 "manufacturer": "New Cosmos Electric",
 "manufacturer_slug": "new-cosmos",
 "model": "PS-8 series extractive gas detector (Modbus TCP)",
 "model_slug": "ps-8",
 "short_model": "PS-8",
 "aliases": [
  "PS-8",
  "PS-8 series",
  "New Cosmos PS-8"
 ],
 "equipment_type": "Sensor (extractive gas detector)",
 "applies_to": "New Cosmos PS-8 series pump-type gas detectors for semiconductor plants (up to 16 sensor channels) with Ethernet Modbus TCP, Instruction Manual for Communication GAE-180-00 (December 2024).",
 "summary": "The PS-8 is a New Cosmos pump-sampling gas detector for semiconductor process and flammable gases, holding up to 16 sensor units. Its Ethernet port is a Modbus TCP server with all data in holding registers. This map covers the integer gas readings, decimal points and flow for all 16 channels, relay states, heartbeat, alarm reset, clock, and the channel 1 settings block (other channels repeat every 101 registers).",
 "transport": [
  "TCP"
 ],
 "defaults": {
  "unit_id": null,
  "baud": null,
  "parity": null,
  "data_bits": null,
  "stop_bits": null,
  "tcp_port": 502
 },
 "addressing": {
  "convention": "Modicon",
  "note": "Registers are printed as 40001-42984 with a relative (wire) address column; 40005 = relative address 4, confirmed by the function 03 example frame that reads 40005 with start address 0x0004."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "PS-8 Series Gas Detector Instruction Manual for Communication",
  "doc_number": "GAE-180-00",
  "revision_date": "2024-12",
  "url": "https://new-cosmos.co.jp/wp/wp-content/uploads/ind/ps8_signalsetting_manu_en.pdf",
  "pages": "p. 6 (TCP specs), pp. 16-18 (frame examples), pp. 21-37 (register maps)"
 },
 "notes": [
  "All 32-bit items are left out: the status and fault-detail DWords (40001-40004 per channel), and every IEEE-754 float (40126-40249 block, float settings). The manual gives float examples as \"upper word\" / \"lower word\" without saying which register address each sits at, so the word order cannot be settled from the source.",
  "Character strings (serial number, tag and gas names) are also left out: the manual puts the 2nd character in the upper byte and the 1st in the lower byte, an order the string type here cannot express.",
  "Gas readings are integers: real value = raw / 10^decimal (decimal register 0-3). Example from the source: 20.9 vol% = 209 with decimal 1.",
  "The channel 1 settings block (40301-40397) repeats for channels 2-16 at +101 registers per channel (channel 2 starts at 40402). Grouped arrays for all 16 channels also exist at 42301-42984; only the concentration and unit arrays are listed here.",
  "Factory IP address is 192.168.0.101; the specification table allows at most 2 connected units. Writing to reserved or read-only registers is ignored; reading reserved registers returns 0."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 4,
   "documented": "40005",
   "name": "Sensor 1 concentration (integer)",
   "description": "Gas reading x 10^decimal (next register).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5,
   "documented": "40006",
   "name": "Sensor 1 decimal point",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No decimal",
    "1": "1 decimal place",
    "2": "2 decimal places",
    "3": "3 decimal places"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6,
   "documented": "40007",
   "name": "Sensor 1 flow rate",
   "description": "Sample flow as an FL value (0x1F4 = FL500).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11,
   "documented": "40012",
   "name": "Sensor 2 concentration (integer)",
   "description": "Gas reading x 10^decimal (next register).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 12,
   "documented": "40013",
   "name": "Sensor 2 decimal point",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No decimal",
    "1": "1 decimal place",
    "2": "2 decimal places",
    "3": "3 decimal places"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 13,
   "documented": "40014",
   "name": "Sensor 2 flow rate",
   "description": "Sample flow as an FL value (0x1F4 = FL500).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 18,
   "documented": "40019",
   "name": "Sensor 3 concentration (integer)",
   "description": "Gas reading x 10^decimal (next register).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 19,
   "documented": "40020",
   "name": "Sensor 3 decimal point",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No decimal",
    "1": "1 decimal place",
    "2": "2 decimal places",
    "3": "3 decimal places"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 20,
   "documented": "40021",
   "name": "Sensor 3 flow rate",
   "description": "Sample flow as an FL value (0x1F4 = FL500).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 25,
   "documented": "40026",
   "name": "Sensor 4 concentration (integer)",
   "description": "Gas reading x 10^decimal (next register).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 26,
   "documented": "40027",
   "name": "Sensor 4 decimal point",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No decimal",
    "1": "1 decimal place",
    "2": "2 decimal places",
    "3": "3 decimal places"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 27,
   "documented": "40028",
   "name": "Sensor 4 flow rate",
   "description": "Sample flow as an FL value (0x1F4 = FL500).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 32,
   "documented": "40033",
   "name": "Sensor 5 concentration (integer)",
   "description": "Gas reading x 10^decimal (next register).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 33,
   "documented": "40034",
   "name": "Sensor 5 decimal point",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No decimal",
    "1": "1 decimal place",
    "2": "2 decimal places",
    "3": "3 decimal places"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 34,
   "documented": "40035",
   "name": "Sensor 5 flow rate",
   "description": "Sample flow as an FL value (0x1F4 = FL500).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 39,
   "documented": "40040",
   "name": "Sensor 6 concentration (integer)",
   "description": "Gas reading x 10^decimal (next register).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 40,
   "documented": "40041",
   "name": "Sensor 6 decimal point",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No decimal",
    "1": "1 decimal place",
    "2": "2 decimal places",
    "3": "3 decimal places"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 41,
   "documented": "40042",
   "name": "Sensor 6 flow rate",
   "description": "Sample flow as an FL value (0x1F4 = FL500).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 46,
   "documented": "40047",
   "name": "Sensor 7 concentration (integer)",
   "description": "Gas reading x 10^decimal (next register).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 47,
   "documented": "40048",
   "name": "Sensor 7 decimal point",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No decimal",
    "1": "1 decimal place",
    "2": "2 decimal places",
    "3": "3 decimal places"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 48,
   "documented": "40049",
   "name": "Sensor 7 flow rate",
   "description": "Sample flow as an FL value (0x1F4 = FL500).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 53,
   "documented": "40054",
   "name": "Sensor 8 concentration (integer)",
   "description": "Gas reading x 10^decimal (next register).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 54,
   "documented": "40055",
   "name": "Sensor 8 decimal point",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No decimal",
    "1": "1 decimal place",
    "2": "2 decimal places",
    "3": "3 decimal places"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 55,
   "documented": "40056",
   "name": "Sensor 8 flow rate",
   "description": "Sample flow as an FL value (0x1F4 = FL500).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 60,
   "documented": "40061",
   "name": "Sensor 9 concentration (integer)",
   "description": "Gas reading x 10^decimal (next register).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 61,
   "documented": "40062",
   "name": "Sensor 9 decimal point",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No decimal",
    "1": "1 decimal place",
    "2": "2 decimal places",
    "3": "3 decimal places"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 62,
   "documented": "40063",
   "name": "Sensor 9 flow rate",
   "description": "Sample flow as an FL value (0x1F4 = FL500).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 67,
   "documented": "40068",
   "name": "Sensor 10 concentration (integer)",
   "description": "Gas reading x 10^decimal (next register).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 68,
   "documented": "40069",
   "name": "Sensor 10 decimal point",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No decimal",
    "1": "1 decimal place",
    "2": "2 decimal places",
    "3": "3 decimal places"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 69,
   "documented": "40070",
   "name": "Sensor 10 flow rate",
   "description": "Sample flow as an FL value (0x1F4 = FL500).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 74,
   "documented": "40075",
   "name": "Sensor 11 concentration (integer)",
   "description": "Gas reading x 10^decimal (next register).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 75,
   "documented": "40076",
   "name": "Sensor 11 decimal point",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No decimal",
    "1": "1 decimal place",
    "2": "2 decimal places",
    "3": "3 decimal places"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 76,
   "documented": "40077",
   "name": "Sensor 11 flow rate",
   "description": "Sample flow as an FL value (0x1F4 = FL500).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 81,
   "documented": "40082",
   "name": "Sensor 12 concentration (integer)",
   "description": "Gas reading x 10^decimal (next register).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 82,
   "documented": "40083",
   "name": "Sensor 12 decimal point",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No decimal",
    "1": "1 decimal place",
    "2": "2 decimal places",
    "3": "3 decimal places"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 83,
   "documented": "40084",
   "name": "Sensor 12 flow rate",
   "description": "Sample flow as an FL value (0x1F4 = FL500).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 88,
   "documented": "40089",
   "name": "Sensor 13 concentration (integer)",
   "description": "Gas reading x 10^decimal (next register).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 89,
   "documented": "40090",
   "name": "Sensor 13 decimal point",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No decimal",
    "1": "1 decimal place",
    "2": "2 decimal places",
    "3": "3 decimal places"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 90,
   "documented": "40091",
   "name": "Sensor 13 flow rate",
   "description": "Sample flow as an FL value (0x1F4 = FL500).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 95,
   "documented": "40096",
   "name": "Sensor 14 concentration (integer)",
   "description": "Gas reading x 10^decimal (next register).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 96,
   "documented": "40097",
   "name": "Sensor 14 decimal point",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No decimal",
    "1": "1 decimal place",
    "2": "2 decimal places",
    "3": "3 decimal places"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 97,
   "documented": "40098",
   "name": "Sensor 14 flow rate",
   "description": "Sample flow as an FL value (0x1F4 = FL500).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 102,
   "documented": "40103",
   "name": "Sensor 15 concentration (integer)",
   "description": "Gas reading x 10^decimal (next register).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 103,
   "documented": "40104",
   "name": "Sensor 15 decimal point",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No decimal",
    "1": "1 decimal place",
    "2": "2 decimal places",
    "3": "3 decimal places"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 104,
   "documented": "40105",
   "name": "Sensor 15 flow rate",
   "description": "Sample flow as an FL value (0x1F4 = FL500).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 109,
   "documented": "40110",
   "name": "Sensor 16 concentration (integer)",
   "description": "Gas reading x 10^decimal (next register).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 110,
   "documented": "40111",
   "name": "Sensor 16 decimal point",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No decimal",
    "1": "1 decimal place",
    "2": "2 decimal places",
    "3": "3 decimal places"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 111,
   "documented": "40112",
   "name": "Sensor 16 flow rate",
   "description": "Sample flow as an FL value (0x1F4 = FL500).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 112,
   "documented": "40113",
   "name": "Heartbeat",
   "description": "Counts up once a second, 0-255 then wraps.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 113,
   "documented": "40114",
   "name": "Relay output monitor sensors 1/2",
   "description": "High byte sensor 1, low byte sensor 2; bits 0/1/2 = AL1/AL2/fault relay.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 114,
   "documented": "40115",
   "name": "Relay output monitor sensors 3/4",
   "description": "High byte sensor 3, low byte sensor 4; bits 0/1/2 = AL1/AL2/fault relay.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 115,
   "documented": "40116",
   "name": "Relay output monitor sensors 5/6",
   "description": "High byte sensor 5, low byte sensor 6; bits 0/1/2 = AL1/AL2/fault relay.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 116,
   "documented": "40117",
   "name": "Relay output monitor sensors 7/8",
   "description": "High byte sensor 7, low byte sensor 8; bits 0/1/2 = AL1/AL2/fault relay.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 117,
   "documented": "40118",
   "name": "Relay output monitor sensors 9/10",
   "description": "High byte sensor 9, low byte sensor 10; bits 0/1/2 = AL1/AL2/fault relay.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 118,
   "documented": "40119",
   "name": "Relay output monitor sensors 11/12",
   "description": "High byte sensor 11, low byte sensor 12; bits 0/1/2 = AL1/AL2/fault relay.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 119,
   "documented": "40120",
   "name": "Relay output monitor sensors 13/14",
   "description": "High byte sensor 13, low byte sensor 14; bits 0/1/2 = AL1/AL2/fault relay.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 120,
   "documented": "40121",
   "name": "Relay output monitor sensors 15/16",
   "description": "High byte sensor 15, low byte sensor 16; bits 0/1/2 = AL1/AL2/fault relay.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 123,
   "documented": "40124",
   "name": "Setting change channel flags",
   "description": "Bit n set when channel n+1 settings changed; write 0 after reading.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Channel 1 changed",
    "1": "Channel 2 changed",
    "2": "Channel 3 changed",
    "3": "Channel 4 changed",
    "4": "Channel 5 changed",
    "5": "Channel 6 changed",
    "6": "Channel 7 changed",
    "7": "Channel 8 changed",
    "8": "Channel 9 changed",
    "9": "Channel 10 changed",
    "10": "Channel 11 changed",
    "11": "Channel 12 changed",
    "12": "Channel 13 changed",
    "13": "Channel 14 changed",
    "14": "Channel 15 changed",
    "15": "Channel 16 changed"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 250,
   "documented": "40251",
   "name": "Alarm cancellation",
   "description": "Write 1 to cancel a latched alarm (manual-reset mode only).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 253,
   "documented": "40254",
   "name": "Alarm cancellation mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Auto-resetting",
    "1": "Manual-resetting"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 254,
   "documented": "40255",
   "name": "Collective contact AL1 setting",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normally not energized",
    "1": "Normally energized"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 255,
   "documented": "40256",
   "name": "Collective contact AL2 setting",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normally not energized",
    "1": "Normally energized"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 256,
   "documented": "40257",
   "name": "Collective fault contact setting",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normally not energized",
    "1": "Normally energized"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 258,
   "documented": "40259",
   "name": "Date/time: month and year",
   "description": "High byte month, low byte year 0-99; access the 3 date words together.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 259,
   "documented": "40260",
   "name": "Date/time: hour and day",
   "description": "High byte hour (24 h), low byte day.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 260,
   "documented": "40261",
   "name": "Date/time: seconds and minutes",
   "description": "High byte seconds, low byte minutes.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 308,
   "documented": "40309",
   "name": "Sensor 1 alarm AL1 setting (integer)",
   "description": "Setpoint x 10^decimal.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 309,
   "documented": "40310",
   "name": "Sensor 1 alarm AL2 setting (integer)",
   "description": "Setpoint x 10^decimal.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 314,
   "documented": "40315",
   "name": "Sensor 1 full scale (integer)",
   "description": "Writable only with AI module allocation.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 315,
   "documented": "40316",
   "name": "Sensor 1 decimal point (settings)",
   "description": "Writable only with AI module allocation.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No decimal",
    "1": "1 decimal place",
    "2": "2 decimal places",
    "3": "3 decimal places"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 318,
   "documented": "40319",
   "name": "Sensor 1 unit",
   "description": "Writable only with AI module allocation.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No unit",
    "1": "ppm",
    "2": "ppb",
    "3": "vol%",
    "4": "%LEL",
    "5": "%"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 319,
   "documented": "40320",
   "name": "Sensor 1 alarm mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "AL1 high / AL2 high",
    "1": "AL1 low / AL2 low",
    "2": "AL1 low / AL2 high"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 336,
   "documented": "40337",
   "name": "Sensor 1 alarm delay AL1",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 337,
   "documented": "40338",
   "name": "Sensor 1 alarm delay AL2",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 349,
   "documented": "40350",
   "name": "DO module allocation",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 350,
   "documented": "40351",
   "name": "4-20 mA analog input allocation",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 356,
   "documented": "40357",
   "name": "Sensor 1 sensor days of use",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "days",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 357,
   "documented": "40358",
   "name": "Sensor 1 pump days of use",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "days",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 358,
   "documented": "40359",
   "name": "Sensor 1 pump duty",
   "description": "Pump control value 0-100.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 382,
   "documented": "40383",
   "name": "Sensor 1 relay AL1 setting",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Normally not energized",
    "1": "Normally energized"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 383,
   "documented": "40384",
   "name": "Sensor 1 relay AL2 setting",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Normally not energized",
    "1": "Normally energized"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 384,
   "documented": "40385",
   "name": "Sensor 1 fault relay setting",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Normally not energized",
    "1": "Normally energized"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 389,
   "documented": "40390",
   "name": "Sensor 1 maintenance mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "Maintenance mode 1",
    "2": "Maintenance mode 2"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 390,
   "documented": "40391",
   "name": "Sensor 1 alarm test on/off",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "End alarm test",
    "1": "Start alarm test"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 391,
   "documented": "40392",
   "name": "Sensor 1 alarm test concentration",
   "description": "Test value in %FS using the fixed-point setting.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2628,
   "documented": "42629",
   "name": "Sensor 1 unit (grouped)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No unit",
    "1": "ppm",
    "2": "ppb",
    "3": "vol%",
    "4": "%LEL",
    "5": "%"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2629,
   "documented": "42630",
   "name": "Sensor 2 unit (grouped)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No unit",
    "1": "ppm",
    "2": "ppb",
    "3": "vol%",
    "4": "%LEL",
    "5": "%"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2630,
   "documented": "42631",
   "name": "Sensor 3 unit (grouped)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No unit",
    "1": "ppm",
    "2": "ppb",
    "3": "vol%",
    "4": "%LEL",
    "5": "%"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2631,
   "documented": "42632",
   "name": "Sensor 4 unit (grouped)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No unit",
    "1": "ppm",
    "2": "ppb",
    "3": "vol%",
    "4": "%LEL",
    "5": "%"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2632,
   "documented": "42633",
   "name": "Sensor 5 unit (grouped)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No unit",
    "1": "ppm",
    "2": "ppb",
    "3": "vol%",
    "4": "%LEL",
    "5": "%"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2633,
   "documented": "42634",
   "name": "Sensor 6 unit (grouped)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No unit",
    "1": "ppm",
    "2": "ppb",
    "3": "vol%",
    "4": "%LEL",
    "5": "%"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2634,
   "documented": "42635",
   "name": "Sensor 7 unit (grouped)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No unit",
    "1": "ppm",
    "2": "ppb",
    "3": "vol%",
    "4": "%LEL",
    "5": "%"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2635,
   "documented": "42636",
   "name": "Sensor 8 unit (grouped)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No unit",
    "1": "ppm",
    "2": "ppb",
    "3": "vol%",
    "4": "%LEL",
    "5": "%"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2636,
   "documented": "42637",
   "name": "Sensor 9 unit (grouped)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No unit",
    "1": "ppm",
    "2": "ppb",
    "3": "vol%",
    "4": "%LEL",
    "5": "%"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2637,
   "documented": "42638",
   "name": "Sensor 10 unit (grouped)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No unit",
    "1": "ppm",
    "2": "ppb",
    "3": "vol%",
    "4": "%LEL",
    "5": "%"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2638,
   "documented": "42639",
   "name": "Sensor 11 unit (grouped)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No unit",
    "1": "ppm",
    "2": "ppb",
    "3": "vol%",
    "4": "%LEL",
    "5": "%"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2639,
   "documented": "42640",
   "name": "Sensor 12 unit (grouped)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No unit",
    "1": "ppm",
    "2": "ppb",
    "3": "vol%",
    "4": "%LEL",
    "5": "%"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2640,
   "documented": "42641",
   "name": "Sensor 13 unit (grouped)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No unit",
    "1": "ppm",
    "2": "ppb",
    "3": "vol%",
    "4": "%LEL",
    "5": "%"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2641,
   "documented": "42642",
   "name": "Sensor 14 unit (grouped)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No unit",
    "1": "ppm",
    "2": "ppb",
    "3": "vol%",
    "4": "%LEL",
    "5": "%"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2642,
   "documented": "42643",
   "name": "Sensor 15 unit (grouped)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No unit",
    "1": "ppm",
    "2": "ppb",
    "3": "vol%",
    "4": "%LEL",
    "5": "%"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2643,
   "documented": "42644",
   "name": "Sensor 16 unit (grouped)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No unit",
    "1": "ppm",
    "2": "ppb",
    "3": "vol%",
    "4": "%LEL",
    "5": "%"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2728,
   "documented": "42729",
   "name": "Sensor 1 concentration (integer, grouped)",
   "description": "Same value as the periodic block; scale by the decimal register.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2729,
   "documented": "42730",
   "name": "Sensor 2 concentration (integer, grouped)",
   "description": "Same value as the periodic block; scale by the decimal register.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2730,
   "documented": "42731",
   "name": "Sensor 3 concentration (integer, grouped)",
   "description": "Same value as the periodic block; scale by the decimal register.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2731,
   "documented": "42732",
   "name": "Sensor 4 concentration (integer, grouped)",
   "description": "Same value as the periodic block; scale by the decimal register.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2732,
   "documented": "42733",
   "name": "Sensor 5 concentration (integer, grouped)",
   "description": "Same value as the periodic block; scale by the decimal register.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2733,
   "documented": "42734",
   "name": "Sensor 6 concentration (integer, grouped)",
   "description": "Same value as the periodic block; scale by the decimal register.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2734,
   "documented": "42735",
   "name": "Sensor 7 concentration (integer, grouped)",
   "description": "Same value as the periodic block; scale by the decimal register.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2735,
   "documented": "42736",
   "name": "Sensor 8 concentration (integer, grouped)",
   "description": "Same value as the periodic block; scale by the decimal register.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2736,
   "documented": "42737",
   "name": "Sensor 9 concentration (integer, grouped)",
   "description": "Same value as the periodic block; scale by the decimal register.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2737,
   "documented": "42738",
   "name": "Sensor 10 concentration (integer, grouped)",
   "description": "Same value as the periodic block; scale by the decimal register.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2738,
   "documented": "42739",
   "name": "Sensor 11 concentration (integer, grouped)",
   "description": "Same value as the periodic block; scale by the decimal register.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2739,
   "documented": "42740",
   "name": "Sensor 12 concentration (integer, grouped)",
   "description": "Same value as the periodic block; scale by the decimal register.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2740,
   "documented": "42741",
   "name": "Sensor 13 concentration (integer, grouped)",
   "description": "Same value as the periodic block; scale by the decimal register.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2741,
   "documented": "42742",
   "name": "Sensor 14 concentration (integer, grouped)",
   "description": "Same value as the periodic block; scale by the decimal register.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2742,
   "documented": "42743",
   "name": "Sensor 15 concentration (integer, grouped)",
   "description": "Same value as the periodic block; scale by the decimal register.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2743,
   "documented": "42744",
   "name": "Sensor 16 concentration (integer, grouped)",
   "description": "Same value as the periodic block; scale by the decimal register.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Connect over Ethernet to 192.168.0.101 port 502 and read holding registers 0-111 (seven words per sensor) with function 03; use the integer concentration and decimal registers for each channel.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 4,
    "why": "Sensor 1 concentration"
   },
   {
    "table": "holding_register",
    "address": 5,
    "why": "Sensor 1 decimal point"
   },
   {
    "table": "holding_register",
    "address": 6,
    "why": "Sensor 1 flow"
   },
   {
    "table": "holding_register",
    "address": 112,
    "why": "Heartbeat"
   },
   {
    "table": "holding_register",
    "address": 113,
    "why": "Relay states sensors 1/2"
   },
   {
    "table": "holding_register",
    "address": 318,
    "why": "Sensor 1 unit"
   }
  ],
  "enable": "Menu > Device Information > Modbus: select TCP/IP. Set IP and subnet (or DHCP) under Device Information.",
  "watchdog": null,
  "quirks": [
   "Register 400xx minus 40001 = wire address.",
   "Reading starting at a reserved register gives an illegal-address error; reserved registers inside a longer read return 0.",
   "Date/time must be read or written as all three words together."
  ],
  "setup": [
   "Factory IP 192.168.0.101, port 502 fixed.",
   "No proxy; the built-in web page at the IP shows live channel data for a quick check."
  ],
  "gotchas": [
   "Maintenance mode masks the alarm and fault bits of the status words.",
   "Settings marked change notification set a bit in 40124; clear it by writing 0."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/new-cosmos/ps-8",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}