 "manufacturer": "Omron",
 "manufacturer_slug": "omron",
 "model": "E5CC / E5EC / E5AC / E5DC digital temperature controllers (E5_C series)",
 "model_slug": "e5-c-series",
 "short_model": "E5CC / E5EC",
 "aliases": [
  "E5CC",
  "E5EC",
  "E5AC",
  "E5DC",
  "E5CC-U",
  "E5@C",
  "E5_C"
 ],
 "equipment_type": "Sensor (digital temperature controller)",
 "applies_to": "Omron E5CC, E5EC, E5AC, E5DC and E5CC-U controllers with RS-485, per the E5_C Communications Manual H175; registers present depend on model and options.",
 "summary": "Omron's E5_C temperature controllers speak CompoWay/F or Modbus RTU on their RS-485 option. The variable area can be read in 4-byte mode (two registers per value) or 2-byte mode (one register per value, addresses from 0x2000); this map uses 2-byte mode for PV, set points, MV, heater current, alarms and status, plus the operation-command register for RUN/STOP, auto/manual and auto-tune.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": 1,
  "baud": null,
  "parity": null,
  "data_bits": 8,
  "stop_bits": null,
  "tcp_port": null
 },
 "addressing": {
  "convention": "hex 0-based",
  "note": "Addresses are printed in hex and sent as-is: the manual's 2-byte example reads PV with 01 03 20 00 00 01. 4-byte mode addresses (0000, 0002, ...) hold the same data as two registers each; only 2-byte mode addresses are listed here."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "E5@C Digital Temperature Controllers Communications Manual",
  "doc_number": "H175-E1-17",
  "revision_date": "2022-09",
  "url": "https://files.omron.eu/downloads/latest/manual/en/h175_e5_c_communications_manual_en.pdf",
  "pages": "Comm parameters p. 1-6; Modbus procedure pp. 4-7 to 4-14 (modes, examples, operation commands); variable area pp. 5-2 to 5-16; status bits pp. 3-23 to 3-25 (PDF pp. 75-77, 96)"
 },
 "notes": [
  "Values are sent without the decimal point (105.0 is sent as 1050). PV, set points and alarm values use the decimal places reported by 2410; MV (x0.1 %) and heater current (x0.1 A) have fixed scaling per the setting ranges.",
  "In 2-byte mode 2001 and 2406 return the low 16 bits of the 32-bit status and 2407 the high 16 bits; bit meanings come from the status table on pp. 3-23 to 3-25.",
  "Before any write, send operation command 'communications writing ON' (0x0001 to address FFFF). FC06 single writes work only in 2-byte mode; FC16 works in both.",
  "The manual states a default unit number of 1 and a default send data wait of 20 ms; default baud rate and parity are only shown as highlighted cells, so they are not listed. With Modbus the data length is fixed at 8 bits, with 1 stop bit for even/odd parity or 2 for none.",
  "Left out: the rest of the adjustment, initial-setting and advanced levels (PID, scaling, input type and so on), alarm 3/4 values, valve opening, and program/SP ramp parameters."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 8192,
   "documented": "2000",
   "name": "PV",
   "description": "Process value. Raw value without decimal point; decimal places per 2410.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8193,
   "documented": "2001",
   "name": "Status (low word)",
   "description": "Bits 0-15 of the 32-bit status.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Heater overcurrent (CT1)",
    "1": "Heater current hold (CT1)",
    "2": "A/D converter error",
    "3": "HS alarm (CT1)",
    "4": "RSP input error",
    "6": "Input error",
    "7": "Potentiometer input error",
    "8": "Control output (heating) / open output ON",
    "9": "Control output (cooling) / close output ON",
    "10": "HB alarm (CT1)",
    "11": "HB alarm (CT2)",
    "12": "Alarm 1",
    "13": "Alarm 2",
    "14": "Alarm 3",
    "15": "Program end output"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8194,
   "documented": "2002",
   "name": "Internal set point",
   "description": "Raw value without decimal point; decimal places per 2410.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8195,
   "documented": "2003",
   "name": "Heater current 1",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8196,
   "documented": "2004",
   "name": "MV monitor (heating)",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8197,
   "documented": "2005",
   "name": "MV monitor (cooling)",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8451,
   "documented": "2103",
   "name": "Set point",
   "description": "Raw value without decimal point; decimal places per 2410.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8452,
   "documented": "2104",
   "name": "Alarm value 1",
   "description": "Raw value without decimal point; decimal places per 2410.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8453,
   "documented": "2105",
   "name": "Alarm 1 upper limit",
   "description": "Raw value without decimal point; decimal places per 2410.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8454,
   "documented": "2106",
   "name": "Alarm 1 lower limit",
   "description": "Raw value without decimal point; decimal places per 2410.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8455,
   "documented": "2107",
   "name": "Alarm value 2",
   "description": "Raw value without decimal point; decimal places per 2410.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8456,
   "documented": "2108",
   "name": "Alarm 2 upper limit",
   "description": "Raw value without decimal point; decimal places per 2410.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8457,
   "documented": "2109",
   "name": "Alarm 2 lower limit",
   "description": "Raw value without decimal point; decimal places per 2410.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9220,
   "documented": "2404",
   "name": "Multi-SP number",
   "description": "Active set point 0-7.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9223,
   "documented": "2407",
   "name": "Status (high word)",
   "description": "Bits 16-31 of the 32-bit status, shown here as bits 0-15.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Event input 1",
    "1": "Event input 2",
    "2": "Event input 3",
    "3": "Event input 4",
    "4": "Write mode (1 = RAM write mode)",
    "5": "Non-volatile memory differs from RAM",
    "6": "Setup area 1",
    "7": "AT in progress",
    "8": "Stop (0 = Run)",
    "9": "Communications writing enabled",
    "10": "Manual mode (0 = automatic)",
    "11": "Program start",
    "12": "Heater overcurrent (CT2)",
    "13": "Heater current hold (CT2)",
    "15": "HS alarm (CT2)"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9232,
   "documented": "2410",
   "name": "Decimal point monitor",
   "description": "Decimal places (0-3) used by PV, SP and alarm values.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9728,
   "documented": "2600",
   "name": "Manual MV",
   "description": "Output in manual mode.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9729,
   "documented": "2601",
   "name": "Set point (operation level)",
   "description": "Raw value without decimal point; decimal places per 2410.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9730,
   "documented": "2602",
   "name": "Remote SP monitor",
   "description": "Raw value without decimal point; decimal places per 2410.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 65535,
   "documented": "FFFF",
   "name": "Operation command",
   "description": "FC06 only: command code in the high byte, related information in the low byte.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": {
    "0": "0x0000: communications writing OFF",
    "1": "0x0001: communications writing ON",
    "256": "0x0100: RUN",
    "257": "0x0101: STOP",
    "768": "0x0300: AT cancel",
    "769": "0x0301: 100% AT execute",
    "770": "0x0302: 40% AT execute",
    "1024": "0x0400: backup write mode",
    "1025": "0x0401: RAM write mode",
    "1280": "0x0500: save RAM data",
    "1536": "0x0600: software reset",
    "2304": "0x0900: automatic mode",
    "2305": "0x0901: manual mode",
    "3087": "0x0C0F: cancel all alarm latches",
    "3328": "0x0D00: local SP mode",
    "3329": "0x0D01: remote SP mode"
   },
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Read 0x2000-0x2005 with FC03 for PV, status, internal SP, heater current and MV; read 0x2410 once for the decimal point. To change the set point, first write 0x0001 to 0xFFFF (communications writing ON), then write 0x2103.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 8192,
    "why": "PV"
   },
   {
    "table": "holding_register",
    "address": 8193,
    "why": "Status low word (alarms, errors, outputs)"
   },
   {
    "table": "holding_register",
    "address": 8196,
    "why": "Heating MV"
   },
   {
    "table": "holding_register",
    "address": 8451,
    "why": "Set point"
   },
   {
    "table": "holding_register",
    "address": 9223,
    "why": "Status high word (run/stop, auto/manual)"
   },
   {
    "table": "holding_register",
    "address": 9232,
    "why": "Decimal point"
   },
   {
    "table": "holding_register",
    "address": 65535,
    "why": "Operation command (write enable, RUN/STOP)"
   }
  ],
  "enable": "Set Protocol Setting (psel) to Modbus in the communications setting level, set unit number and baud, then cycle power. Writes need 'communications writing ON' via the operation command.",
  "watchdog": null,
  "quirks": [
   "Values carry no decimal point; check 2410.",
   "Use 2-byte mode addresses (0x2000+) for 16-bit tools; 4-byte mode needs even addresses and even counts.",
   "Reading in setup area 1 freezes or clears some status bits."
  ],
  "setup": [
   "Protocol (psel), unit no. (u-no, default 1), baud (bps), parity (prty) and send data wait (sdwt, default 20 ms) are set on the front panel in the communications setting level; reset the controller to apply changes.",
   "Up to 106 registers per read in 2-byte mode."
  ],
  "gotchas": [
   "In backup mode every communications write of an operation/adjustment parameter is also saved to non-volatile memory; RAM write mode (0x0401) skips that until backup mode or 'save RAM data'."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/omron/e5-c-series",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}