 "manufacturer": "Nilan",
 "manufacturer_slug": "nilan",
 "model": "CTS602 controller with HMI350T panel (Modbus version 23)",
 "model_slug": "cts602-hmi350t",
 "short_model": "CTS602",
 "aliases": [
  "CTS 602",
  "CTS602 HMI350T",
  "CTS602 w. HMI350T"
 ],
 "equipment_type": "Heat pump / ventilation unit controller (air handler)",
 "applies_to": "Nilan ventilation, heat-recovery and compact heat pump units with the CTS602 board and HMI350T user panel, Modbus protocol version 23 (software 3.6.58/3.6.59).",
 "summary": "The Nilan CTS602 is the controller in Nilan's residential and light-commercial ventilation units and compact heat pumps (ventilation, heat recovery, hot water and optional central heating). Its RS-485 port COM1 is a Modbus RTU slave at fixed 19200 8E1. Input registers give temperatures T0-T18 (x0.01 °C), humidity, CO2, digital inputs, alarm list, run and control states, fan steps and differential-pressure flows; holding registers carry on/off, operation mode, ventilation step, temperature setpoint, hot water and central heating settings, outputs and the clock.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": 30,
  "baud": 19200,
  "parity": "Even",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "0-based",
  "note": "Nilan lists the addresses exactly as sent in the Modbus request, without the 30001/40001 global offset: reading input register 100 with function 04 is global address 30101. Use the printed number directly as the wire address."
 },
 "default_word_order": null,
 "firmware": "Modbus protocol version 23 (Bus.Version), CTS602 software 3.6.58 / 3.6.59",
 "source": {
  "title": "Protocol description - Nilan CTS602 with HMI350T - Modbus version 23",
  "doc_number": "52173104",
  "revision_date": "2023-11-22",
  "url": "https://taphome.com/compatibility/devices/nilan-cts602-heat-pump/manufacturer/CTS602_HMI350T_Modbus_v23.pdf",
  "pages": "p. 5 (setup, functions), p. 6 (addressing note), pp. 6-11 (input registers), pp. 12-20 (holding registers), p. 21 (example frames)",
  "unofficial": true
 },
 "notes": [
  "Nilan does not host this protocol description at a public URL we could find (its manuals say it can be downloaded from the Nilan website, but no direct link turned up). The linked copy, hosted by the home-automation vendor TapHome in its 'manufacturer' folder, is the unchanged Nilan document 52173104.",
  "Scale column: '100' means the raw value is divided by 100 (e.g. temperatures and % values with two decimals). Registers without a scale are whole numbers.",
  "Signedness is not stated per register; temperatures and temperature settings are typed INT16 because they can be negative (the list shows ranges down to -40.00 °C), everything else UINT16.",
  "Left out: software version text registers (1-3, two ASCII characters each), suction/discharge pressure (219/220, no scale given), registers scaled by 60 (1503, 4018) whose unit is unclear, user-function temperature/offset (604/605 and their user-function-2 copies 614/615) and fan-scaling (4098/4099) which have no scale, the pressure-control P/I settings (2300-2304), the alarm log detail block (3050-3074), week-program editing registers (4030-4036) and the menu-open flag (2002).",
  "Enumerations are only given where the list prints the full value set; several holding registers in the display section (e.g. 4003-4005, 4012, 4013, 4020, 4021, 4041, 4108-4112) are listed without their complete value lists and are left without values.",
  "Some holding-register descriptions in the source are in Danish (2300-2327 'Trin n tilluft/fraluft' = step n supply/extract air flow or pressure, 1209 heat source select); they are translated in the names here.",
  "The document does not mark which holding registers are read-only; the output registers 100-206 and the clock 300-305 report states rather than commands.",
  "All input registers can also be read as holding registers with function 03 at address + 10000 (read only).",
  "External fire alarm auto reset (holding 4040) is left without value labels: the printed table shows codes 0-2, but the cell is cut off and the document's text layer holds a further code 3 that is not visible."
 ],
 "registers": [
  {
   "table": "input_register",
   "address": 0,
   "documented": "000",
   "name": "Protocol version number",
   "description": "Nilan variable Bus.Version.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 4,
   "documented": "004",
   "name": "Application Id",
   "description": "Nilan variable Info.AppID.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 5,
   "documented": "005",
   "name": "Application hardware Id",
   "description": "Nilan variable Info.HWType.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 100,
   "documented": "100",
   "name": "User function",
   "description": "Digital input state; Nilan variable Input.UserFunc.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 101,
   "documented": "101",
   "name": "Air filter alarm",
   "description": "Digital input state; Nilan variable Input.AirFilter.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 102,
   "documented": "102",
   "name": "Door contact",
   "description": "Digital input state; Nilan variable Input.DoorOpen.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 103,
   "documented": "103",
   "name": "Smoke alarm",
   "description": "Digital input state; Nilan variable Input.Smoke.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 104,
   "documented": "104",
   "name": "Motor thermo fuse",
   "description": "Digital input state; Nilan variable Input.MotorThermo.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 105,
   "documented": "105",
   "name": "Heating surface frost / overheat",
   "description": "Digital input state; Nilan variable Input.Frost_Overht.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 106,
   "documented": "106",
   "name": "Airflow monitor",
   "description": "Digital input state; Nilan variable Input.AirFlow.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 107,
   "documented": "107",
   "name": "High pressure switch",
   "description": "Digital input state; Nilan variable Input.P_HI.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 108,
   "documented": "108",
   "name": "Low pressure switch",
   "description": "Digital input state; Nilan variable Input.P_LO.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 109,
   "documented": "109",
   "name": "Hot water boiling",
   "description": "Digital input state; Nilan variable Input.Boil.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 110,
   "documented": "110",
   "name": "Hot water 3-way valve position",
   "description": "Digital input state; Nilan variable Input.3WayPos.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 111,
   "documented": "111",
   "name": "Hotgas defrost type selection",
   "description": "Digital input state; Nilan variable Input.DefrostHG.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 112,
   "documented": "112",
   "name": "Defrost thermostat",
   "description": "Digital input state; Nilan variable Input.Defrost.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 113,
   "documented": "113",
   "name": "User function 2",
   "description": "Digital input state; Nilan variable Input.UserFunc_2.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 114,
   "documented": "114",
   "name": "Air damper closed position switch",
   "description": "Digital input state; Nilan variable Input.DamperClosed.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 115,
   "documented": "115",
   "name": "Air damper opened position switch",
   "description": "Digital input state; Nilan variable Input.DamperOpened.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 116,
   "documented": "116",
   "name": "Combined FC and thermo alarm",
   "description": "Digital input state; Nilan variable Input.FCorThermoAl.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 117,
   "documented": "117",
   "name": "Brine pressostat",
   "description": "Digital input state; Nilan variable Input.BrinePress.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 200,
   "documented": "200",
   "name": "Controller board temperature",
   "description": "Nilan variable Input.T0_Controller.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 201,
   "documented": "201",
   "name": "Fresh air intake temperature",
   "description": "Nilan variable Input.T1_Intake.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 202,
   "documented": "202",
   "name": "Inlet temperature (before heater)",
   "description": "Nilan variable Input.T2_Inlet.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 203,
   "documented": "203",
   "name": "Room exhaust temperature",
   "description": "Nilan variable Input.T3_Exhaust.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 204,
   "documented": "204",
   "name": "Outlet temperature",
   "description": "Nilan variable Input.T4_Outlet.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 205,
   "documented": "205",
   "name": "Condenser temperature",
   "description": "Nilan variable Input.T5_Cond.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 206,
   "documented": "206",
   "name": "Evaporator temperature",
   "description": "Nilan variable Input.T6_Evap.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 207,
   "documented": "207",
   "name": "Inlet temperature (after heater)",
   "description": "Nilan variable Input.T7_Inlet.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 208,
   "documented": "208",
   "name": "Outdoor temperature",
   "description": "Nilan variable Input.T8_Outdoor.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 209,
   "documented": "209",
   "name": "Heating surface temperature",
   "description": "Nilan variable Input.T9_Heater.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 210,
   "documented": "210",
   "name": "External room temperature",
   "description": "Nilan variable Input.T10_Extern.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 211,
   "documented": "211",
   "name": "Hot water top temperature",
   "description": "Nilan variable Input.T11_Top.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 212,
   "documented": "212",
   "name": "Hot water bottom temperature",
   "description": "Nilan variable Input.T12_Bottom.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 213,
   "documented": "213",
   "name": "EK return temperature",
   "description": "Nilan variable Input.T13_Return.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 214,
   "documented": "214",
   "name": "EK supply temperature",
   "description": "Nilan variable Input.T14_Supply.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 215,
   "documented": "215",
   "name": "User panel room temperature",
   "description": "Nilan variable Input.T15_Room.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 216,
   "documented": "216",
   "name": "AUX temperature (Hotwater anode)",
   "description": "Nilan variable Input.T16.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 217,
   "documented": "217",
   "name": "Preheater or earth tube air intake temperature",
   "description": "Nilan variable Input.T17_PreHeat.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 218,
   "documented": "218",
   "name": "Pressure pibe temperature",
   "description": "Nilan variable Input.T18_PresPibe.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 221,
   "documented": "221",
   "name": "Humidity sensor value",
   "description": "Nilan variable AirQual.RH.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 222,
   "documented": "222",
   "name": "Carbon dioxide sensor value",
   "description": "Nilan variable AirQual.CO2.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "ppm",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 400,
   "documented": "400",
   "name": "Alarm state bit mask",
   "description": "Bit 7 (0x80) = alarms active; low nibble (0x0F) = number of alarms.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 401,
   "documented": "401",
   "name": "Alarm 1 - Code",
   "description": "Nilan variable Alarm.List_1_ID.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 402,
   "documented": "402",
   "name": "Alarm 1 - Date",
   "description": "Nilan variable Alarm.List_1_Date.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 403,
   "documented": "403",
   "name": "Alarm 1 - Time",
   "description": "Nilan variable Alarm.List_1_Time.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 404,
   "documented": "404",
   "name": "Alarm 2 - Code",
   "description": "Nilan variable Alarm.List_2_ID.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 405,
   "documented": "405",
   "name": "Alarm 2 - Date",
   "description": "Nilan variable Alarm.List_2_Date.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 406,
   "documented": "406",
   "name": "Alarm 2 - Time",
   "description": "Nilan variable Alarm.List_2_Time.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 407,
   "documented": "407",
   "name": "Alarm 3 - Code",
   "description": "Nilan variable Alarm.List_3_ID.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 408,
   "documented": "408",
   "name": "Alarm 3 - Date",
   "description": "Nilan variable Alarm.List_3_Date.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 409,
   "documented": "409",
   "name": "Alarm 3 - Time",
   "description": "Nilan variable Alarm.List_3_Time.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1000,
   "documented": "1000",
   "name": "Actual on/off state",
   "description": "Nilan variable Control.RunAct.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1001,
   "documented": "1001",
   "name": "Actual operation mode",
   "description": "Nilan variable Control.ModeAct.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "Heat",
    "2": "Cool",
    "3": "Auto",
    "4": "Service"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1002,
   "documented": "1002",
   "name": "Actual control state",
   "description": "Nilan variable Control.StateDisplay.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "9": "Hot water",
    "1": "Shift",
    "10": "Legionella",
    "2": "Stop",
    "11": "Cooling + hot water",
    "3": "Start",
    "12": "Central heating",
    "4": "Standby",
    "13": "Defrost",
    "5": "Ventilation stop",
    "14": "Frost sequre",
    "6": "Ventilation",
    "15": "Service",
    "7": "Heating",
    "16": "Alarm",
    "8": "Cooling",
    "17": "Heating + hot water"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1003,
   "documented": "1003",
   "name": "Actual time in state",
   "description": "Nilan variable Control.SecInState.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1100,
   "documented": "1100",
   "name": "Actual ventilation step set point",
   "description": "Nilan variable AirFlow.VentSet.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1101,
   "documented": "1101",
   "name": "Actual inlet fan speed step",
   "description": "Nilan variable AirFlow.InletAct.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1102,
   "documented": "1102",
   "name": "Actual exhaust fan speed step",
   "description": "Nilan variable AirFlow.ExhaustAct.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1103,
   "documented": "1103",
   "name": "Days since last air filter change alarm",
   "description": "Nilan variable AirFlow.SinceFiltDay.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "d",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1104,
   "documented": "1104",
   "name": "Days to next air filter change alarm",
   "description": "Nilan variable AirFlow.ToFiltDay.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "d",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1200,
   "documented": "1200",
   "name": "Summer state",
   "description": "Nilan variable AirTemp.IsSummer.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1201,
   "documented": "1201",
   "name": "Inlet temperature request (T7 setpoint)",
   "description": "Nilan variable AirTemp.TempInletSet.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1202,
   "documented": "1202",
   "name": "Actual value for controlled temperature",
   "description": "Nilan variable AirTemp.TempControl.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1203,
   "documented": "1203",
   "name": "Actual room temperature (T15 or T10)",
   "description": "Nilan variable AirTemp.TempRoom.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1204,
   "documented": "1204",
   "name": "Passive heat exchanger efficiency calculation",
   "description": "Nilan variable AirTemp.EffPct.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1205,
   "documented": "1205",
   "name": "Requested capacity",
   "description": "Nilan variable AirTemp.CapSet.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1206,
   "documented": "1206",
   "name": "Actual capacity",
   "description": "Nilan variable AirTemp.CapAct.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1500,
   "documented": "1500",
   "name": "Compressor type",
   "description": "Nilan variable Compressor.Type.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "None",
    "1": "On/Off",
    "2": "Modulated hotgas valve"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1700,
   "documented": "1700",
   "name": "Hot water type",
   "description": "Nilan variable HotWater.Type.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "None",
    "1": "Only hot water (VGU)",
    "2": "With ventilation (VP)",
    "3": "With central heating (VGU180)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1701,
   "documented": "1701",
   "name": "Hot water anode state",
   "description": "Nilan variable HotWater.AnodeState.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "OFF",
    "1": "OK",
    "2": "SERVICE",
    "3": "ERROR"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1800,
   "documented": "1800",
   "name": "Actual setpoint for external heating source",
   "description": "Nilan variable CentralHeat.HeatExtSet.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2100,
   "documented": "2100",
   "name": "Remaining time for the pre-heater blocking function",
   "description": "Nilan variable PreHeat.BlockRemain.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2200,
   "documented": "2200",
   "name": "DPT in session",
   "description": "Nilan variable DPT.InSession.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2201,
   "documented": "2201",
   "name": "Calculated air flow 1",
   "description": "Nilan variable DPT.AirFlow1.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "m3/h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2202,
   "documented": "2202",
   "name": "Calculated air flow 2",
   "description": "Nilan variable DPT.AirFlow2.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "m3/h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2221,
   "documented": "2221",
   "name": "Calculated air pressure 1",
   "description": "Nilan variable DPT.Pressure1.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "Pa",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2222,
   "documented": "2222",
   "name": "Calculated air pressure 2",
   "description": "Nilan variable DPT.Pressure2.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "Pa",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2230,
   "documented": "2230",
   "name": "DPT2 in session",
   "description": "Nilan variable DPT2.InSession.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2231,
   "documented": "2231",
   "name": "DPT2 calculated air flow 1",
   "description": "Nilan variable DPT2.AirFlow1.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "m3/h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2232,
   "documented": "2232",
   "name": "DPT2 calculated air flow 2",
   "description": "Nilan variable DPT2.AirFlow2.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "m3/h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2241,
   "documented": "2241",
   "name": "DPT2 calculated air pressure 1",
   "description": "Nilan variable DPT2.Pressure1.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "Pa",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2242,
   "documented": "2242",
   "name": "DPT2 calculated air pressure 2",
   "description": "Nilan variable DPT2.Pressure2.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "Pa",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3000,
   "documented": "3000",
   "name": "Bypass damper",
   "description": "Nilan variable AirBypass.IsOpen.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Closed",
    "1": "Open"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3001,
   "documented": "3001",
   "name": "After heating element",
   "description": "Nilan variable Output.AirHeatCap.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3002,
   "documented": "3002",
   "name": "De-icing heat exchanger",
   "description": "Nilan variable Defrost.ExchDefrost.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On (Passive exchanger defrost is active)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3003,
   "documented": "3003",
   "name": "CO2 sensor present in the system or not",
   "description": "Nilan variable AirQual.CO2_Enable.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3004,
   "documented": "3004",
   "name": "Stop at low room temperature",
   "description": "Nilan variable AirFlow.RoomReduce.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3005,
   "documented": "3005",
   "name": "Date for last air damper self-test",
   "description": "Nilan variable AirFlow.LastTestDay.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3006,
   "documented": "3006",
   "name": "Days since last air filter change",
   "description": "Nilan variable AirFlow.SinceFiltDay.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3007,
   "documented": "3007",
   "name": "Low fan speed at low outdoor temperature",
   "description": "Nilan variable AirFLow.WinterReduce.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3008,
   "documented": "3008",
   "name": "Actual resulting set-point for room temperature",
   "description": "Nilan variable AirTemp.TempSet.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3009,
   "documented": "3009",
   "name": "Master sensor for the controlled temperature (room / inlet)",
   "description": "Nilan variable AirTemp.TempControl.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3075,
   "documented": "3075",
   "name": "Operation states for Control module",
   "description": "Nilan variable Alarm.LogCtrState.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "OFF",
    "1": "SHIFTING",
    "2": "STOPPING",
    "3": "STARTING",
    "4": "STANDBY",
    "5": "VENT_STOP",
    "6": "AIR_EXCH",
    "7": "AIR_HEAT",
    "8": "AIR_COOL",
    "9": "HOTWATER",
    "10": "LEGIONELLA",
    "11": "AIR_COOL_HOT_WATER",
    "12": "CENT_HEAT",
    "13": "DEFROST",
    "14": "FROST",
    "15": "SERVICE",
    "16": "ALARM_SHUTDOWN",
    "17": "AIR_HEAT_HOT_WATER"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3100,
   "documented": "3100",
   "name": "Humidity average value.",
   "description": "Nilan variable AirQual.RH_Avg.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3101,
   "documented": "3101",
   "name": "If expansion I/O board is present the value must be 12.",
   "description": "Nilan variable Opt9_1.BoardId.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3102,
   "documented": "3102",
   "name": "Ventilation state",
   "description": "Nilan variable AirFlow.VentState.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "OFF",
    "1": "NORMAL",
    "2": "LOW_HUMIDITY",
    "3": "HIGH_HUMIDITY",
    "4": "HIGH_CO2",
    "5": "LOW_ROOM_TEMP",
    "6": "LOW_OUTDOOR_TEMP"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 50,
   "documented": "050",
   "name": "Protocol node address (default = 30)",
   "description": "Nilan variable Bus.Address.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 100,
   "documented": "100",
   "name": "Air flap",
   "description": "Output state; Nilan variable Output.AirFlap.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 101,
   "documented": "101",
   "name": "Smoke flap",
   "description": "Output state; Nilan variable Output.SmokeFlap.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 102,
   "documented": "102",
   "name": "Bypass flap open",
   "description": "Output state; Nilan variable Output.BypassOpen.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 103,
   "documented": "103",
   "name": "Bypass flap close",
   "description": "Output state; Nilan variable Output.BypassClose.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 104,
   "documented": "104",
   "name": "Air heat circulation pump",
   "description": "Output state; Nilan variable Output.AirCircPump.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 105,
   "documented": "105",
   "name": "Air heating selected",
   "description": "Output state; Nilan variable Output.AirHeatAllow.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 106,
   "documented": "106",
   "name": "Air heater relays",
   "description": "Output state; Nilan variable Output.AirHeat_1.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 107,
   "documented": "107",
   "name": "AirHeat_2",
   "description": "Output state; Nilan variable Output.AirHeat_2.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 108,
   "documented": "108",
   "name": "AirHeat_3",
   "description": "Output state; Nilan variable Output.AirHeat_3.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 109,
   "documented": "109",
   "name": "Compressor",
   "description": "Output state; Nilan variable Output.Compressor.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 110,
   "documented": "110",
   "name": "Compressor 2",
   "description": "Output state; Nilan variable Output.Compressor_2.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 111,
   "documented": "111",
   "name": "4-way valve",
   "description": "Output state; Nilan variable Output.4WayCool.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 112,
   "documented": "112",
   "name": "Hotgas valve - heat",
   "description": "Output state; Nilan variable Output.HotgasHeat.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 113,
   "documented": "113",
   "name": "Hotgas valve - cool",
   "description": "Output state; Nilan variable Output.HotgasCool.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 114,
   "documented": "114",
   "name": "Air condenser active",
   "description": "Output state; Nilan variable Output.CondOpen.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 115,
   "documented": "115",
   "name": "Air condenser inactive",
   "description": "Output state; Nilan variable Output.CondClose.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 116,
   "documented": "116",
   "name": "Hot water heater",
   "description": "Output state; Nilan variable Output.WaterHeat.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 117,
   "documented": "117",
   "name": "Hot water 3-way valve",
   "description": "Output state; Nilan variable Output.3WayValve.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 118,
   "documented": "118",
   "name": "EK circulation pump",
   "description": "Output state; Nilan variable Output.CenCircPump.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 119,
   "documented": "119",
   "name": "EK heater relays",
   "description": "Output state; Nilan variable Output.CenHeat_1.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 120,
   "documented": "120",
   "name": "CenHeat_2",
   "description": "Output state; Nilan variable Output.CenHeat_2.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 121,
   "documented": "121",
   "name": "CenHeat_3",
   "description": "Output state; Nilan variable Output.CenHeat_3.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 122,
   "documented": "122",
   "name": "External radiator heat",
   "description": "Output state; Nilan variable Output.CenHeatExt.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 123,
   "documented": "123",
   "name": "User function active",
   "description": "Output state; Nilan variable Output.UserFunc.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 124,
   "documented": "124",
   "name": "UserFunc_2",
   "description": "Output state; Nilan variable Output.UserFunc_2.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 125,
   "documented": "125",
   "name": "Defrost function active",
   "description": "Output state; Nilan variable Output.Defrosting.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 126,
   "documented": "126",
   "name": "Alarm relay state",
   "description": "Output state; Nilan variable Output.AlarmRelay.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 127,
   "documented": "127",
   "name": "Preheater or earth tube activation",
   "description": "Output state; Nilan variable Output.PreHeat.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 128,
   "documented": "128",
   "name": "EHD or BAH active",
   "description": "Output state; Nilan variable Output.EHD_BAH.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 200,
   "documented": "200",
   "name": "Exhaust fan speed",
   "description": "Nilan variable Output.ExhaustSpeed.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 201,
   "documented": "201",
   "name": "Inlet fan speed",
   "description": "Nilan variable Output.InletSpeed.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 202,
   "documented": "202",
   "name": "Air heater capacity",
   "description": "Nilan variable Output.AirHeatCap.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 203,
   "documented": "203",
   "name": "Central heater capacity",
   "description": "Nilan variable Output.CenHeatCap.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 204,
   "documented": "204",
   "name": "Compresor capacity",
   "description": "Nilan variable Output.CprCap.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 205,
   "documented": "205",
   "name": "Preheater capacity or earth tube air intake fan speed",
   "description": "Nilan variable Output.PreHeatCap.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 206,
   "documented": "206",
   "name": "Rotary heat exchanger",
   "description": "Nilan variable Output.RotorVeksler.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 300,
   "documented": "300",
   "name": "Second",
   "description": "Nilan variable Time.Second.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 301,
   "documented": "301",
   "name": "Minute",
   "description": "Nilan variable Time.Minute.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 302,
   "documented": "302",
   "name": "Hour",
   "description": "Nilan variable Time.Hour.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "h",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 303,
   "documented": "303",
   "name": "Day",
   "description": "Nilan variable Time.Day.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "day",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 304,
   "documented": "304",
   "name": "Month",
   "description": "Nilan variable Time.Month.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "month",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 305,
   "documented": "305",
   "name": "Year",
   "description": "Nilan variable Time.Year.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "year",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 400,
   "documented": "400",
   "name": "Alarm reset",
   "description": "Write 101-199 to clear display code 1-99, 255 to clear all alarms.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No command",
    "255": "Clear all alarms"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 500,
   "documented": "500",
   "name": "Week program nb. select",
   "description": "Nilan variable Program.Select.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "None",
    "1": "Program 1",
    "2": "Program 2",
    "3": "Program 3",
    "4": "Erase"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 600,
   "documented": "600",
   "name": "User function active (See “UserFuncSet”)",
   "description": "Nilan variable Program.UserFuncAct.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 601,
   "documented": "601",
   "name": "User function select",
   "description": "Nilan variable Program.UserFuncSet.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "None",
    "1": "Extend",
    "2": "Inlet",
    "3": "Exhaust",
    "4": "External heater offset",
    "5": "Ventilate",
    "6": "Cooker Hood"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 602,
   "documented": "602",
   "name": "User function period",
   "description": "Nilan variable Program.UserTimeSet.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 603,
   "documented": "603",
   "name": "User function ventilation step select",
   "description": "Nilan variable Program.UserVentSet.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 610,
   "documented": "610",
   "name": "User function 2 active",
   "description": "Same meaning as register 600, for user function 2. Variable Program.User2FuncAct.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 611,
   "documented": "611",
   "name": "User function 2 select",
   "description": "Same meaning as register 601, for user function 2. Variable Program.User2FuncSet.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 612,
   "documented": "612",
   "name": "User function 2 period",
   "description": "Same meaning as register 602, for user function 2. Variable Program.User2TimeSet.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 613,
   "documented": "613",
   "name": "User function 2 ventilation step select",
   "description": "Same meaning as register 603, for user function 2. Variable Program.User2VentSet.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 700,
   "documented": "700",
   "name": "Periodic data log interval select",
   "description": "Nilan variable Log.Interval.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1000,
   "documented": "1000",
   "name": "Machine type select (factory setting)",
   "description": "Nilan variable Control.Type.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1001,
   "documented": "1001",
   "name": "User on / off select (equal to ON/OFF keys)",
   "description": "Nilan variable Control.RunSet.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off (user input functions can still activate operation)",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1002,
   "documented": "1002",
   "name": "User operation mode select",
   "description": "Nilan variable Control.ModeSet.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "Heat (no cooling active)",
    "2": "Cool (no heating active)",
    "3": "Auto",
    "4": "Service (readonly - write to register 1005)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1003,
   "documented": "1003",
   "name": "User ventilation step select",
   "description": "Nilan variable Control.VentSet.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1004,
   "documented": "1004",
   "name": "User temperature setpoint",
   "description": "Nilan variable Control.TempSet.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1005,
   "documented": "1005",
   "name": "Service mode select",
   "description": "Nilan variable Control.ServiceMode.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "Defrost",
    "2": "Flaps",
    "3": "Inlet",
    "4": "Exhaust",
    "5": "Compressor",
    "6": "Heating",
    "7": "Hot water",
    "8": "Central heat"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1006,
   "documented": "1006",
   "name": "Service mode capacity setpoint",
   "description": "Nilan variable Control.ServicePct.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1007,
   "documented": "1007",
   "name": "Request preset to default settings",
   "description": "Nilan variable Control.Preset.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Ready",
    "1": "Standard (to factory defaults)",
    "2": "Backup (to user file)",
    "3": "Restore (from user file)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1100,
   "documented": "1100",
   "name": "Air exchange mode",
   "description": "Nilan variable AirFlow.AirExchMode.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Energy",
    "1": "Comfort",
    "2": "ComfortWater"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1101,
   "documented": "1101",
   "name": "Cooling high ventilation step",
   "description": "Nilan variable AirFlow.CoolVent.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1102,
   "documented": "1102",
   "name": "Select a day for weekly air damper position self-test",
   "description": "Nilan variable AirFlow.TestSelect.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "Monday",
    "2": "Tuesday",
    "3": "Wednesday",
    "4": "Thursday",
    "5": "Friday",
    "6": "Saturday",
    "7": "Sunday"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1103,
   "documented": "1103",
   "name": "Date of last air damper position test",
   "description": "Nilan variable AirFlow.LastTestDay.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1104,
   "documented": "1104",
   "name": "Actual air damper position test state",
   "description": "Nilan variable AirFlow.TestState.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "Standby",
    "2": "Start (Set to Start to run manual test)",
    "3": "Closing",
    "4": "Opening",
    "5": "OK",
    "6": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1105,
   "documented": "1105",
   "name": "Air filter monitoring alarm type and period select",
   "description": "Nilan variable AirFlow.FiltAlmType.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Pressure guard (input)",
    "1": "30 days",
    "2": "90 days",
    "3": "180 days",
    "4": "360 days",
    "5": "70 days and pressure guard"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1200,
   "documented": "1200",
   "name": "Cooling temperature setpoint select",
   "description": "Nilan variable AirTemp.CoolSet.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off (No cooling allowed)",
    "1": "Set + 0 °C (User setpoint plus 0 degrees)",
    "2": "Set + 1 °C",
    "3": "Set + 2 °C",
    "4": "Set + 3 °C",
    "5": "Set + 4 °C",
    "6": "Set + 5 °C",
    "7": "Set + 7 °C",
    "8": "Set + 10 °C"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1201,
   "documented": "1201",
   "name": "Inlet temp. min. summer",
   "description": "Nilan variable AirTemp.TempMinSum.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1202,
   "documented": "1202",
   "name": "Inlet temp. min. winter",
   "description": "Nilan variable AirTemp.TempMinWin.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1203,
   "documented": "1203",
   "name": "Inlet temp. max. summer",
   "description": "Nilan variable AirTemp.TempMaxSum.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1204,
   "documented": "1204",
   "name": "Inlet temp. max. winter",
   "description": "Nilan variable AirTemp.TempMaxWin.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1205,
   "documented": "1205",
   "name": "Summer/winter limit",
   "description": "Nilan variable AirTemp.TempSummer.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1206,
   "documented": "1206",
   "name": "Outdoor day temperature for night cooling activation",
   "description": "Nilan variable AirTemp.NightDayLim.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1207,
   "documented": "1207",
   "name": "Free energy night cooling room setpoint",
   "description": "Nilan variable AirTemp.NightSet.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1208,
   "documented": "1208",
   "name": "Control temperature sensor select",
   "description": "Nilan variable AirTemp.SensorSelect.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "User panel",
    "1": "External sensor",
    "2": "Inlet channel",
    "3": "Exhaust channel"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1209,
   "documented": "1209",
   "name": "Heat source select",
   "description": "Nilan variable AirTemp.HeatSelect.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No heating active",
    "1": "Heat pump only",
    "2": "HP + after-heat",
    "3": "After-heat only",
    "4": "After-heat + HP"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1500,
   "documented": "1500",
   "name": "Condenser temperature curve low",
   "description": "Nilan variable Compressor.CondTempMin.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1501,
   "documented": "1501",
   "name": "Condenser temperature curve high",
   "description": "Nilan variable Compressor.CondTempMax.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1502,
   "documented": "1502",
   "name": "Low temperature compressor start",
   "description": "Nilan variable AirTemp.TempMinCpr.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1700,
   "documented": "1700",
   "name": "Top temperature setpoint (electric)",
   "description": "Nilan variable HotWater.TempSet_T11.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1701,
   "documented": "1701",
   "name": "Bottom temperature setpoint (compressor)",
   "description": "Nilan variable HotWater.TempSet_T12.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1702,
   "documented": "1702",
   "name": "Hot water priority",
   "description": "Nilan variable HotWater.Priority.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Water",
    "1": "Inlet"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1703,
   "documented": "1703",
   "name": "Scald protection Temperature",
   "description": "Nilan variable HotWater.TempCprMax.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1704,
   "documented": "1704",
   "name": "Hot water electric supplement",
   "description": "Nilan variable HotWater.HeatType.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "OFF",
    "1": "El"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1705,
   "documented": "1705",
   "name": "Legionella day",
   "description": "Legionella day; list codes 0 = off to 7 = Sunday (Danish text).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1706,
   "documented": "1706",
   "name": "Bypass offset",
   "description": "Nilan variable HotWater.TempPri.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1800,
   "documented": "1800",
   "name": "External heating offset from room temperature setpoint",
   "description": "Nilan variable CentralHeat.HeatExtern.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1801,
   "documented": "1801",
   "name": "Central heat select",
   "description": "Nilan variable CentralHeat.HeatSelect.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Only pump motion and frost protection",
    "1": "Always central heating",
    "2": "Only central heating when room temperature is low"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1802,
   "documented": "1802",
   "name": "Min supply temperature",
   "description": "Nilan variable CentralHeat.SupplyMin.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1803,
   "documented": "1803",
   "name": "Max supply temperature",
   "description": "Nilan variable CentralHeat.SupplyMax.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1804,
   "documented": "1804",
   "name": "Outdoor temperature compensation",
   "description": "Nilan variable CentralHeat.SupplyOffset.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1805,
   "documented": "1805",
   "name": "Temp. compensation curve",
   "description": "Nilan variable CentralHeat.CurveSelect.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1806,
   "documented": "1806",
   "name": "Central heat circulation pump mode",
   "description": "Nilan variable CentralHeat.CircPumpMode.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Only when heating is active",
    "1": "Continuous operation"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1807,
   "documented": "1807",
   "name": "Central heat type",
   "description": "Nilan variable CentralHeat.HeatType.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "OFF",
    "1": "El",
    "2": "Heatpump",
    "3": "Both (compressor first, then electric)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1808,
   "documented": "1808",
   "name": "PID regulations time",
   "description": "Nilan variable CentralHeat.RegTime.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1910,
   "documented": "1910",
   "name": "Humidity low winter step select",
   "description": "Nilan variable AirQual.RH_VentLo.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1911,
   "documented": "1911",
   "name": "Humidity high step select",
   "description": "Nilan variable AirQual.RH_VentHi.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1912,
   "documented": "1912",
   "name": "Humidity limit for low ventilation",
   "description": "Nilan variable AirQual.RH_LimLo.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1913,
   "documented": "1913",
   "name": "Humidity max. time on high ventilation",
   "description": "Nilan variable AirQual.RH_TimeOut.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1920,
   "documented": "1920",
   "name": "CO2 high step select",
   "description": "Nilan variable AirQual.CO2_VentHi.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1921,
   "documented": "1921",
   "name": "CO2 limit for normal ventilation",
   "description": "Nilan variable AirQual.CO2_LimLo.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "ppm",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1922,
   "documented": "1922",
   "name": "CO2 limit for high ventilation",
   "description": "Nilan variable AirQual.CO2_LimHi.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "ppm",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2003,
   "documented": "2003",
   "name": "HMI language",
   "description": "Nilan variable User.Language.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "English",
    "1": "German",
    "2": "French",
    "3": "Swedish",
    "4": "Danish",
    "5": "Norwegian",
    "6": "Finnish",
    "7": "Czech",
    "8": "Polish",
    "9": "Italian"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2100,
   "documented": "2100",
   "name": "Pre-heater block request",
   "description": "Nilan variable PreHeat.Block.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No command",
    "1": "Request heater block (2 hours)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2200,
   "documented": "2200",
   "name": "Calibrate DPT",
   "description": "Nilan variable DPT.DoCalibrate.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Start calibration"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2201,
   "documented": "2201",
   "name": "Calibrate DPT2",
   "description": "Nilan variable DPT2.DoCalibrate.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Start calibration"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2310,
   "documented": "2310",
   "name": "Step 1 supply air flow",
   "description": "Nilan variable Pressure.Level1InFlow.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "m3/h",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2311,
   "documented": "2311",
   "name": "Step 2 supply air flow",
   "description": "Nilan variable Pressure.Level2InFlow.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "m3/h",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2312,
   "documented": "2312",
   "name": "Step 3 supply air flow",
   "description": "Nilan variable Pressure.Level3InFlow.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "m3/h",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2313,
   "documented": "2313",
   "name": "Step 4 supply air flow",
   "description": "Nilan variable Pressure.Level4InFlow.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "m3/h",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2314,
   "documented": "2314",
   "name": "Step 1 extract air flow",
   "description": "Nilan variable Pressure.Level1OuFlow.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "m3/h",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2315,
   "documented": "2315",
   "name": "Step 2 extract air flow",
   "description": "Nilan variable Pressure.Level2OuFlow.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "m3/h",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2316,
   "documented": "2316",
   "name": "Step 3 extract air flow",
   "description": "Nilan variable Pressure.Level3OuFlow.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "m3/h",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2317,
   "documented": "2317",
   "name": "Step 4 extract air flow",
   "description": "Nilan variable Pressure.Level4OuFlow.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "m3/h",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2320,
   "documented": "2320",
   "name": "Step 1 supply air pressure",
   "description": "Nilan variable Pressure.Level1InPres.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "Pa",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2321,
   "documented": "2321",
   "name": "Step 2 supply air pressure",
   "description": "Nilan variable Pressure.Level2InPres.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "Pa",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2322,
   "documented": "2322",
   "name": "Step 3 supply air pressure",
   "description": "Nilan variable Pressure.Level3InPres.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "Pa",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2323,
   "documented": "2323",
   "name": "Step 4 supply air pressure",
   "description": "Nilan variable Pressure.Level4InPres.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "Pa",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2324,
   "documented": "2324",
   "name": "Step 1 extract air pressure",
   "description": "Nilan variable Pressure.Level1OuPres.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "Pa",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2325,
   "documented": "2325",
   "name": "Step 2 extract air pressure",
   "description": "Nilan variable Pressure.Level2OuPres.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "Pa",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2326,
   "documented": "2326",
   "name": "Step 3 extract air pressure",
   "description": "Nilan variable Pressure.Level3OuPres.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "Pa",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2327,
   "documented": "2327",
   "name": "Step 4 extract air pressure",
   "description": "Nilan variable Pressure.Level4OuPres.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "Pa",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4000,
   "documented": "4000",
   "name": "Regulation deadband external room heating",
   "description": "Nilan variable CentralHeat.HeatExtern.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4001,
   "documented": "4001",
   "name": "High fan speed at high indoor temp (cooling demand)",
   "description": "Nilan variable AirFlow.CoolVent.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4002,
   "documented": "4002",
   "name": "Low outdoor temperature",
   "description": "Nilan variable AirFlow.WinterTemp.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4003,
   "documented": "4003",
   "name": "Fan speed at low outdoor temperature",
   "description": "Nilan variable AirFlow.WinerVent.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4004,
   "documented": "4004",
   "name": "Day for automatic test",
   "description": "Nilan variable AirFlow.TestSelect.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4005,
   "documented": "4005",
   "name": "After heating type",
   "description": "Nilan variable AirHeat.Type.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4006,
   "documented": "4006",
   "name": "Delay timer for after-heat activation",
   "description": "Nilan variable AirHeat.Delay.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4007,
   "documented": "4007",
   "name": "Summer minimum supply air temperature",
   "description": "Nilan variable AirTemp.TempMinSum.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4008,
   "documented": "4008",
   "name": "Summer maximum supply air temperature",
   "description": "Nilan variable AirTemp.TempMaxSum.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4009,
   "documented": "4009",
   "name": "Winter minimum supply air temperature",
   "description": "Nilan variable AirTemp.TempMinWin.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4010,
   "documented": "4010",
   "name": "Winter maximum supply air temperature",
   "description": "Nilan variable AirTemp.TempMaxWin.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4011,
   "documented": "4011",
   "name": "Room temperature regulation deadband",
   "description": "Nilan variable AirTemp.RoomNZ.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4012,
   "documented": "4012",
   "name": "Low room temperature for stepwise reduced ventilation",
   "description": "Nilan variable AirTemp.TempRoomLow.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4013,
   "documented": "4013",
   "name": "After heating activation",
   "description": "Nilan variable AirHeat.SelectSet.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4015,
   "documented": "4015",
   "name": "Min. inlet",
   "description": "Nilan variable AirFlow.InletMin.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4016,
   "documented": "4016",
   "name": "Min exhaust",
   "description": "Nilan variable AirFlow.ExhaustMin.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4017,
   "documented": "4017",
   "name": "Max exhaust",
   "description": "Nilan variable AirFlow.ExhaustMax.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4019,
   "documented": "4019",
   "name": "Damper walkin time",
   "description": "Nilan variable AirBypass.WalkingTime.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4020,
   "documented": "4020",
   "name": "Frost protection or de-icing - Ventilation level",
   "description": "Nilan variable Defrost.Fans.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4021,
   "documented": "4021",
   "name": "Frost protection or de-icing - Bypass position",
   "description": "Nilan variable Defrost.Bypass.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4022,
   "documented": "4022",
   "name": "Frost protection or de-icing - Time between activations",
   "description": "Nilan variable Defrost.BlockMinutes.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4023,
   "documented": "4023",
   "name": "Frost protection or de-icing - Start criteria",
   "description": "Nilan variable Defrost.TempStart.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4024,
   "documented": "4024",
   "name": "Frost protection or de-icing - Stop criteria",
   "description": "Nilan variable Defrost.TempStop.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4025,
   "documented": "4025",
   "name": "Frost protection or de-icing - Max duration compressor",
   "description": "Nilan variable Defrost.DurMaxCpr.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4026,
   "documented": "4026",
   "name": "Frost protection or de-icing - Max duration exchanger",
   "description": "Nilan variable Defrost.DurMaxExh.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4027,
   "documented": "4027",
   "name": "T6 min defrost time",
   "description": "Nilan variable Defrost.T6MinRunSec.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4040,
   "documented": "4040",
   "name": "External fire alarm auto reset",
   "description": "Nilan variable Control.RestartMode.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4041,
   "documented": "4041",
   "name": "Enable power saving features",
   "description": "Nilan variable Control.PowerSave.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4100,
   "documented": "4100",
   "name": "Inlet step 1 speed setup",
   "description": "Nilan variable AirFlow.InletSpd_1.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4101,
   "documented": "4101",
   "name": "Inlet step 2 speed setup",
   "description": "Nilan variable AirFlow.InletSpd_2.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4102,
   "documented": "4102",
   "name": "Inlet step 3 speed setup",
   "description": "Nilan variable AirFlow.InletSpd_3.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4103,
   "documented": "4103",
   "name": "Inlet step 4 speed setup",
   "description": "Nilan variable AirFlow.InletSpd_4.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4104,
   "documented": "4104",
   "name": "Exhaust step 1 speed setup",
   "description": "Nilan variable AirFlow.ExhaustSpd_1.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4105,
   "documented": "4105",
   "name": "Exhaust step 2 speed setup",
   "description": "Nilan variable AirFlow.ExhaustSpd_2.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4106,
   "documented": "4106",
   "name": "Exhaust step 3 speed setup",
   "description": "Nilan variable AirFlow.ExhaustSpd_3.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4107,
   "documented": "4107",
   "name": "Exhaust step 4 speed setup",
   "description": "Nilan variable AirFlow.ExhaustSpd_4.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4108,
   "documented": "4108",
   "name": "Enable Indoor Air Quality (IAQ) control function",
   "description": "Nilan variable AirQual.Type.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4109,
   "documented": "4109",
   "name": "Heater output signal type (if not air channel type)",
   "description": "Nilan variable Control.AnaOutType.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4110,
   "documented": "4110",
   "name": "Room temperature controller response type",
   "description": "Nilan variable AirTemp.RoomResponse.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4111,
   "documented": "4111",
   "name": "Nordic: Select anti frost also during evap. defrost",
   "description": "Nilan variable PreHeat.Defrost.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4112,
   "documented": "4112",
   "name": "T4 start criteria when temperature controlled",
   "description": "Nilan variable PreHeat.TempSet.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Connect to COM1 (CN7 pins 2/3/6) at 19200 8E1, slave 30. Read input registers 200-222 for temperatures and air quality, 1000-1002 for run/mode/state and 400 for alarms; command the unit with holding registers 1001 (on/off), 1002 (mode), 1003 (ventilation step) and 1004 (temperature setpoint, x0.01 °C).",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 1001,
    "why": "On/off"
   },
   {
    "table": "holding_register",
    "address": 1002,
    "why": "Operation mode"
   },
   {
    "table": "holding_register",
    "address": 1003,
    "why": "Ventilation step"
   },
   {
    "table": "holding_register",
    "address": 1004,
    "why": "Temperature setpoint"
   },
   {
    "table": "input_register",
    "address": 1002,
    "why": "Actual control state"
   },
   {
    "table": "input_register",
    "address": 208,
    "why": "Outdoor temperature"
   },
   {
    "table": "input_register",
    "address": 203,
    "why": "Room exhaust temperature"
   },
   {
    "table": "input_register",
    "address": 400,
    "why": "Alarm status"
   }
  ],
  "enable": "No enable step: the CTS602 always answers on COM1. Only the node address can be changed (holding register 50 or the panel); speed and framing are fixed.",
  "watchdog": null,
  "quirks": [
   "Only function codes 03, 04 and 16 are supported; single-register write (06) is not, so write with function 16.",
   "Temperatures are x0.01, not x0.1.",
   "Packet size is limited to 255 bytes."
  ],
  "setup": [
   "COM1 on connector CN7: pin 2 = Data+ (A), pin 3 = Data- (B), pin 6 = ground. COM2 (pins 4/5) is the user panel bus.",
   "Terminate both bus ends with 120 ohm; there is no opto-isolation on the CTS602, so all nodes need a common ground.",
   "Up to 200 m of shielded twisted pair; default node address 30, selectable 1-247."
  ],
  "gotchas": [
   "Holding register 1007 can restore factory defaults (1) or a backup; do not write it casually.",
   "Mode 4 (Service) in 1002 is read-only; service functions are selected through 1005."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/nilan/cts602-hmi350t",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}