 "manufacturer": "Novus",
 "manufacturer_slug": "novus",
 "model": "N20K48 modular process controller (Modbus RTU)",
 "model_slug": "n20k48",
 "short_model": "N20K48",
 "aliases": [
  "Novus N20K48",
  "N20K48 modular controller"
 ],
 "equipment_type": "Sensor (process / temperature controller)",
 "applies_to": "N20K48 controllers with the optional RS-485 interface, communication protocol V1.0x.",
 "summary": "The Novus N20K48 is a modular PID temperature and process controller with optional RS-485 Modbus RTU. All registers are 16-bit holding registers covering identity, input configuration, control, tuning, timers, alarms and ramp/soak programs. This map covers the setpoint, process variable, output, run/auto modes, input setup, tuning and alarm setpoints.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": null,
  "baud": null,
  "parity": null,
  "data_bits": null,
  "stop_bits": null,
  "tcp_port": null
 },
 "addressing": {
  "convention": "0-based",
  "note": "The register table lists addresses from 0 (INFO_ID), which only fits 0-based protocol addresses; send the printed number unchanged. Add 1 (or 40001) for a 1-based or Modicon tool."
 },
 "default_word_order": null,
 "firmware": "Protocol V1.0x",
 "source": {
  "title": "N20K48 Modular Controller - Communication Protocol V1.0x",
  "doc_number": null,
  "revision_date": null,
  "url": "https://cdn.shopify.com/s/files/1/2586/3536/files/n20k48_communication_protocol.pdf",
  "unofficial": true,
  "pages": "interface and function codes p. 3; register table pp. 4-32"
 },
 "notes": [
  "This copy is hosted on a reseller's Shopify store; it is the Novus N20K48 Communication Protocol V1.0x document.",
  "Function codes 03, 05, 06 and 16 are supported; the manual says all registers are 16-bit integers. Signed types are used where a published range goes negative.",
  "Scaling: the PV of a temperature input is always the value times 10, whatever INPUT_DPPO says; for linear inputs, PV and setpoint decimals follow INPUT_DPPO (279). Setpoint-type registers are listed unscaled because the manual does not say whether the x10 rule also applies to them.",
  "Left out: AI_DIAG (88) and the status words, whose bit numbering (printed from bit 1) is not tied to bit 0 in the text; serial-number, Bluetooth name and ramp/soak program registers; dual-word input limits 78-81 and 103-106, whose word order is not stated.",
  "Serial settings are made at the controller; the protocol document gives no defaults.",
  "Addressing rests on the register table starting at address 0 with a real register (INFO_ID); the document has no request-frame example."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 0,
   "documented": "0",
   "name": "INFO_ID device ID",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1,
   "documented": "1",
   "name": "INFO_FW_VERSION firmware version",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "2",
   "name": "INFO_FW_RELEASE firmware release",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 74,
   "documented": "74",
   "name": "AI_ENABLE analog input enable",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 75,
   "documented": "75",
   "name": "AI_TYPE input sensor type",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "T/C J",
    "1": "T/C K",
    "2": "T/C T",
    "3": "T/C N",
    "4": "T/C R",
    "5": "T/C S",
    "6": "T/C B",
    "7": "T/C E",
    "8": "Pt100",
    "9": "0-20 mA",
    "10": "4-20 mA",
    "11": "0-50 mV",
    "12": "0-5 V",
    "13": "0-10 V"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 76,
   "documented": "76",
   "name": "AI_FILTER input filter",
   "description": "One decimal place.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 77,
   "documented": "77",
   "name": "AI_UNIT temperature unit",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "°C",
    "1": "°F"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 87,
   "documented": "87",
   "name": "AI_GRID_FREQ mains frequency",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "50 Hz",
    "1": "60 Hz"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 110,
   "documented": "110",
   "name": "PULSE_ENABLE pulse output enable",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 111,
   "documented": "111",
   "name": "RELAY_ENABLE relay output enable",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 112,
   "documented": "112",
   "name": "PULSE_STATE pulse output status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 113,
   "documented": "113",
   "name": "RELAY_STATE relay output status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 200,
   "documented": "200",
   "name": "CTRL_SP control setpoint",
   "description": "Main setpoint, between SPLL and SPHL; decimal point per INPUT_DPPO (279).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 201,
   "documented": "201",
   "name": "CTRL_PV1 process variable",
   "description": "Temperature inputs: always value x 10. Linear inputs: decimals per INPUT_DPPO.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 202,
   "documented": "202",
   "name": "CTRL_MV1 control output power",
   "description": "0-1000 = 0.0-100.0 %, manual or automatic.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 210,
   "documented": "210",
   "name": "CTRL_REMOTE_SP_EN remote setpoint enable",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 211,
   "documented": "211",
   "name": "CTRL_REMOTE_SP remote setpoint",
   "description": "Between SPLL and SPHL; decimal point per INPUT_DPPO.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 212,
   "documented": "212",
   "name": "CTRL_ACT control action",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Inverse",
    "1": "Direct"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 213,
   "documented": "213",
   "name": "CTRL_AUTO control mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Manual",
    "1": "Automatic"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 214,
   "documented": "214",
   "name": "CTRL_RUN run",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 215,
   "documented": "215",
   "name": "CTRL_IE_MV_ONOFF on/off output on input error",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 226,
   "documented": "226",
   "name": "CTRL_SFST soft start time",
   "description": "0-9999 s.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 257,
   "documented": "257",
   "name": "TUNE_AUTO auto-tuning mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "Fast auto-tune",
    "2": "Precise auto-tune",
    "3": "Self-adaptive + precise",
    "4": "Force new precise + self-adaptive",
    "5": "Force new precise when RUN or at power-up"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 258,
   "documented": "258",
   "name": "TUNE_PB proportional band",
   "description": "Range 0-5000.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 259,
   "documented": "259",
   "name": "TUNE_IR integral rate",
   "description": "Range 0-2400.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "rep/min",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 260,
   "documented": "260",
   "name": "TUNE_DT derivative time",
   "description": "Range 0-2400.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 261,
   "documented": "261",
   "name": "TUNE_CT PWM cycle time",
   "description": "Range 5-1000.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 279,
   "documented": "279",
   "name": "INPUT_DPPO decimal point position",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "XXXX",
    "1": "XXX.X",
    "2": "XX.XX",
    "3": "X.XXX"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 280,
   "documented": "280",
   "name": "INPUT_LL_PV1 sensor lower limit",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 281,
   "documented": "281",
   "name": "INPUT_HL_PV1 sensor upper limit",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 310,
   "documented": "310",
   "name": "FUA1 alarm 1 function",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "Lo",
    "2": "Hi",
    "3": "DiF",
    "4": "DIf.L",
    "5": "DIF.H",
    "6": "i.Err",
    "7": "rS",
    "8": "End.t",
    "9": "Lbd"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 311,
   "documented": "311",
   "name": "SPA1 alarm 1 setpoint",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 319,
   "documented": "319",
   "name": "FUA2 alarm 2 function",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "Lo",
    "2": "Hi",
    "3": "DiF",
    "4": "DIf.L",
    "5": "DIF.H",
    "6": "i.Err",
    "7": "rS",
    "8": "End.t",
    "9": "Lbd"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 320,
   "documented": "320",
   "name": "SPA2 alarm 2 setpoint",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 328,
   "documented": "328",
   "name": "FUA3 alarm 3 function",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "Lo",
    "2": "Hi",
    "3": "DiF",
    "4": "DIf.L",
    "5": "DIF.H",
    "6": "i.Err",
    "7": "rS",
    "8": "End.t",
    "9": "Lbd"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 329,
   "documented": "329",
   "name": "SPA3 alarm 3 setpoint",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 337,
   "documented": "337",
   "name": "FUA4 alarm 4 function",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "Lo",
    "2": "Hi",
    "3": "DiF",
    "4": "DIf.L",
    "5": "DIF.H",
    "6": "i.Err",
    "7": "rS",
    "8": "End.t",
    "9": "Lbd"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 338,
   "documented": "338",
   "name": "SPA4 alarm 4 setpoint",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Poll 200-202 for setpoint, PV and output power. Write 200 to change the setpoint, 214 to run/stop control and 213 for manual/automatic.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 201,
    "why": "Process variable"
   },
   {
    "table": "holding_register",
    "address": 200,
    "why": "Setpoint"
   },
   {
    "table": "holding_register",
    "address": 202,
    "why": "Output power 0.1 %"
   },
   {
    "table": "holding_register",
    "address": 214,
    "why": "Run control"
   },
   {
    "table": "holding_register",
    "address": 213,
    "why": "Manual/automatic"
   },
   {
    "table": "holding_register",
    "address": 279,
    "why": "Decimal point position"
   }
  ],
  "enable": "Fit the RS-485 option and set address and serial parameters on the controller.",
  "watchdog": null,
  "quirks": [
   "Addresses are 0-based.",
   "Temperature PV is x10 regardless of the decimal-point setting."
  ],
  "setup": [
   "Up to 247 controllers on one RS-485 line; terminals 3 (D1/D+/B), 2 (D0/D-/A), 1 (GND)."
  ],
  "gotchas": [
   "Setpoint writes are limited to SPLL/SPHL (220/221)."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/novus/n20k48",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}