 "manufacturer": "Neptronic",
 "manufacturer_slug": "neptronic",
 "model": "SKVF evaporative cooler / humidifier (Modbus communication module)",
 "model_slug": "skvf",
 "short_model": "SKVF",
 "aliases": [
  "SKVF Evaporative Cooler",
  "SKVF Series",
  "Neptronic SKVF Modbus"
 ],
 "equipment_type": "Air handler evaporative cooler (adiabatic cooling / humidification)",
 "applies_to": "Neptronic SKVF series evaporative coolers with the Modbus communication module, guide SKVF-Modbus Guide-211025.",
 "summary": "The Neptronic SKVF is an evaporative cooler that can run humidification or cooling control profiles. Its Modbus RTU module exposes holding registers only: signal voltages, room and supply RH and temperature readings, demand and output, humidity and cooling set points with PID terms, water supply, drain and drying settings, inputs and relays as 0/1 registers, and state, alarm, request and control-profile codes.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": null,
  "baud": null,
  "parity": "None",
  "data_bits": null,
  "stop_bits": 2,
  "tcp_port": null
 },
 "addressing": {
  "convention": "0-based",
  "note": "The guide prints a protocol-base (0-based) address and a six-digit holding register (base 400001) side by side, e.g. 6005 / 406006. The protocol-base number is the wire address."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "SKVF Evaporative Cooler - Modbus Communication Module User Guide",
  "doc_number": "SKVF-Modbus Guide-211025",
  "revision_date": "2021-10-25",
  "url": "https://www.neptronic.com/humidifiers/pdf/SKVF/20211208/SKVF-Modbus%20Guide-211025.pdf",
  "pages": "p. 1 (requirements), pp. 2-20 (Modbus registers table)"
 },
 "notes": [
  "Only function codes 03, 06 and 16 are supported, so binary points (inputs, relays, flags) are 16-bit holding registers holding 0 or 1.",
  "'Scale N' with 'Value x N' means the raw value is the engineering value times N; this map stores the multiplier 1/N.",
  "Temperature and capacity units follow Modbus Server Units (415001): 0 metric, 1 imperial.",
  "The guide text calls automatic baud detection the default, while register 1 lists 19200 as its default value; the baud default is left blank here.",
  "Default unit address is not stated; it is set from the device menu or register 0.",
  "Left out: product name ASCII registers 3-6; 2001 (a second 'Control Signal' row) and 15003/15004 (two rows both named 'Control Signal Type'), where it is unclear which is which; ECM Fan Signal 4001, RH and temperature Supply High Limit Proportional Band 6101/6111 (scale and example disagree); the temperature-control block 6004-6007 (names repeat Control Input/Min/Max/Bias and the example is in %); Room RH Bias 6011 and Room Temperature Network Reading 6082 (typed unsigned with negative ranges); Alarm LED / Power LED 11005/11006 (holding numbers 411004/411005 clash with the protocol column).",
  "Several values are printed as two- or four-register entries marked (0)...(3) - Demand, run/on/service time counters, Room Temperature Setpoint, Room RH and Room Temperature Demand Proportional Band/Gain, Water Supply Duty Cycle/Period, Water Treatment Service Interval, Keep Alive, Demand Low Dead Band and Network Timeout. No word order is given, so they are left out.",
  "System Power State (15000) is printed read-only in this guide."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 0,
   "documented": "0 / 400001",
   "name": "Modbus Address and Product Type",
   "description": "High byte = product type (read only); low byte = Modbus address 1-247 (writable).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1,
   "documented": "1 / 400002",
   "name": "Device Baud Rate",
   "description": "Baud rate / 100 (e.g. 384 = 38400); 0 = auto-detect.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 100,
   "units": "baud",
   "access": "RW",
   "values": {
    "0": "Auto baud rate detection"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "2 / 400003",
   "name": "Modbus Slave Communication Port Configuration",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No parity, 2 stop bits",
    "1": "Even parity, 1 stop bit",
    "2": "Odd parity, 1 stop bit"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 7,
   "documented": "7 / 400008",
   "name": "Product Actual Firmware Version (in Integer x100)",
   "description": "Firmware version x100 (e.g. 100 = 1.00).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8,
   "documented": "8 / 400009",
   "name": "Product Actual EEPROM Version (in Integer x100)",
   "description": "EEPROM version x100.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2000,
   "documented": "2000 / 402001",
   "name": "Control Signal",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.001,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2002,
   "documented": "2002 / 402003",
   "name": "Room RH Signal",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.001,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2003,
   "documented": "2003 / 402004",
   "name": "Room Temperature Signal",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.001,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2004,
   "documented": "2004 / 402005",
   "name": "Supply RH Signal",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.001,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2005,
   "documented": "2005 / 402006",
   "name": "Supply Temperature Signal",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.001,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2006,
   "documented": "2006 / 402007",
   "name": "ECM Fan Feedback",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2007,
   "documented": "2007 / 402008",
   "name": "ECM Fan Feedback 2",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2008,
   "documented": "2008 / 402009",
   "name": "Float Switch Signal",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.001,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2009,
   "documented": "2009 / 402010",
   "name": "Board Temperature Signal",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.001,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2010,
   "documented": "2010 / 402011",
   "name": "Main Power Supply",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4000,
   "documented": "4000 / 404001",
   "name": "Power Output Feedback Signal",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.001,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6000,
   "documented": "6000 / 406001",
   "name": "Control Input",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6001,
   "documented": "6001 / 406002",
   "name": "Control Min",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6002,
   "documented": "6002 / 406003",
   "name": "Control Max",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6003,
   "documented": "6003 / 406004",
   "name": "Control Bias",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6008,
   "documented": "6008 / 406009",
   "name": "Room RH",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%RH",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6009,
   "documented": "6009 / 406010",
   "name": "Room RH Min",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%RH",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6010,
   "documented": "6010 / 406011",
   "name": "Room RH Max",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%RH",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6012,
   "documented": "6012 / 406013",
   "name": "Room Temperature",
   "description": "Room temperature reading; printed as writable.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C / °F",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6013,
   "documented": "6013 / 406014",
   "name": "Room Temperature Min",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C / °F",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6014,
   "documented": "6014 / 406015",
   "name": "Room Temperature Max",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C / °F",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6015,
   "documented": "6015 / 406016",
   "name": "Room Temperature Bias",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C / °F",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6016,
   "documented": "6016 / 406017",
   "name": "Supply High Limit RH",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%RH",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6017,
   "documented": "6017 / 406018",
   "name": "Supply High Limit RH Min",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%RH",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6018,
   "documented": "6018 / 406019",
   "name": "Supply High Limit RH Max",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%RH",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6019,
   "documented": "6019 / 406020",
   "name": "Supply High Limit RH Bias",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6020,
   "documented": "6020 / 406021",
   "name": "Supply High Limit Temperature",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C / °F",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6021,
   "documented": "6021 / 406022",
   "name": "Supply High Limit Temperature Min",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C / °F",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6022,
   "documented": "6022 / 406023",
   "name": "Supply High Limit Temperature Max",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C / °F",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6023,
   "documented": "6023 / 406024",
   "name": "Supply High Limit Temperature Bias",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C / °F",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6028,
   "documented": "6028 / 406029",
   "name": "Power Output",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6045,
   "documented": "6045 / 406046",
   "name": "Dead Band",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6046,
   "documented": "6046 / 406047",
   "name": "Minimum Production Output",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6047,
   "documented": "6047 / 406048",
   "name": "Maximum Production Output",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6048,
   "documented": "6048 / 406049",
   "name": "Fan On Delay",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6049,
   "documented": "6049 / 406050",
   "name": "Dry Fan Speed",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6050,
   "documented": "6050 / 406051",
   "name": "Service Interval",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "h",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6051,
   "documented": "6051 / 406052",
   "name": "Dilution Ratio",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6052,
   "documented": "6052 / 406053",
   "name": "Drain Interval",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "h",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6053,
   "documented": "6053 / 406054",
   "name": "Fixed Drain Time",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "h",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6054,
   "documented": "6054 / 406055",
   "name": "Line Rinse Time",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6061,
   "documented": "6061 / 406062",
   "name": "Completely Dry Delay",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "h",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6062,
   "documented": "6062 / 406063",
   "name": "Hour of Day Drying Cycle",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "h",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6065,
   "documented": "6065 / 406066",
   "name": "HRL Temperature",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C / °F",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6066,
   "documented": "6066 / 406067",
   "name": "HRL Humidity",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%RH",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6067,
   "documented": "6067 / 406068",
   "name": "Board Temperature",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C / °F",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6068,
   "documented": "6068 / 406069",
   "name": "Power Output Feedback Bias",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.001,
   "units": "V",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6069,
   "documented": "6069 / 406070",
   "name": "Power Output Feedback Min",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.001,
   "units": "V",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6070,
   "documented": "6070 / 406071",
   "name": "Power Output Feedback Max",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.001,
   "units": "V",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6071,
   "documented": "6071 / 406072",
   "name": "Power Output Feedback",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6072,
   "documented": "6072 / 406073",
   "name": "Room RH Network Reading",
   "description": "Room RH written by the BAS when Room RH Source = Network.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%RH",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6073,
   "documented": "6073 / 406074",
   "name": "Room RH Setpoint",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%RH",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6074,
   "documented": "6074 / 406075",
   "name": "Room RH Unoccupied Setpoint",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%RH",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6075,
   "documented": "6075 / 406076",
   "name": "Room RH Vacant Setpoint",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%RH",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6076,
   "documented": "6076 / 406077",
   "name": "Room RH Demand Proportional Gain",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6077,
   "documented": "6077 / 406078",
   "name": "Room RH Demand Integral Time",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6078,
   "documented": "6078 / 406079",
   "name": "Room RH Demand Derivative Time",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6079,
   "documented": "6079 / 406080",
   "name": "Room RH Demand",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%RH",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6085,
   "documented": "6085 / 406086",
   "name": "Room Temperature Unoccupied Setpoint",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C / °F",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6086,
   "documented": "6086 / 406087",
   "name": "Room Temperature Vacant Setpoint",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C / °F",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6089,
   "documented": "6089 / 406090",
   "name": "Room Temperature Demand Integral Time",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6090,
   "documented": "6090 / 406091",
   "name": "Room Temperature Demand Derivative Time",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6091,
   "documented": "6091 / 406092",
   "name": "Room Temperature Demand",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6092,
   "documented": "6092 / 406093",
   "name": "Room Temp Demand Proportional Band",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6093,
   "documented": "6093 / 406094",
   "name": "RH Supply High Limit Network Reading",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%RH",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6094,
   "documented": "6094 / 406095",
   "name": "RH Supply High Limit Setpoint",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%RH",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6095,
   "documented": "6095 / 406096",
   "name": "RH Supply High Limit Unoccupied Setpoint",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%RH",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6096,
   "documented": "6096 / 406097",
   "name": "RH Supply High Limit Vacant Setpoint",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%RH",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6097,
   "documented": "6097 / 406098",
   "name": "RH Supply High Limit Proportional Gain",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6098,
   "documented": "6098 / 406099",
   "name": "RH Supply High Limit Integral Time",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6099,
   "documented": "6099 / 406100",
   "name": "RH Supply High Limit Derivative Time",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6100,
   "documented": "6100 / 406101",
   "name": "RH Supply High Limit Demand",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%RH",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6103,
   "documented": "6103 / 406104",
   "name": "Temp Supply High Limit Network Reading",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C / °F",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6104,
   "documented": "6104 / 406105",
   "name": "Temp Supply High Limit Setpoint",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C / °F",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6105,
   "documented": "6105 / 406106",
   "name": "Temp Supply High Limit Unoccupied Setpoint",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C / °F",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6106,
   "documented": "6106 / 406107",
   "name": "Temp Supply High Limit Vacant Setpoint",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C / °F",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6107,
   "documented": "6107 / 406108",
   "name": "Temp Supply High Limit Proportional Gain",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6108,
   "documented": "6108 / 406109",
   "name": "Temp Supply High Limit Integral Time",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6109,
   "documented": "6109 / 406110",
   "name": "Temp Supply High Limit Derivative Time",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6110,
   "documented": "6110 / 406111",
   "name": "Temp Supply High Limit Demand",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6112,
   "documented": "6112 / 406113",
   "name": "Control Network Demand",
   "description": "Demand written by the BAS when Control Demand Source = Network.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6113,
   "documented": "6113 / 406114",
   "name": "Control Network High Limit",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6114,
   "documented": "6114 / 406115",
   "name": "User Demand",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6119,
   "documented": "6119 / 406120",
   "name": "System Steam Capacity",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "kg/h / lb/h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10000,
   "documented": "10000 / 410001",
   "name": "Air Flow",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Closed",
    "1": "Open"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10001,
   "documented": "10001 / 410002",
   "name": "Supply High Limit",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Closed",
    "1": "Open"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10002,
   "documented": "10002 / 410003",
   "name": "Interlock",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Closed",
    "1": "Open"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10003,
   "documented": "10003 / 410004",
   "name": "Binary External Demand",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "0 %",
    "1": "100 %"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10004,
   "documented": "10004 / 410005",
   "name": "Water Leak Detection",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Ok",
    "1": "Leak"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10005,
   "documented": "10005 / 410006",
   "name": "RS485 Interface",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10006,
   "documented": "10006 / 410007",
   "name": "Ethernet Interface",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10007,
   "documented": "10007 / 410008",
   "name": "Relay Fuse",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Blown Fuse"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10008,
   "documented": "10008 / 410009",
   "name": "Control PCB Fuse",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Open Fuse"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11000,
   "documented": "11000 / 411001",
   "name": "Alarm Warning Relay",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11001,
   "documented": "11001 / 411002",
   "name": "Service Warning Relay",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11002,
   "documented": "11002 / 411003",
   "name": "Water Supply Valve",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11003,
   "documented": "11003 / 411004",
   "name": "Drain Valve",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11004,
   "documented": "11004 / 411005",
   "name": "Circulation Pump",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11007,
   "documented": "11007 / 411008",
   "name": "Buzzer",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 12000,
   "documented": "12000 / 412001",
   "name": "Network Control State",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Normal",
    "1": "Fault"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 12001,
   "documented": "12001 / 412002",
   "name": "Float Switch",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Inactive",
    "1": "Active"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 12002,
   "documented": "12002 / 412003",
   "name": "Water Treatment Service Due",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 12003,
   "documented": "12003 / 412004",
   "name": "Service Due",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Not Allowed",
    "1": "Allowed"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 12004,
   "documented": "12004 / 412005",
   "name": "Run While Water Service Alarm",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Not Allowed",
    "1": "Allowed"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 12005,
   "documented": "12005 / 412006",
   "name": "Startup Line Rinse",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 12006,
   "documented": "12006 / 412007",
   "name": "Run While Service Alarm",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Not Allowed",
    "1": "Allowed"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 12007,
   "documented": "12007 / 412008",
   "name": "HRL Lock Setpoint",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Unlock",
    "1": "Lock"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 12008,
   "documented": "12008 / 412009",
   "name": "Notify Alarm",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 12009,
   "documented": "12009 / 412010",
   "name": "Notify Warning",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 12010,
   "documented": "12010 / 412011",
   "name": "Notify App Msg",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 15000,
   "documented": "15000 / 415001",
   "name": "System Power State",
   "description": "Cooler on/off state (printed read-only).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 15001,
   "documented": "15001 / 415002",
   "name": "System Log Verbose Level",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "None",
    "1": "Emergency",
    "2": "Alert",
    "3": "Critical",
    "4": "Error",
    "5": "Warning",
    "6": "Notice",
    "7": "Info",
    "8": "Debug"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 15002,
   "documented": "15002 / 415003",
   "name": "Modbus Server Units",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Metric",
    "1": "Imperial"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 15005,
   "documented": "15005 / 415006",
   "name": "Room RH Signal Type",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "0-10Vdc",
    "1": "2-10Vdc",
    "2": "4-20mA",
    "3": "0-20mA"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 15006,
   "documented": "15006 / 415007",
   "name": "Room Temperature Signal Type",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "0-10Vdc",
    "1": "2-10Vdc",
    "2": "4-20mA",
    "3": "0-20mA"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 15007,
   "documented": "15007 / 415008",
   "name": "Supply RH Signal Type",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "0-10Vdc",
    "1": "2-10Vdc",
    "2": "4-20mA",
    "3": "0-20mA"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 15008,
   "documented": "15008 / 415009",
   "name": "Supply Temperature Signal Type",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "0-10Vdc",
    "1": "2-10Vdc",
    "2": "4-20mA",
    "3": "0-20mA"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 15009,
   "documented": "15009 / 415010",
   "name": "State",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "Idle",
    "2": "LineRinse",
    "3": "Filling",
    "4": "Draining",
    "5": "Running",
    "6": "Alarm",
    "7": "Drying"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 15010,
   "documented": "15010 / 415011",
   "name": "System Alarm",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "DrainTimeout",
    "2": "FillTimeout",
    "3": "WaterLeak",
    "4": "FanDefect"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 15011,
   "documented": "15011 / 415012",
   "name": "Recirculation Request",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "None",
    "1": "ResetAlarms",
    "2": "Drain",
    "3": "ResetServCnt",
    "4": "ResetWtrServCnt",
    "5": "Filling"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 15012,
   "documented": "15012 / 415013",
   "name": "DirectFeed Request",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "None",
    "1": "ResetAlarms",
    "3": "ResetServCnt",
    "4": "ResetWtrServCnt"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 15013,
   "documented": "15013 / 415014",
   "name": "Fan Request",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "Default",
    "2": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 15014,
   "documented": "15014 / 415015",
   "name": "Pump Request",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "Default",
    "2": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 15015,
   "documented": "15015 / 415016",
   "name": "Water Supply Request",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "Default",
    "2": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 15016,
   "documented": "15016 / 415017",
   "name": "Control Profile",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "ExternAnalog",
    "1": "ExternNetwork",
    "2": "InternHumAnalog",
    "3": "InternHumNetwork",
    "4": "InternCoolAnalog",
    "5": "InternCoolNetwork",
    "6": "HRLHum",
    "7": "HRLCool",
    "8": "Custom"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 15017,
   "documented": "15017 / 415018",
   "name": "Modulating High Limit Profile",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "ExternAnalog",
    "2": "ExternNetwork",
    "3": "InternHumAnalog",
    "4": "InternHumNetwork",
    "5": "InternCoolAnalog",
    "6": "InternCoolNetwork",
    "7": "Custom"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 15018,
   "documented": "15018 / 415019",
   "name": "Occupancy State",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Occupied",
    "1": "Unoccupied",
    "2": "Vacant",
    "3": "Off"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 15019,
   "documented": "15019 / 415020",
   "name": "Room RH Source",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "None",
    "1": "RoomRH",
    "2": "Network",
    "3": "HRL"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 15020,
   "documented": "15020 / 415021",
   "name": "Room RH Setpoint Source",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "None",
    "1": "Internal",
    "2": "ControlInput"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 15021,
   "documented": "15021 / 415022",
   "name": "Room Temperature Source",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "None",
    "1": "RoomTemp",
    "2": "Network",
    "3": "HRL"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 15022,
   "documented": "15022 / 415023",
   "name": "Room Temperature Setpoint Source",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "None",
    "1": "Internal",
    "2": "ControlInput"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 15023,
   "documented": "15023 / 415024",
   "name": "RH Supply High Limit Reading Source",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "None",
    "1": "SuppyHLRH",
    "2": "Network"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 15024,
   "documented": "15024 / 415025",
   "name": "RH Supply High Limit Setpoint Source",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "None",
    "1": "Internal",
    "2": "ControlInput"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 15025,
   "documented": "15025 / 415026",
   "name": "Temp Supply High Limit Reading Source",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "None",
    "1": "SuppyHLTemp",
    "2": "Network"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 15026,
   "documented": "15026 / 415027",
   "name": "Temp Supply High Limit Setpoint Source",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "None",
    "1": "Internal",
    "2": "ControlInput"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 15027,
   "documented": "15027 / 415028",
   "name": "Control Demand Source",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "None",
    "1": "ControlInput",
    "2": "RoomDemand",
    "3": "Network"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 15028,
   "documented": "15028 / 415029",
   "name": "Control High Limit Source",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "None",
    "1": "ControlInput",
    "2": "RHSupplyHLDemand",
    "3": "Network",
    "4": "TempSupplyHLDemand"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 15029,
   "documented": "15029 / 415030",
   "name": "Control Cutout State",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "Normal",
    "2": "LowLimit",
    "3": "HighLimit",
    "4": "NoAirFlow",
    "5": "Interlock"
   },
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Read Room RH (6008), Room Temperature (6012), Power Output (6028), State (15009) and System Alarm (15010). For BAS control choose a network Control Profile (15016) and Control Demand Source (15027 = Network) and write Control Network Demand (6112).",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 6008,
    "why": "Room RH"
   },
   {
    "table": "holding_register",
    "address": 6012,
    "why": "Room temperature"
   },
   {
    "table": "holding_register",
    "address": 6028,
    "why": "Power output"
   },
   {
    "table": "holding_register",
    "address": 6073,
    "why": "Room RH set point"
   },
   {
    "table": "holding_register",
    "address": 15009,
    "why": "Unit state"
   },
   {
    "table": "holding_register",
    "address": 15010,
    "why": "System alarm"
   },
   {
    "table": "holding_register",
    "address": 15016,
    "why": "Control profile"
   },
   {
    "table": "holding_register",
    "address": 6112,
    "why": "Network demand"
   }
  ],
  "enable": "Fit the Modbus communication module, set the address in the device menu (or register 0) and choose the control profile (15016) and sources (15019-15028) if the BAS supplies readings or demand.",
  "watchdog": "A Network Timeout exists but it is printed as a two-register value without word order (6117-6118), so it is not listed; Network Control State (12000) flags a network fault.",
  "quirks": [
   "All points, binary ones included, are holding registers (FC03/06/16 only).",
   "Default framing is no parity with 2 stop bits."
  ],
  "setup": [
   "RS-485 two-wire, RTU; 9600-57600 baud or auto baud detection.",
   "Parity/stop bits via register 2 or the Modbus Comport Config menu item."
  ],
  "gotchas": [
   "Control Profile chooses humidification (Hum) or cooling (Cool) logic; network profiles need the matching network registers written."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/neptronic/skvf",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}