 "manufacturer": "Novelan",
 "manufacturer_slug": "novelan",
 "model": "Novelan heat pump controller via Novelan GLT (Modbus TCP)",
 "model_slug": "novelan-glt-modbus-tcp",
 "short_model": "Novelan GLT Modbus",
 "aliases": [
  "Novelan GLT",
  "83055703",
  "ait-deutschland GLT"
 ],
 "equipment_type": "Heat pump",
 "applies_to": "Novelan (ait-deutschland) heat pumps whose heating and heat pump controller runs software V1.74 / V2.74 / V3.76 / V4.76 or later, with the GLT function licensed via the Novelan GLT USB dongle; operating manual 83055703hDE.",
 "summary": "With the GLT licence active, the Novelan heating and heat pump controller is a Modbus TCP slave on port 502 at the controller's own IP address. Discrete inputs show utility block, smart-grid and compressor/heater states; input registers give temperatures, pressures, running hours, plant status, faults, output and 32-bit heat and energy counters; coils reset faults and force pumps on; holding registers take outdoor temperature, setpoints, operating modes, smart-grid state and heating-curve settings.",
 "transport": [
  "TCP"
 ],
 "defaults": {
  "unit_id": null,
  "baud": null,
  "parity": null,
  "data_bits": null,
  "stop_bits": null,
  "tcp_port": 502
 },
 "addressing": {
  "convention": "0-based",
  "note": "The manual warns that registers are 0-based: the printed ID is the wire address (input register 0 = mean outdoor temperature, holding register 0 = outdoor temperature)."
 },
 "default_word_order": "ABCD",
 "firmware": "Controller software V1.74/V2.74/V3.76/V4.76 or later for Modbus TCP",
 "source": {
  "title": "Zubehör für Wärmepumpen - Anbindung an eine Gebäudeleittechnik via BACnet/IP | ModBus/TCP - Novelan GLT (Betriebsanleitung)",
  "doc_number": "83055703hDE",
  "revision_date": null,
  "url": "https://forum.iobroker.net/assets/uploads/files/1732701258966-83055703hde_novelan_glt.pdf",
  "unofficial": true,
  "pages": "p. 3 software requirements; p. 4 licence; p. 17 Modbus specification (0-based note, port 502); pp. 18-22 data points (discrete inputs, input registers, coils, holding registers); p. 23 abbreviations"
 },
 "notes": [
  "ait-deutschland / Novelan do not appear to host this manual publicly; the link is an unaltered copy of the manufacturer's PDF posted on the ioBroker forum.",
  "The manual calls all registers integer values without stating signedness. Temperatures and the holding offset 23 are listed as INT16 because the holding outdoor temperature accepts -200 (= -20.0 °C) and the offset -50; the input-register temperatures have no printed range, so negative readings assume two's complement.",
  "'Auflösung 10' means tenths (scale 0.1) and 'Auflösung 100' hundredths (scale 0.01). Heat and energy counters are printed in 'kW/h' and are taken as kWh.",
  "Each 32-bit counter is split into High and Low registers; the manual says to shift High 16 bits left and add Low, with High at the lower ID, so they are listed as UINT32 high word first.",
  "Data points marked * in the manual exist only on units with LIN and/or Modbus components; greyed points need a comfort/extension or ventilation board. Values for points not visible on the controller display are invalid.",
  "Discrete inputs exist only for IDs 0-7. Coil 1 is reserved and left out.",
  "Coils read 0 = off and 1 = on. Writing 1 forces the output on; writing 0 hands it back to automatic control."
 ],
 "registers": [
  {
   "table": "coil",
   "address": 0,
   "documented": "0",
   "name": "Fehlerreset",
   "description": "Write 1 to acknowledge the currently active fault.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 2,
   "documented": "2",
   "name": "HUP",
   "description": "Force the HUP pump on",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Automatic",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 3,
   "documented": "3",
   "name": "VEN",
   "description": "Force fan on",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Automatic",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 4,
   "documented": "4",
   "name": "ZUP",
   "description": "Force auxiliary circulation pump on",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Automatic",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 5,
   "documented": "5",
   "name": "BUP",
   "description": "Force hot water circulation pump on",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Automatic",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 6,
   "documented": "6",
   "name": "BOSUP",
   "description": "Force well/brine pump on",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Automatic",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 7,
   "documented": "7",
   "name": "ZIP",
   "description": "Force DHW circulation pump on",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Automatic",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 8,
   "documented": "8",
   "name": "FUP2",
   "description": "Force floor heating pump 2 on",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Automatic",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 9,
   "documented": "9",
   "name": "FUP3",
   "description": "Force floor heating pump 3 on",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Automatic",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 10,
   "documented": "10",
   "name": "SLP",
   "description": "Force solar charge pump on",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Automatic",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 11,
   "documented": "11",
   "name": "SUP",
   "description": "Force pool circulation pump on",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Automatic",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 12,
   "documented": "12",
   "name": "VSK",
   "description": "Force the bypass flap (VSK) on",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Automatic",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 13,
   "documented": "13",
   "name": "FRH",
   "description": "Force defroster heater contactor on",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Automatic",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 0,
   "documented": "0",
   "name": "EVU",
   "description": "Utility blocking time (EVU) input",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 1,
   "documented": "1",
   "name": "EVU2",
   "description": "Smart grid input EVU2",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 2,
   "documented": "2",
   "name": "SWT",
   "description": "Pool thermostat input",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 3,
   "documented": "3",
   "name": "VD1",
   "description": "Compressor 1",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 4,
   "documented": "4",
   "name": "VD2",
   "description": "Compressor 2",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 5,
   "documented": "5",
   "name": "ZWE1",
   "description": "Auxiliary heater 1",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 6,
   "documented": "6",
   "name": "ZWE2",
   "description": "Auxiliary heater 2",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 7,
   "documented": "7",
   "name": "ZWE3",
   "description": "Auxiliary heater 3",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 0,
   "documented": "0",
   "name": "Mitteltemperatur",
   "description": "Mean outdoor temperature",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1,
   "documented": "1",
   "name": "Vorlauftemperatur",
   "description": "Flow temperature",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2,
   "documented": "2",
   "name": "Rücklauftemperatur",
   "description": "Return temperature",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3,
   "documented": "3",
   "name": "Rücklauf extern",
   "description": "External return temperature",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 4,
   "documented": "4",
   "name": "Trinkwarmwassertemperatur",
   "description": "Hot water temperature",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 5,
   "documented": "5",
   "name": "Mischkreis 1 Vorlauf",
   "description": "Mixing circuit 1 flow temperature",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 6,
   "documented": "6",
   "name": "Mischkreis 2 Vorlauf",
   "description": "Mixing circuit 2 flow temperature",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 7,
   "documented": "7",
   "name": "Mischkreis 3 Vorlauf",
   "description": "Mixing circuit 3 flow temperature",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 8,
   "documented": "8",
   "name": "Heissgastemperatur",
   "description": "Hot gas temperature",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 9,
   "documented": "9",
   "name": "Wärmequelle Eintritt",
   "description": "Heat source inlet temperature",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 10,
   "documented": "10",
   "name": "Wärmequelle Austritt",
   "description": "Heat source outlet temperature",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 11,
   "documented": "11",
   "name": "Raumfernversteller 1",
   "description": "Remote room unit 1 temperature",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 12,
   "documented": "12",
   "name": "Raumfernversteller 2",
   "description": "Remote room unit 2 temperature",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 13,
   "documented": "13",
   "name": "Raumfernversteller 3",
   "description": "Remote room unit 3 temperature",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 14,
   "documented": "14",
   "name": "Solarkollektor",
   "description": "Solar collector temperature",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 15,
   "documented": "15",
   "name": "Solarspeicher",
   "description": "Solar tank temperature",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 16,
   "documented": "16",
   "name": "Externe Energiequelle",
   "description": "External energy source temperature",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 17,
   "documented": "17",
   "name": "Zulufttemperatur",
   "description": "Supply air temperature",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 18,
   "documented": "18",
   "name": "Ablufttemperatur",
   "description": "Extract air temperature",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 19,
   "documented": "19",
   "name": "Ansaugtemperatur Verdichter",
   "description": "Compressor suction temperature (LIN/Modbus units)",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 20,
   "documented": "20",
   "name": "Ansaugtemperatur Verdampfer",
   "description": "Evaporator suction temperature (LIN/Modbus units)",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 21,
   "documented": "21",
   "name": "Temperatur Verdichterheizung",
   "description": "Compressor heater temperature (LIN/Modbus units)",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 22,
   "documented": "22",
   "name": "Überhitzung",
   "description": "Superheat (LIN/Modbus units).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "K",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 23,
   "documented": "23",
   "name": "Überhitzung Soll",
   "description": "Superheat setpoint (LIN/Modbus units).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "K",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 24,
   "documented": "24",
   "name": "RBE Raumtemperatur Ist",
   "description": "Room control unit actual temperature.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 25,
   "documented": "25",
   "name": "RBE Raumtemperatur Soll",
   "description": "Room control unit setpoint.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 26,
   "documented": "26",
   "name": "Druck HD (Hochdruck)",
   "description": "High pressure (LIN/Modbus units).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "bar",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 27,
   "documented": "27",
   "name": "Druck ND (Niederdruck)",
   "description": "Low pressure (LIN/Modbus units).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "bar",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 28,
   "documented": "28",
   "name": "Betriebsstunden VD 1",
   "description": "Compressor 1 hours",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 29,
   "documented": "29",
   "name": "Betriebsstunden VD 2",
   "description": "Compressor 2 hours",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 30,
   "documented": "30",
   "name": "Betriebsstunden ZWE 1",
   "description": "Aux heater 1 hours",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 31,
   "documented": "31",
   "name": "Betriebsstunden ZWE 2",
   "description": "Aux heater 2 hours",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 32,
   "documented": "32",
   "name": "Betriebsstunden ZWE 3",
   "description": "Aux heater 3 hours",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 33,
   "documented": "33",
   "name": "Betriebsstunden Wärmepumpe",
   "description": "Heat pump hours",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 34,
   "documented": "34",
   "name": "Betriebsstunden Heizung",
   "description": "Heating hours",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 35,
   "documented": "35",
   "name": "Betriebsstunden Trinkwarmwasser",
   "description": "Hot water hours",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 36,
   "documented": "36",
   "name": "Betriebsstunden SWoPV",
   "description": "Pool or photovoltaic (SWoPV) hours",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 37,
   "documented": "37",
   "name": "Anlagenstatus",
   "description": "Plant status.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Heating",
    "1": "Hot water",
    "2": "Swimming pool",
    "3": "Utility block (EVU)",
    "4": "Defrost",
    "5": "Off",
    "6": "External energy source",
    "7": "Cooling"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 38,
   "documented": "38-39",
   "name": "Wärmemenge Heizung",
   "description": "Heat quantity, heating; High word at 38, Low word at 39.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 40,
   "documented": "40-41",
   "name": "Wärmemenge Trinkwarmwasser",
   "description": "Heat quantity, hot water; High word at 40, Low word at 41.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 42,
   "documented": "42-43",
   "name": "Wärmemenge Schwimmbad",
   "description": "Heat quantity, pool; High word at 42, Low word at 43.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 44,
   "documented": "44-45",
   "name": "Wärmemenge gesamt",
   "description": "Heat quantity, total; High word at 44, Low word at 45.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 46,
   "documented": "46",
   "name": "Fehlerspeicher",
   "description": "Number of the currently active fault only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 47,
   "documented": "47",
   "name": "Leistung Ist",
   "description": "Actual heating output.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "kW",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 48,
   "documented": "48-49",
   "name": "Wärmemenge Kühlung",
   "description": "Heat quantity, cooling; High word at 48, Low word at 49.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 50,
   "documented": "50-51",
   "name": "Eingesetzte Energie Heizung",
   "description": "Energy used, heating; High word at 50, Low word at 51.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 52,
   "documented": "52-53",
   "name": "Eingesetzte Energie Trinkwarmwasser",
   "description": "Energy used, hot water; High word at 52, Low word at 53.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 54,
   "documented": "54-55",
   "name": "Eingesetzte Energie Kühlung",
   "description": "Energy used, cooling; High word at 54, Low word at 55.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 56,
   "documented": "56-57",
   "name": "Eingesetzte Energie Schwimmbad",
   "description": "Energy used, pool; High word at 56, Low word at 57.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 58,
   "documented": "58-59",
   "name": "Eingesetzte Energie gesamt",
   "description": "Energy used, total; High word at 58, Low word at 59.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 0,
   "documented": "0",
   "name": "Außentemperatur",
   "description": "Outdoor temperature sent by the BMS, -20.0 to 80.0.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1,
   "documented": "1",
   "name": "Rücklauf-Temperatur Soll",
   "description": "Return temperature setpoint, 15.0-80.0.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "2",
   "name": "Mischkreis 1 Vorlauf Solltemperatur",
   "description": "Mixing circuit 1 flow setpoint, 15.0-80.0.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3,
   "documented": "3",
   "name": "Mischkreis 2 Vorlauf Solltemperatur",
   "description": "Mixing circuit 2 flow setpoint, 15.0-80.0.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4,
   "documented": "4",
   "name": "Mischkreis 3 Vorlauf Solltemperatur",
   "description": "Mixing circuit 3 flow setpoint, 15.0-80.0.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5,
   "documented": "5",
   "name": "Trinkwarmwasser-Temperatur Wunschwert",
   "description": "Hot water setpoint, 15.0-80.0.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6,
   "documented": "6",
   "name": "Sperre / Freigabe Wärmepumpe",
   "description": "Heat pump block / release.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Heat pump blocked",
    "1": "Release 1 compressor",
    "2": "Release 2 compressors"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 7,
   "documented": "7",
   "name": "Betriebsart Heizung",
   "description": "Heating operating mode.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Automatic",
    "1": "Additional heat generator",
    "2": "Party",
    "3": "Holiday",
    "4": "Off"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8,
   "documented": "8",
   "name": "Betriebsart Trinkwarmwasser",
   "description": "Hot water operating mode.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Automatic",
    "1": "Additional heat generator",
    "2": "Party",
    "3": "Holiday",
    "4": "Off"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9,
   "documented": "9",
   "name": "Betriebsart Mischkreis 2",
   "description": "Mixing circuit 2 mode.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Automatic",
    "1": "Additional heat generator",
    "2": "Party",
    "3": "Holiday",
    "4": "Off"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10,
   "documented": "10",
   "name": "Betriebsart Mischkreis 3",
   "description": "Mixing circuit 3 mode.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Automatic",
    "1": "Additional heat generator",
    "2": "Party",
    "3": "Holiday",
    "4": "Off"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11,
   "documented": "11",
   "name": "Betriebsart Kühlung",
   "description": "Cooling mode.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "Automatic"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 12,
   "documented": "12",
   "name": "Betriebsart Lüftung",
   "description": "Ventilation mode.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Automatic",
    "1": "Party",
    "2": "Holiday",
    "3": "Off"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 13,
   "documented": "13",
   "name": "Betriebsart Schwimmbad",
   "description": "Swimming pool mode.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Automatic",
    "1": "Not used",
    "2": "Party",
    "3": "Holiday",
    "4": "Off"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14,
   "documented": "14",
   "name": "Smart Grid",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Utility block (EVU)",
    "1": "Smart Grid Low",
    "2": "Standard",
    "3": "Smart Grid High"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 15,
   "documented": "15",
   "name": "Heizkurve Heizung Endpunkt",
   "description": "Heating curve end point, 20.0-70.0.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16,
   "documented": "16",
   "name": "Heizkurve Heizung Parallelverschiebung",
   "description": "Heating curve parallel shift, 5.0-35.0.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 17,
   "documented": "17",
   "name": "Heizkurve Mischkreis 1 Endpunkt",
   "description": "Mixing circuit 1 curve end point, 20.0-70.0.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 18,
   "documented": "18",
   "name": "Heizkurve Mischkreis 1 Parallelverschiebung",
   "description": "Mixing circuit 1 curve parallel shift, 5.0-35.0.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 19,
   "documented": "19",
   "name": "Heizkurve Mischkreis 2 Endpunkt",
   "description": "Mixing circuit 2 curve end point, 20.0-70.0.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 20,
   "documented": "20",
   "name": "Heizkurve Mischkreis 2 Parallelverschiebung",
   "description": "Mixing circuit 2 curve parallel shift, 5.0-35.0.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 21,
   "documented": "21",
   "name": "Heizkurve Mischkreis 3 Endpunkt",
   "description": "Mixing circuit 3 curve end point, 20.0-70.0.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 22,
   "documented": "22",
   "name": "Heizkurve Mischkreis 3 Parallelverschiebung",
   "description": "Mixing circuit 3 curve parallel shift, 5.0-35.0.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 23,
   "documented": "23",
   "name": "Temperatur + -",
   "description": "Temperature offset, -5.0 to 5.0.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "License GLT with the supplied USB dongle, then poll input registers 0-59 and discrete inputs 0-7 over Modbus TCP and write holding registers 0-23 for outdoor temperature, setpoints and modes.",
  "minimum_registers": [
   {
    "table": "input_register",
    "address": 37,
    "why": "Plant status"
   },
   {
    "table": "input_register",
    "address": 0,
    "why": "Mean outdoor temperature"
   },
   {
    "table": "input_register",
    "address": 1,
    "why": "Flow temperature"
   },
   {
    "table": "input_register",
    "address": 2,
    "why": "Return temperature"
   },
   {
    "table": "input_register",
    "address": 4,
    "why": "Hot water temperature"
   },
   {
    "table": "input_register",
    "address": 46,
    "why": "Active fault"
   },
   {
    "table": "holding_register",
    "address": 1,
    "why": "Return temperature setpoint"
   },
   {
    "table": "holding_register",
    "address": 7,
    "why": "Heating mode"
   },
   {
    "table": "holding_register",
    "address": 14,
    "why": "Smart grid state"
   },
   {
    "table": "coil",
    "address": 0,
    "why": "Fault reset"
   }
  ],
  "enable": "Configure GLT with the Novelan GLT Tool, then insert the supplied USB dongle in the controller's USB port to unlock GLT permanently (otherwise only a test phase runs). Check Service > Informationen > GLT on the controller.",
  "watchdog": null,
  "quirks": [
   "To stop forcing a value, write a value outside its limits (holding registers) or 0 (coils); otherwise the written value stays in force.",
   "Only the currently active fault is shown in input register 46."
  ],
  "setup": [
   "Modbus TCP uses the controller's IP address and port 502; set the IP under Service > Systemsteuerung (DHCP server, DHCP client or fixed IP)."
  ],
  "gotchas": [
   "Controllers with software older than the Modbus TCP versions listed can only use BACnet/IP."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/novelan/novelan-glt-modbus-tcp",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}