "name": "AI-00_resetMinValue",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "1": "reset min. value"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 705,
   "documented": "0x02C1",
   "name": "AI-01_resetMinValue",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "1": "reset min. value"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 706,
   "documented": "0x02C2",
   "name": "AI-02_resetMinValue",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "1": "reset min. value"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 707,
   "documented": "0x02C3",
   "name": "AI-03_resetMinValue",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "1": "reset min. value"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 708,
   "documented": "0x02C4",
   "name": "AI-04_resetMinValue",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "1": "reset min. value"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 709,
   "documented": "0x02C5",
   "name": "AI-05_resetMinValue",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "1": "reset min. value"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 710,
   "documented": "0x02C6",
   "name": "AI-06_resetMinValue",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "1": "reset min. value"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 711,
   "documented": "0x02C7",
   "name": "AI-07_resetMinValue",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "1": "reset min. value"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 736,
   "documented": "0x02E0",
   "name": "AI-00_resetMaxValue",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "1": "reset max. value"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 737,
   "documented": "0x02E1",
   "name": "AI-01_resetMaxValue",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "1": "reset max. value"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 738,
   "documented": "0x02E2",
   "name": "AI-02_resetMaxValue",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "1": "reset max. value"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 739,
   "documented": "0x02E3",
   "name": "AI-03_resetMaxValue",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "1": "reset max. value"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 740,
   "documented": "0x02E4",
   "name": "AI-04_resetMaxValue",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "1": "reset max. value"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 741,
   "documented": "0x02E5",
   "name": "AI-05_resetMaxValue",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "1": "reset max. value"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 742,
   "documented": "0x02E6",
   "name": "AI-06_resetMaxValue",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "1": "reset max. value"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 743,
   "documented": "0x02E7",
   "name": "AI-07_resetMaxValue",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "1": "reset max. value"
   },
   "bits": null
  },
  {
   "table": "input_register",
   "address": 704,
   "documented": "0x02C0",
   "name": "AI-00_rawValue",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 705,
   "documented": "0x02C1",
   "name": "AI-01_rawValue",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 706,
   "documented": "0x02C2",
   "name": "AI-02_rawValue",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 707,
   "documented": "0x02C3",
   "name": "AI-03_rawValue",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 708,
   "documented": "0x02C4",
   "name": "AI-04_rawValue",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 709,
   "documented": "0x02C5",
   "name": "AI-05_rawValue",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 710,
   "documented": "0x02C6",
   "name": "AI-06_rawValue",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 711,
   "documented": "0x02C7",
   "name": "AI-07_rawValue",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 736,
   "documented": "0x02E0",
   "name": "AI-00_rawValueMin",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 737,
   "documented": "0x02E1",
   "name": "AI-01_rawValueMin",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 738,
   "documented": "0x02E2",
   "name": "AI-02_rawValueMin",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 739,
   "documented": "0x02E3",
   "name": "AI-03_rawValueMin",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 740,
   "documented": "0x02E4",
   "name": "AI-04_rawValueMin",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 741,
   "documented": "0x02E5",
   "name": "AI-05_rawValueMin",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 742,
   "documented": "0x02E6",
   "name": "AI-06_rawValueMin",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 743,
   "documented": "0x02E7",
   "name": "AI-07_rawValueMin",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 768,
   "documented": "0x0300",
   "name": "AI-00_rawValueMax",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 769,
   "documented": "0x0301",
   "name": "AI-01_rawValueMax",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 770,
   "documented": "0x0302",
   "name": "AI-02_rawValueMax",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 771,
   "documented": "0x0303",
   "name": "AI-03_rawValueMax",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 772,
   "documented": "0x0304",
   "name": "AI-04_rawValueMax",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 773,
   "documented": "0x0305",
   "name": "AI-05_rawValueMax",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 774,
   "documented": "0x0306",
   "name": "AI-06_rawValueMax",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 775,
   "documented": "0x0307",
   "name": "AI-07_rawValueMax",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 992,
   "documented": "0x03E0",
   "name": "AI-00_status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "normal",
    "1": "burnout",
    "2": "over range",
    "3": "under range"
   },
   "bits": null
  },
  {
   "table": "input_register",
   "address": 993,
   "documented": "0x03E1",
   "name": "AI-01_status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "normal",
    "1": "burnout",
    "2": "over range",
    "3": "under range"
   },
   "bits": null
  },
  {
   "table": "input_register",
   "address": 994,
   "documented": "0x03E2",
   "name": "AI-02_status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "normal",
    "1": "burnout",
    "2": "over range",
    "3": "under range"
   },
   "bits": null
  },
  {
   "table": "input_register",
   "address": 995,
   "documented": "0x03E3",
   "name": "AI-03_status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "normal",
    "1": "burnout",
    "2": "over range",
    "3": "under range"
   },
   "bits": null
  },
  {
   "table": "input_register",
   "address": 996,
   "documented": "0x03E4",
   "name": "AI-04_status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "normal",
    "1": "burnout",
    "2": "over range",
    "3": "under range"
   },
   "bits": null
  },
  {
   "table": "input_register",
   "address": 997,
   "documented": "0x03E5",
   "name": "AI-05_status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "normal",
    "1": "burnout",
    "2": "over range",
    "3": "under range"
   },
   "bits": null
  },
  {
   "table": "input_register",
   "address": 998,
   "documented": "0x03E6",
   "name": "AI-06_status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "normal",
    "1": "burnout",
    "2": "over range",
    "3": "under range"
   },
   "bits": null
  },
  {
   "table": "input_register",
   "address": 999,
   "documented": "0x03E7",
   "name": "AI-07_status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "normal",
    "1": "burnout",
    "2": "over range",
    "3": "under range"
   },
   "bits": null
  },
  {
   "table": "input_register",
   "address": 30000,
   "documented": "0x7530",
   "name": "SYS_modelID",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 30025,
   "documented": "0x7549",
   "name": "SYS_vendorID",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 30026,
   "documented": "0x754A",
   "name": "SYS_unitID",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 30037,
   "documented": "0x7555",
   "name": "SYS_productName",
   "description": "",
   "data_type": "STRING",
   "length": 10,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 30058,
   "documented": "0x756A",
   "name": "SYS_rs485PortMode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "initial-repeater",
    "1": "initial-dual RS- 485",
    "2": "run-repeater",
    "3": "run-dual RS-485"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 704,
   "documented": "0x02C0",
   "name": "AI-00_mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "0-10 V",
    "1": "0-20 mA",
    "2": "4-20 mA burnout",
    "3": "4-20 mA"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 705,
   "documented": "0x02C1",
   "name": "AI-01_mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "0-10 V",
    "1": "0-20 mA",
    "2": "4-20 mA burnout",
    "3": "4-20 mA"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 706,
   "documented": "0x02C2",
   "name": "AI-02_mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "0-10 V",
    "1": "0-20 mA",
    "2": "4-20 mA burnout",
    "3": "4-20 mA"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 707,
   "documented": "0x02C3",
   "name": "AI-03_mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "0-10 V",
    "1": "0-20 mA",
    "2": "4-20 mA burnout",
    "3": "4-20 mA"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 708,
   "documented": "0x02C4",
   "name": "AI-04_mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "0-10 V",
    "1": "0-20 mA",
    "2": "4-20 mA burnout",
    "3": "4-20 mA"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 709,
   "documented": "0x02C5",
   "name": "AI-05_mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "0-10 V",
    "1": "0-20 mA",
    "2": "4-20 mA burnout",
    "3": "4-20 mA"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 710,
   "documented": "0x02C6",
   "name": "AI-06_mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "0-10 V",
    "1": "0-20 mA",
    "2": "4-20 mA burnout",
    "3": "4-20 mA"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 711,
   "documented": "0x02C7",
   "name": "AI-07_mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "0-10 V",
    "1": "0-20 mA",
    "2": "4-20 mA burnout",
    "3": "4-20 mA"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 30052,
   "documented": "0x7564",
   "name": "SYS_modbusWatchdogFuntion",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disable",
    "1": "Enable"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 30053,
   "documented": "0x7565",
   "name": "SYS_modbusWatchdogTimeout",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 30054,
   "documented": "0x7566",
   "name": "SYS_modbusWatchdogStatus",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Normal",
    "1": "Timeout"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 30056,
   "documented": "0x7568",
   "name": "SYS_restartDevice",
   "description": "Write 404 to trigger.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 30057,
   "documented": "0x7569",
   "name": "SYS_loadFactoryDefault",
   "description": "Write 404 to trigger.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 30060,
   "documented": "0x756C",
   "name": "SYS_port0Baudrate",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "1": "1200",
    "2": "2400",
    "3": "4800",
    "4": "9600",
    "5": "19200",
    "6": "38400",
    "7": "57600",
    "8": "115200",
    "9": "921600"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 30061,
   "documented": "0x756D",
   "name": "SYS_port1Baudrate",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "1": "1200",
    "2": "2400",
    "3": "4800",
    "4": "9600",
    "5": "19200",
    "6": "38400",
    "7": "57600",
    "8": "115200",
    "9": "921600"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 30064,
   "documented": "0x7570",
   "name": "SYS_port0StopBit",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "1",
    "1": "2"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 30065,
   "documented": "0x7571",
   "name": "SYS_port1StopBit",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "1",
    "1": "2"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 30066,
   "documented": "0x7572",
   "name": "SYS_port0Parity",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "None",
    "1": "Even",
    "2": "Odd"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 30067,
   "documented": "0x7573",
   "name": "SYS_port1Parity",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "None",
    "1": "Even",
    "2": "Odd"
   },
   "bits": null
  }
 ],
 "integration": {
  "summary": "Read the raw analog values and channel status with function 04 and set each channel range with function 03/06. The host-connection watchdog (0x7564, timeout 0x7565) is shared by the whole series.",
  "minimum_registers": [
   {
    "table": "input_register",
    "address": 30000,
    "why": "Model ID check"
   },
   {
    "table": "holding_register",
    "address": 30052,
    "why": "Enable communication watchdog"
   },
   {
    "table": "holding_register",
    "address": 30053,
    "why": "Watchdog timeout"
   },
   {
    "table": "input_register",
    "address": 704,
    "why": "First analog input raw value"
   },
   {
    "table": "input_register",
    "address": 992,
    "why": "First analog input status"
   }
  ],
  "enable": "Set the device ID (1-99) on the two rotary dials. Put the Initial/Run switch on Initial to configure the unit at 9600 baud, no parity, 8 data bits, 1 stop bit (with ioSearch or the SYS_port* registers), then switch back to Run.",
  "watchdog": "SYS_modbusWatchdogFuntion (0x7564) enables the host-connection watchdog, SYS_modbusWatchdogTimeout (0x7565) sets the timeout in seconds (factory default 10 s), SYS_modbusWatchdogStatus (0x7566) shows a timeout. It is disabled by default; safe-status settings only act when it is enabled.",
  "quirks": [
   "System registers sit at 0x7530 and up (six-digit references 330001/430002).",
   "Write 404 to SYS_restartDevice or SYS_loadFactoryDefault to trigger them."
  ],
  "setup": [
   "Device ID 1-99 on the rotary dials (x1 and x10).",
   "The Dual/Rep switch selects two separate RS-485 ports or repeater mode; SYS_rs485PortMode reports which is active.",
   "Baud rate codes: 1=1200 ... 4=9600, 5=19200 ... 9=921600."
  ],
  "gotchas": [
   "Factory defaults (reset button held 5 s, ioSearch, or SYS_loadFactoryDefault) return the serial settings to 9600 n 8 1 and disable the watchdog."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/moxa/iologik-r1240",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}