 "manufacturer": "Neptronic",
 "manufacturer_slug": "neptronic",
 "model": "TUCB / TUHB Series universal wall-mount controller (Modbus RTU)",
 "model_slug": "tucb-tuhb-wall-mount-controller",
 "short_model": "TUCB / TUHB",
 "aliases": [
  "TUCB24C6X2",
  "TUHB24C6X2",
  "TUCB",
  "TUHB",
  "TUXB"
 ],
 "equipment_type": "Thermostat / heat pump and unitary controller",
 "applies_to": "Neptronic TUCB24C6X2 (temperature) and TUHB24C6X2 (temperature and humidity) universal wall-mount controllers with 6 binary and 2 analog outputs, guide TUXB-Modbus Guide-190515.",
 "summary": "The TUCB and TUHB are Neptronic wall-mount controllers with built-in sensors, six binary and two analog outputs, for fan coils, heat pumps (with reversing valve and emergency heat options) and other unitary equipment. Over Modbus RTU they expose temperatures, humidity (TUHB), CO2, ramp demands, output states, mode, fan and setpoint control and the configuration registers.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": null,
  "baud": null,
  "parity": null,
  "data_bits": null,
  "stop_bits": null,
  "tcp_port": null
 },
 "addressing": {
  "convention": "0-based",
  "note": "This older guide prints a \"Register Index\" with a 4 prefix starting at 40000. Its introduction places the device address at holding register index 0 and the baud rate at index 1, which the table shows as 40000 and 40001, so wire address = printed number - 40000 (not the usual 40001 rule)."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "TUCB & TUHB Series Universal Wall-Mount Controller Modbus Communication Module User Guide",
  "doc_number": "TUXB-Modbus Guide-190515",
  "revision_date": "2019-05-15",
  "url": "https://www.neptronic.com/Controls/PDF/20190515/TUXB-Modbus%20Guide-190515.pdf",
  "pages": "p. 1 (protocol, register index 0/1/2), pp. 2-16 (holding register table)"
 },
 "notes": [
  "Every register is a 16-bit holding register; there are no 32-bit values.",
  "Temperatures, setpoints and bands follow the Modbus temperature-unit bit of system option 1 (°C or °F); sensor readings and offsets are x100, setpoints and bands x10.",
  "Do not apply the 40001 rule: in this guide 40000 is register 0.",
  "Left out: the four ASCII product-name registers and register 40042 (all bits reserved)."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 0,
   "documented": "40000",
   "name": "Address - Neptronic ID and Modbus address of current device",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1,
   "documented": "40001",
   "name": "Baud rate (baud / 100)",
   "description": "0 = automatic detection.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 100,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "40002",
   "name": "Communication port configuration",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "No parity, 2 Stop bits",
    "2": "Even parity, 1 stop bit",
    "3": "Odd parity, 1 stop bit"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 7,
   "documented": "40007",
   "name": "Controller Product_Version, actual firmware version",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8,
   "documented": "40008",
   "name": "Controller parameters version",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9,
   "documented": "40009",
   "name": "System Status 1",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "System operation (0 = Normal, 1 = Fault)",
    "2": "System override by NSB or OCC (0 = Normal, 1 = OFF)",
    "3": "ChangeOverMode (0 = Cooling, 1 = Heating)",
    "4": "AL_FlowSwitch (0 = No alarm, 1 = Alarm activated)",
    "6": "AL_DirtyFilter (0 = No alarm, 1 = Alarm activated)"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10,
   "documented": "40010",
   "name": "System Status 2",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Selector Switch Status (0 = Remote Mode, 1 = Local Mode)",
    "2": "CO2 Alarm (0 = Normal, 1 = Alarm)",
    "7": "AL_Override (0 = Off, 1 = On)",
    "8": "AL_WindowOpened (0 = Off, 1 = On)",
    "9": "AL_DoorOpened (0 = Off, 1 = On)",
    "10": "AL_BI1 (0 = Off, 1 = On)",
    "11": "AL_BI2 (0 = Off, 1 = On)",
    "12": "AL_AI1 (0 = Off, 1 = On)",
    "13": "AL_AI2 (0 = Off, 1 = On)",
    "15": "AL_OverHeat (0 = Off, 1 = On)"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11,
   "documented": "40011",
   "name": "Internal temperature sensor reading",
   "description": "Unit follows the Modbus temperature-unit option (°C or °F).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C / °F",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 12,
   "documented": "40012",
   "name": "External temperature sensor reading",
   "description": "Unit follows the Modbus temperature-unit option (°C or °F).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C / °F",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 13,
   "documented": "40013",
   "name": "Changeover temperature sensor reading",
   "description": "Unit follows the Modbus temperature-unit option (°C or °F).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C / °F",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14,
   "documented": "40014",
   "name": "Control temperature reading",
   "description": "Unit follows the Modbus temperature-unit option (°C or °F).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C / °F",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 15,
   "documented": "40015",
   "name": "Internal humidity sensor reading",
   "description": "TUHB24C6X2 only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%RH",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16,
   "documented": "40016",
   "name": "External humidity sensor reading",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%RH",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 17,
   "documented": "40017",
   "name": "Analog input 1 reading",
   "description": "Volts or temperature, depending on how the input is configured.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "V / °C / °F",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 18,
   "documented": "40018",
   "name": "Analog input 2 reading",
   "description": "Volts or temperature, depending on how the input is configured.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "V / °C / °F",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 19,
   "documented": "40019",
   "name": "CO2 sensor value in ppm",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "ppm",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 20,
   "documented": "40020",
   "name": "Binary input statuses of 2 binary inputs",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Binary Input 1 (0 = Open, 1 = Close)",
    "1": "Binary Input 2 (0 = Open, 1 = Close)"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 21,
   "documented": "40021",
   "name": "Actual system occupancy state",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "1": "NoOccupancy",
    "2": "Occupancy",
    "3": "Override"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 22,
   "documented": "40022",
   "name": "Actual night setback state of the system",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "1": "Day",
    "2": "Night",
    "3": "Override"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 23,
   "documented": "40023",
   "name": "Actual heating demand of ramp 1",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 24,
   "documented": "40024",
   "name": "Actual heating demand of ramp 2",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 25,
   "documented": "40025",
   "name": "Actual cooling demand of ramp 1",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 26,
   "documented": "40026",
   "name": "Actual cooling demand of ramp 2",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 27,
   "documented": "40027",
   "name": "Actual changeover demand",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 28,
   "documented": "40028",
   "name": "Actual fan demand",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 29,
   "documented": "40029",
   "name": "Actual dehumidification demand",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 30,
   "documented": "40030",
   "name": "Actual humidification demand",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 31,
   "documented": "40031",
   "name": "Cooling/heating switch timer countdown",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 32,
   "documented": "40032",
   "name": "Analog output 1 value",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 33,
   "documented": "40033",
   "name": "Analog output 2 value",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 34,
   "documented": "40034",
   "name": "Binary output - 6 relays output status",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Binary Output 1 (0 = Open, 1 = Close)",
    "1": "Binary Output 2 (0 = Open, 1 = Close)",
    "2": "Binary Output 3 (0 = Open, 1 = Close)",
    "3": "Binary Output 4 (0 = Open, 1 = Close)",
    "4": "Binary Output 5 (0 = Open, 1 = Close)",
    "5": "Binary Output 6 (0 = Open, 1 = Close)"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 35,
   "documented": "40035",
   "name": "System command",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Cfg_ServiceDisplayAddress (0 = Normal, 1 = Display address on LCD)",
    "1": "Cfg_CoolingRampLock (0 = Off, 1 = On)",
    "3": "Cfg_HeatingRamp1Lock (0 = Off, 1 = On)",
    "4": "Cfg_HeatingRamp2Lock (0 = Off, 1 = On)",
    "5": "Cfg_ChangeOverRampLock (0 = Off, 1 = On)",
    "7": "Cfg_HumidifyRampLock (0 = Off, 1 = On)",
    "8": "Cfg_DehumidifyRampLock (0 = Off, 1 = On)"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 36,
   "documented": "40036",
   "name": "System mode status",
   "description": "Each mode is only accepted when the system control mode and option bits allow it.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Auto",
    "2": "Heating",
    "3": "Emergency heat (EMH)",
    "4": "Cooling",
    "5": "Fan",
    "6": "Off"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 37,
   "documented": "40037",
   "name": "Fan speed selection by user",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Auto",
    "2": "Low",
    "3": "Med",
    "4": "High"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 38,
   "documented": "40038",
   "name": "Temperature setpoint in occupancy or day mode",
   "description": "Unit follows the Modbus temperature-unit option (°C or °F).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C / °F",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 39,
   "documented": "40039",
   "name": "System option 1",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Cfg_TempUnitTstat (0 = °C, 1 = °F)",
    "1": "Cfg_TempUnitModbus (0 = °C, 1 = °F)",
    "2": "Cfg_TempSetPointLock (0 = Off, 1 = On)",
    "3": "Cfg_HumSetPointLock (0 = Off, 1 = On)",
    "4": "Cfg_ProgramModeLock (0 = Off, 1 = On)",
    "7": "AL_FreezeProtection (0 = Off, 1 = On)",
    "8": "Cfg_UserSysOffModes (0 = Enable, 1 = Disable)",
    "9": "Cfg_KeyPadBottomLeftLock (0 = Off, 1 = On)",
    "10": "Cfg_KeyPadUpperLeftLock (0 = Off, 1 = On)",
    "11": "Cfg_KeyPadArrowsLock (0 = Off, 1 = On)",
    "12": "Cfg_UserFanAutoMode (0 = Enable, 1 = Disable)",
    "13": "Cfg_ NightOrNoOccMode (0 = Setpoint, 1 = OFF)",
    "14": "Cfg_HumControlSource (0 = Intern Sensor, 1 = Extern Sensor (Writable only if an intern RH option is available) Only available on model TUHB24C6X2.)",
    "15": "Time Mode (0 = 24h, 1 = 12h)"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 40,
   "documented": "40040",
   "name": "System option 2",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Cfg_WindowOpenedMode (0 = Setpoint, 1 = OFF)",
    "1": "Cfg_DoorOpenedMode (0 = Setpoint, 1 = OFF)",
    "2": "Baud Rate (0 = Auto, 1 = Manual)",
    "3": "Cfg_ActivateSchedule (0 = Off, 1 = On)",
    "4": "Cfg_AnalogOutput1Direction (0 = Direct, 1 = Reverse)",
    "5": "Cfg_AnalogOutput2Direction (0 = Direct, 1 = Reverse)",
    "6": "Cfg_BinaryOutput1Direction (0 = Direct, 1 = Reverse)",
    "7": "Cfg_BinaryOutput2Direction (0 = Direct, 1 = Reverse)",
    "8": "Cfg_BinaryOutput3Direction (0 = Direct, 1 = Reverse)",
    "9": "Cfg_BinaryOutput4Direction (0 = Direct, 1 = Reverse)",
    "10": "Cfg_BinaryOutput5Direction (0 = Direct, 1 = Reverse)",
    "11": "Cfg_BinaryOutput6Direction (0 = Direct, 1 = Reverse)",
    "12": "Cfg_ FanSpeedOption (0 = Standard, 1 = Advanced (OE1))",
    "13": "Cfg_UserSysFanMode (0 = Disable, 1 = Enable)",
    "14": "Cfg_HideFanDisplay (0 = N0, 1 = Yes)"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 41,
   "documented": "40041",
   "name": "System option 3",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "DAYLIGHT_SAVINGS_STATUS (0 = Normal, 1 = Summer)",
    "1": "Cfg_EMHOutput (0 = Disable, 1 = Enable)",
    "2": "Cfg_ HeatPumpMode (0 = Off (General Unit), 1 = On (HeatPump))",
    "3": "Cfg_ReversingValve (O/B) (0 = O, 1 = B)",
    "4": "Cfg_EMHAutoMode (0 = No, 1 = Yes)",
    "5": "Cfg_Y2Output (0 = Disable, 1 = Enable)"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 43,
   "documented": "40043",
   "name": "Display information",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Temperature and Demand",
    "2": "Setpoint and Demand",
    "3": "Temperature Only",
    "4": "Setpoint Only",
    "5": "Off"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 44,
   "documented": "40044",
   "name": "Temperature control source",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Network Temp",
    "2": "Intern Temp",
    "3": "Extern Temp"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 45,
   "documented": "40045",
   "name": "Network fallback timeout",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 46,
   "documented": "40046",
   "name": "Minimum occupancy/day setpoint",
   "description": "Unit follows the Modbus temperature-unit option (°C or °F).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C / °F",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 47,
   "documented": "40047",
   "name": "Maximum occupancy/day setpoint",
   "description": "Unit follows the Modbus temperature-unit option (°C or °F).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C / °F",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 48,
   "documented": "40048",
   "name": "Cooling temperature setpoint in unoccupied or night mode",
   "description": "Unit follows the Modbus temperature-unit option (°C or °F).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C / °F",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 49,
   "documented": "40049",
   "name": "Heating temperature setpoint in unoccupied or night mode",
   "description": "Unit follows the Modbus temperature-unit option (°C or °F).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C / °F",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 50,
   "documented": "40050",
   "name": "Heating proportional band for ramp 1",
   "description": "Unit follows the Modbus temperature-unit option (°C or °F).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C / °F",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 51,
   "documented": "40051",
   "name": "Heating proportional band for ramp 2",
   "description": "Unit follows the Modbus temperature-unit option (°C or °F).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C / °F",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 52,
   "documented": "40052",
   "name": "Cooling proportional band for ramp 1",
   "description": "Unit follows the Modbus temperature-unit option (°C or °F).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C / °F",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 53,
   "documented": "40053",
   "name": "Cooling proportional band for ramp 2",
   "description": "Unit follows the Modbus temperature-unit option (°C or °F).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C / °F",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 54,
   "documented": "40054",
   "name": "Changeover proportional band",
   "description": "Unit follows the Modbus temperature-unit option (°C or °F).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C / °F",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 55,
   "documented": "40055",
   "name": "Heating deadband for ramp 1",
   "description": "Unit follows the Modbus temperature-unit option (°C or °F).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C / °F",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 56,
   "documented": "40056",
   "name": "Heating deadband for ramp 2",
   "description": "Unit follows the Modbus temperature-unit option (°C or °F).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C / °F",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 57,
   "documented": "40057",
   "name": "Cooling deadband for ramp 1",
   "description": "Unit follows the Modbus temperature-unit option (°C or °F).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C / °F",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 58,
   "documented": "40058",
   "name": "Cooling deadband for ramp 2",
   "description": "Unit follows the Modbus temperature-unit option (°C or °F).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C / °F",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 59,
   "documented": "40059",
   "name": "Changeover deadband",
   "description": "Unit follows the Modbus temperature-unit option (°C or °F).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C / °F",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 60,
   "documented": "40060",
   "name": "Changeover setpoint",
   "description": "Unit follows the Modbus temperature-unit option (°C or °F).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C / °F",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 61,
   "documented": "40061",
   "name": "Fan time out in seconds",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 62,
   "documented": "40062",
   "name": "Fan damping factor in seconds",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 63,
   "documented": "40063",
   "name": "Heating integral time factor in seconds",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64,
   "documented": "40064",
   "name": "Cooling integral time factor in seconds",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 65,
   "documented": "40065",
   "name": "Delay between cooling and heating",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 66,
   "documented": "40066",
   "name": "Cooling anticycle delay in minutes",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 67,
   "documented": "40067",
   "name": "NSB override delay in minutes",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 68,
   "documented": "40068",
   "name": "Unoccupied override delay in minutes",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 69,
   "documented": "40069",
   "name": "Occupancy minimum time in minutes",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 70,
   "documented": "40070",
   "name": "Unoccupied override delay count down in minutes",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 71,
   "documented": "40071",
   "name": "Fan mode (speed) in unoccupied or NSB mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Low",
    "2": "Med",
    "3": "High",
    "4": "Auto"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 72,
   "documented": "40072",
   "name": "Fan mode (speed) when window is opened (alarm)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Low",
    "2": "Med",
    "3": "High",
    "4": "Auto"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 73,
   "documented": "40073",
   "name": "Fan mode (speed) when door is opened (alarm)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Low",
    "2": "Med",
    "3": "High",
    "4": "Auto"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 74,
   "documented": "40074",
   "name": "System control mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Auto",
    "2": "Heat",
    "3": "Cool",
    "4": "Heat or Cool",
    "5": "Auto Lock"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 75,
   "documented": "40075",
   "name": "Override System occupancy/NSB mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Locally",
    "2": "OFF",
    "3": "Occupied",
    "4": "Unoccupied",
    "5": "Day",
    "6": "Night"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 76,
   "documented": "40076",
   "name": "Internal temperature sensor offset correction",
   "description": "Unit follows the Modbus temperature-unit option (°C or °F).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C / °F",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 77,
   "documented": "40077",
   "name": "Analog Input 1 signal",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "OFF",
    "2": "Extern sensor 10K",
    "3": "Change over sensor",
    "4": "Change over normally cool",
    "5": "Change over normally heat",
    "6": "Outside air sensor",
    "7": "Extern sensor 0-10V",
    "8": "CO2 sensor 0-10V",
    "9": "Occupancy binary input",
    "10": "NSB binary input",
    "11": "Override binary input",
    "12": "Window binary input",
    "13": "Door binary input",
    "14": "Dirty Filter binary input",
    "15": "Flow switch binary input",
    "16": "OverHeat binary input",
    "17": "Selector switch binary input",
    "18": "Humidity sensor 0-10V"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 78,
   "documented": "40078",
   "name": "Analog Input 2 signal",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "OFF",
    "2": "Extern sensor 10K",
    "3": "Change over sensor",
    "4": "Change over normally cool",
    "5": "Change over normally heat",
    "6": "Outside air sensor",
    "7": "Extern sensor 0-10V",
    "8": "CO2 sensor 0-10V",
    "9": "Occupancy binary input",
    "10": "NSB binary input",
    "11": "Override binary input",
    "12": "Window binary input",
    "13": "Door binary input",
    "14": "Dirty Filter binary input",
    "15": "Flow switch binary input",
    "16": "OverHeat binary input",
    "17": "Selector switch binary input",
    "18": "Humidity sensor 0-10V"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 79,
   "documented": "40079",
   "name": "External temperature sensor offset correction",
   "description": "Unit follows the Modbus temperature-unit option (°C or °F).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C / °F",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 80,
   "documented": "40080",
   "name": "Changeover control mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Local",
    "2": "Cool",
    "3": "Heat"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 81,
   "documented": "40081",
   "name": "Minimum external temperature reading",
   "description": "Unit follows the Modbus temperature-unit option (°C or °F).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C / °F",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 82,
   "documented": "40082",
   "name": "Maximum external temperature reading",
   "description": "Unit follows the Modbus temperature-unit option (°C or °F).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C / °F",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 83,
   "documented": "40083",
   "name": "Maximum CO2 reading",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "ppm",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 84,
   "documented": "40084",
   "name": "Alarm level of CO2",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "ppm",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 85,
   "documented": "40085",
   "name": "Fan output signal",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "1 speed",
    "2": "2 speeds",
    "3": "3 speeds",
    "4": "Analog",
    "5": "VFD"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 86,
   "documented": "40086",
   "name": "Ramp to control analog output 1",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Off",
    "2": "Changeover with fan",
    "3": "Cooling 1 with fan",
    "4": "Cooling 2 with fan",
    "5": "Heating 1 with fan",
    "6": "Heating 2 with fan",
    "7": "Heating 2",
    "8": "Cooling 1 Heating 1 With Fan",
    "9": "HumidifyWithFan",
    "10": "CO2 alarm",
    "11": "6 way valve"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 87,
   "documented": "40087",
   "name": "Minimum voltage for analog output 1 (volt)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "V",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 88,
   "documented": "40088",
   "name": "Maximum voltage for analog output 1 (volt)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "V",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 89,
   "documented": "40089",
   "name": "Ramp to control analog output 2",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Off",
    "2": "Changeover with fan",
    "3": "Cooling 1 with fan",
    "4": "Cooling 2 with fan",
    "5": "Heating 1 with fan",
    "6": "Heating 2 with fan",
    "7": "Heating 2",
    "8": "Cooling 1 Heating 1 With Fan",
    "9": "HumidifyWithFan",
    "10": "CO2 alarm",
    "11": "6 way valve",
    "12": "FAN"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 90,
   "documented": "40090",
   "name": "Minimum voltage for analog output 2 (volt)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "V",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 91,
   "documented": "40091",
   "name": "Maximum voltage for analog output 2 (volt)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "V",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 92,
   "documented": "40092",
   "name": "Position of CH1 AO output while heating (%)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 93,
   "documented": "40093",
   "name": "Ramp to control binary output 1",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Off",
    "2": "Changeover with fan",
    "3": "Cooling 1 with fan",
    "4": "Cooling 2 with fan",
    "5": "Heating 1 with fan",
    "6": "Heating 2 with fan",
    "7": "Heating 2",
    "8": "Cooling 1 Heating 1 With Fan",
    "9": "HumidifyWithFan",
    "10": "CO2 alarm"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 94,
   "documented": "40094",
   "name": "Delay before activation of BO1 in minutes",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 95,
   "documented": "40095",
   "name": "Close position percentage for contact BO1",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 96,
   "documented": "40096",
   "name": "Open position percentage for contact BO1",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 97,
   "documented": "40097",
   "name": "Ramp to control binary output 2",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Off",
    "2": "Changeover with fan",
    "3": "Cooling 1 with fan",
    "4": "Cooling 2 with fan",
    "5": "Heating 1 with fan",
    "6": "Heating 2 with fan",
    "7": "Heating 2",
    "8": "Cooling 1 Heating 1 With Fan",
    "9": "HumidifyWithFan",
    "10": "CO2 alarm"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 98,
   "documented": "40098",
   "name": "Delay before activation of BO2 in minutes",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 99,
   "documented": "40099",
   "name": "Close position percentage for contact BO2",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 100,
   "documented": "40100",
   "name": "Open position percentage for contact BO2",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 101,
   "documented": "40101",
   "name": "Ramp to control binary output 3",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Off",
    "2": "Changeover with fan",
    "3": "Cooling 1 with fan",
    "4": "Cooling 2 with fan",
    "5": "Heating 1 with fan",
    "6": "Heating 2 with fan",
    "7": "Heating 2",
    "8": "Cooling 1 Heating 1 With Fan",
    "9": "HumidifyWithFan",
    "10": "CO2 alarm"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 102,
   "documented": "40102",
   "name": "Delay before activation of BO3 in minutes",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 103,
   "documented": "40103",
   "name": "Close position percentage for contact BO3",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 104,
   "documented": "40104",
   "name": "Open position percentage for contact BO3",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 105,
   "documented": "40105",
   "name": "Ramp to control binary output 4",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Off",
    "2": "Changeover with fan",
    "3": "Cooling 1 with fan",
    "4": "Cooling 2 with fan",
    "5": "Heating 1 with fan",
    "6": "Heating 2 with fan",
    "7": "Heating 2",
    "8": "Cooling 1 Heating 1 With Fan",
    "9": "HumidifyWithFan",
    "10": "CO2 alarm",
    "11": "FAN"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 106,
   "documented": "40106",
   "name": "Delay before activation of BO4 in minutes",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 107,
   "documented": "40107",
   "name": "Close position percentage for contact BO4",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 108,
   "documented": "40108",
   "name": "Open position percentage for contact BO4",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 109,
   "documented": "40109",
   "name": "Ramp to control binary output 5",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Off",
    "2": "Changeover with fan",
    "3": "Cooling 1 with fan",
    "4": "Cooling 2 with fan",
    "5": "Heating 1 with fan",
    "6": "Heating 2 with fan",
    "7": "Heating 2",
    "8": "Cooling 1 Heating 1 With Fan",
    "9": "HumidifyWithFan",
    "10": "CO2 alarm",
    "11": "FAN"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 110,
   "documented": "40110",
   "name": "Delay before activation of BO5 in minutes",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 111,
   "documented": "40111",
   "name": "Close position percentage for contact BO5",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 112,
   "documented": "40112",
   "name": "Open position percentage for contact BO5",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 113,
   "documented": "40113",
   "name": "Ramp to control binary output 6",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Off",
    "2": "Changeover with fan",
    "3": "Cooling 1 with fan",
    "4": "Cooling 2 with fan",
    "5": "Heating 1 with fan",
    "6": "Heating 2 with fan",
    "7": "Heating 2",
    "8": "Cooling 1 Heating 1 With Fan",
    "9": "HumidifyWithFan",
    "10": "CO2 alarm",
    "11": "FAN (only when the fan type is 1, 2 or 3 speeds)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 114,
   "documented": "40114",
   "name": "Delay before activation of BO6 in minutes",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 115,
   "documented": "40115",
   "name": "Close position percentage for contact BO6",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 116,
   "documented": "40116",
   "name": "Open position percentage for contact BO6",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 117,
   "documented": "40117",
   "name": "Input contact of binary input 1, 2 and analog input 1, 2",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Binary input 1 (0 = Normally Open, 1 = Normally Close)",
    "1": "Binary input 2 (0 = Normally Open, 1 = Normally Close)",
    "2": "Analog input 1 (0 = Normally Open, 1 = Normally Close)",
    "3": "Analog input 2 (0 = Normally Open, 1 = Normally Close)"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 118,
   "documented": "40118",
   "name": "Configuration of binary input 1 mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "OFF",
    "2": "Override",
    "3": "Window",
    "4": "Door",
    "5": "DirtyFilter",
    "6": "FlowSwitch",
    "7": "OverHeat",
    "8": "Selector switch (use together with a flow switch; fan stays off in local mode)",
    "9": "Change over normally cool",
    "10": "Change over normally heat",
    "11": "NSB",
    "12": "Occupancy"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 119,
   "documented": "40119",
   "name": "Delay before activation of BI1 in seconds",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 120,
   "documented": "40120",
   "name": "Configuration of binary input 2 mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "OFF",
    "2": "Override",
    "3": "Window",
    "4": "Door",
    "5": "DirtyFilter",
    "6": "FlowSwitch",
    "7": "OverHeat",
    "8": "Selector switch (use together with a flow switch; fan stays off in local mode)",
    "9": "Change over normally cool",
    "10": "Change over normally heat",
    "11": "NSB",
    "12": "Occupancy"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 121,
   "documented": "40121",
   "name": "Delay before activation of BI2 in seconds",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 122,
   "documented": "40122",
   "name": "Delay before activation of AI1 in seconds",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 123,
   "documented": "40123",
   "name": "Delay before activation of AI2 in seconds",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 124,
   "documented": "40124",
   "name": "Humidity control mode status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Auto",
    "2": "Dehumidification",
    "3": "Humidification",
    "4": "Off"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 125,
   "documented": "40125",
   "name": "Humidity setpoint (%RH) in occupancy or day mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%RH",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 126,
   "documented": "40126",
   "name": "Dehumidification setpoint (%RH) in unoccupied or night mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%RH",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 127,
   "documented": "40127",
   "name": "Humidification setpoint (%RH) in unoccupied or night mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%RH",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 128,
   "documented": "40128",
   "name": "Minimum user setpoint",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%RH",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 129,
   "documented": "40129",
   "name": "Maximum user setpoint",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%RH",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 130,
   "documented": "40130",
   "name": "Humidity proportional band",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%RH",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 131,
   "documented": "40131",
   "name": "Humidity deadband",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%RH",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 132,
   "documented": "40132",
   "name": "Internal humidity sensor offset correction",
   "description": "TUHB24C6X2 only.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%RH",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 133,
   "documented": "40133",
   "name": "External humidity sensor offset correction",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%RH",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 134,
   "documented": "40134",
   "name": "Voltage required for closing the 6-way valve",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "V",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 135,
   "documented": "40135",
   "name": "Minimum output voltage required for cooling for the 6-way valve",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "V",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 136,
   "documented": "40136",
   "name": "Minimum output voltage required for heating for the 6-way valve",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "V",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 137,
   "documented": "40137",
   "name": "6-way valve size selection in inches",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "1/2",
    "2": "3/4",
    "3": "1"
   },
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Read holding registers with function 03 at the printed register index minus 40000 (40011 = address 11). Set the temperature unit for Modbus first, then use the mode, fan and setpoint registers for control.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 11,
    "why": "Internal (room) temperature x100"
   },
   {
    "table": "holding_register",
    "address": 14,
    "why": "Control temperature x100"
   },
   {
    "table": "holding_register",
    "address": 36,
    "why": "System mode"
   },
   {
    "table": "holding_register",
    "address": 37,
    "why": "Fan speed"
   },
   {
    "table": "holding_register",
    "address": 38,
    "why": "Occupied setpoint x10"
   },
   {
    "table": "holding_register",
    "address": 23,
    "why": "Heating demand ramp 1"
   },
   {
    "table": "holding_register",
    "address": 25,
    "why": "Cooling demand ramp 1"
   },
   {
    "table": "holding_register",
    "address": 9,
    "why": "Status 1"
   },
   {
    "table": "holding_register",
    "address": 10,
    "why": "Status 2 (alarms)"
   },
   {
    "table": "holding_register",
    "address": 39,
    "why": "System option 1 (bit 1 = Modbus temp unit)"
   }
  ],
  "enable": "Modbus is the controller's native protocol; set the address (1-246) and, if needed, a fixed baud rate and parity from the device menu or registers 0-2.",
  "watchdog": null,
  "quirks": [
   "The table prints a 4 prefix on a 0-based register index (40000 = address 0), not the 40001 Modicon convention.",
   "Baud register holds baud/100 (384 = 38400); 0 means automatic baud detection."
  ],
  "setup": [
   "RS-485 two-wire, RTU. Supported baud rates 9600, 19200, 38400 and 57600; automatic baud detection is the default.",
   "Parity/stop bits come from the communication-port register: 1 = none + 2 stop, 2 = even + 1 stop, 3 = odd + 1 stop."
  ],
  "gotchas": [
   "Changing the Modbus temperature-unit bit changes the meaning of every temperature register at once.",
   "Some registers only apply to models with a humidity, CO2 or other optional sensor."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/neptronic/tucb-tuhb-wall-mount-controller",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}