 "manufacturer": "New Cosmos Electric",
 "manufacturer_slug": "new-cosmos",
 "model": "PS-7-M series extractive pump gas detector (Modbus RTU / TCP)",
 "model_slug": "ps-7-m",
 "short_model": "PS-7-M",
 "aliases": [
  "PS-7-M",
  "PS-7"
 ],
 "equipment_type": "Sensor (fixed gas detector)",
 "applies_to": "New Cosmos PS-7-M series extractive pump gas detectors (main unit with base unit) over RS-485 Modbus RTU or Ethernet Modbus TCP, communication specifications guide GAE-159-01.",
 "summary": "The New Cosmos PS-7-M is a pump-type fixed gas detector whose base unit has RS-485 Modbus RTU and Ethernet Modbus TCP ports. All data are 16-bit holding registers: current gas concentration, full-scale code, a packed device status word with alarm and fault flags, alarm settings, test and maintenance mode controls and identity data. This map covers the main published registers.",
 "transport": [
  "RTU",
  "TCP"
 ],
 "defaults": {
  "unit_id": null,
  "baud": 9600,
  "parity": "None",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": 502
 },
 "addressing": {
  "convention": "Modicon",
  "note": "The table gives each register as a Modicon number (40001-41321) plus a relative address in hex that goes on the wire: 40001 = relative 0, 41039 = relative 0x40E (1038). The manual's examples read 41039 at relative address 1038."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "PS-7-M Communication Specifications Guide",
  "doc_number": "GAE-159-01",
  "revision_date": "2024-04",
  "url": "https://dodtec.com/amfile/file/download/file/357/product/351/",
  "unofficial": true,
  "pages": "pp. 8-9 printed (RS-485 and TCP specifications), pp. 42-48 printed (register address map, PDF pp. 46-52), p. 55 printed (full-scale code table)"
 },
 "notes": [
  "The guide is a New Cosmos document hosted by the US distributor DOD Technologies; New Cosmos does not offer it as a public download.",
  "All registers are single 16-bit words. Strings carry two ASCII characters per register, first character in the high byte.",
  "Gas concentration (41039) is an unsigned magnitude; status bit 15 (bit 7 of status byte 1) gives the sign (manual example: 5 with the sign bit set = -5 %). Its unit comes from register 40011 and its full scale from the F.S. code at 41040.",
  "Device status 40516: status byte 1 is the high byte and status byte 2 the low byte (manual example 0x0302 = AL1 and AL2 active while in maintenance mode 2).",
  "Left out: f-value and calibration gas code (ASCII), linear table X/Y pairs (two 8-bit values per register), 41284 Modbus setting change permit (meaning of the value not given), and the IP address/mask/gateway registers 41291-41299.",
  "RS-485 settings are fixed: 9600 baud, 8 data bits, no parity, 1 stop bit. The unit ID (1-254) is set on DIP switches and is also the last octet of the IP address for Modbus TCP."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 0,
   "documented": "40001",
   "name": "Flow rate",
   "description": "Current pump flow (e.g. 500 = 500 ml).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "ml",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1,
   "documented": "40002",
   "name": "AL1 set value",
   "description": "Percent of full scale.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%F.S.",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "40003",
   "name": "AL2 set value",
   "description": "Percent of full scale.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%F.S.",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3,
   "documented": "40004",
   "name": "Alarm mode combination",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "High-High limit",
    "1": "Low-Low limit",
    "2": "High-Low limit"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4,
   "documented": "40005",
   "name": "AL1 delay time",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5,
   "documented": "40006",
   "name": "AL2 delay time",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6,
   "documented": "40007",
   "name": "Zero suppression value",
   "description": "21 vol% suppression value for oxygen sensors.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8,
   "documented": "40009-40010",
   "name": "Target gas",
   "description": "Up to 4 ASCII characters, first character in the high byte.",
   "data_type": "STRING",
   "length": 2,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10,
   "documented": "40011",
   "name": "Measurement unit code",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "None",
    "10": "ppm",
    "20": "ppb",
    "30": "%",
    "40": "%LEL"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 12,
   "documented": "40013-40016",
   "name": "Sensor unit Mfg. No.",
   "description": "8 ASCII characters, first in the high byte.",
   "data_type": "STRING",
   "length": 4,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16,
   "documented": "40017",
   "name": "Test mode status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 17,
   "documented": "40018",
   "name": "Test gas concentration",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 18,
   "documented": "40019",
   "name": "Sensor current value",
   "description": "2.00-6.00 mA.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "mA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 22,
   "documented": "40023",
   "name": "Calibration gas concentration",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 30,
   "documented": "40031",
   "name": "Main unit software version",
   "description": "e.g. 112 = ver. 1.12.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 31,
   "documented": "40032",
   "name": "Base unit software version",
   "description": "e.g. 110 = ver. 1.10.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 47,
   "documented": "40048",
   "name": "Test mode on/off",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 48,
   "documented": "40049",
   "name": "Test gas concentration (set)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "W",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 49,
   "documented": "40050",
   "name": "Host maintenance mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": {
    "0": "Off",
    "1": "On (no self-reset)",
    "17": "On (self-resets after 10 min)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 50,
   "documented": "40051",
   "name": "AL1 set value (set)",
   "description": "Always %F.S.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%F.S.",
   "access": "W",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 51,
   "documented": "40052",
   "name": "AL2 set value (set)",
   "description": "Always %F.S.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%F.S.",
   "access": "W",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 52,
   "documented": "40053",
   "name": "Alarm mode combination (set)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": {
    "0": "High-High limit",
    "1": "Low-Low limit",
    "2": "High-Low limit"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 53,
   "documented": "40054",
   "name": "AL1 delay time (set)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "W",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 54,
   "documented": "40055",
   "name": "AL2 delay time (set)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "W",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 55,
   "documented": "40056",
   "name": "Zero suppression value (set)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "W",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 56,
   "documented": "40057",
   "name": "Calibration gas concentration (set)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "W",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 515,
   "documented": "40516",
   "name": "Device status",
   "description": "High byte = status byte 1, low byte = status byte 2.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "15": "Sign of gas concentration (1 = negative)",
    "14": "Reserved",
    "13": "Low flow rate 1 (1 = not good)",
    "12": "Low flow rate 2 (1 = not good)",
    "11": "Broken pyrolyzer wire (1 = not good)",
    "10": "Sensor fault (1 = not good)",
    "9": "AL1 alarm on",
    "8": "AL2 alarm on",
    "7": "Device setup changed",
    "6": "Reserved",
    "5": "Reserved",
    "4": "Host maintenance mode on",
    "3": "Reserved",
    "2": "Test mode on",
    "1": "Maintenance mode 2 on",
    "0": "Maintenance mode 1 on"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1038,
   "documented": "41039",
   "name": "Gas concentration",
   "description": "Magnitude; sign in status bit 15; unit per 40011.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1039,
   "documented": "41040",
   "name": "F.S. code",
   "description": "3-digit full-scale code (e.g. 101 = 100); see manual table 7.5.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1296,
   "documented": "41297",
   "name": "Modbus TCP port number",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Read 41039-41040 for concentration and full-scale code and 40516 for alarms and faults; check 40011 once for the unit. Write AL set values and modes at 40051-40055 when needed.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 1038,
    "why": "Gas concentration"
   },
   {
    "table": "holding_register",
    "address": 1039,
    "why": "Full-scale code"
   },
   {
    "table": "holding_register",
    "address": 515,
    "why": "Status: alarms, faults, sign"
   },
   {
    "table": "holding_register",
    "address": 10,
    "why": "Measurement unit code"
   },
   {
    "table": "holding_register",
    "address": 0,
    "why": "Pump flow rate"
   }
  ],
  "enable": "Turn the base unit power switch OFF, select RS485 or ETHERNET with the mode DIP switch and set the unit ID on the address DIP switches (binary, 1-254), then switch the power back on.",
  "watchdog": null,
  "quirks": [
   "Concentration has no sign in the register itself; read status bit 15.",
   "Use relative (0-based) addresses on the wire: 41039 -> 1038."
  ],
  "setup": [
   "RS-485: up to 32 devices, 1.2 km at 9600 baud, built-in 120 ohm terminator switchable.",
   "Modbus TCP: fixed port 502."
  ],
  "gotchas": [
   "Reading or writing at 41321 and above returns an illegal address error."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/new-cosmos/ps-7-m",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}