 "manufacturer": "Panasonic",
 "manufacturer_slug": "panasonic",
 "model": "KW8M Eco-POWER METER",
 "model_slug": "kw8m",
 "short_model": "KW8M",
 "aliases": [
  "AKW8111",
  "AKW8111H"
 ],
 "equipment_type": "Energy meter",
 "applies_to": "Panasonic KW8M AKW8111 and AKW8111H (logging/demand version) with Modbus RTU selected, manual ARCT1F440E-8.",
 "summary": "The KW8M is a panel-mount energy meter for single- and three-phase circuits with a pulse counter input and an RS485 port running MEWTOCOL or Modbus RTU. Holding registers carry energy, current, voltage, power, PF, frequency, load on/off hours and pulse counts; the AKW8111H adds demand values and logging. This map covers the common table and the H-only demand and status registers.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": 1,
  "baud": 19200,
  "parity": "Odd",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "hex 0-based",
  "note": "The table prints hex data items (0064H) that go into the request unchanged; the manual's example resets energy by writing 2 words at 0064H. The MEWTOCOL DT number in decimal equals the hex Modbus address."
 },
 "default_word_order": "CDAB",
 "firmware": null,
 "source": {
  "title": "KW8M Eco-POWER METER User's Manual",
  "doc_number": "ARCT1F440E-8",
  "revision_date": "2016-08",
  "url": "https://mediap.industry.panasonic.eu/assets/custom-upload/Factory%20%26%20Automation/Eco-POWER%20METERS/Manuals/mn_kw8m_user_pidsx_en.pdf",
  "pages": "Section 7.4.2 Data Register List, manual pp. 62-66 (PDF pp. 71-75)"
 },
 "notes": [
  "Word order: every 32-bit row is printed as two registers marked <LSB> (lower address) and <MSB> (higher address), so the low word comes first (CDAB).",
  "The 'integral active power for arbitrary period' row (0062H) prints its unit as 0.01kW; it is listed without a unit.",
  "Left out: the AKW8111H log-data block (4E20H onward and F6CCH onward) and calendar-timer settings, which are log records rather than live values.",
  "Registers not listed read 0."
 ],
 "integration": {
  "summary": "Switch the protocol to MODBUS(RTU) in Mode 3, then poll with function 03: 0064H energy (2 words, 0.01 kWh), 00B0H active power, 006BH-006DH currents, 00AAH-00AEH voltages, 006FH PF and 0070H frequency.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 100,
    "why": "Integral active energy"
   },
   {
    "table": "holding_register",
    "address": 176,
    "why": "Active power"
   },
   {
    "table": "holding_register",
    "address": 107,
    "why": "Current L1"
   },
   {
    "table": "holding_register",
    "address": 170,
    "why": "Voltage L1"
   },
   {
    "table": "holding_register",
    "address": 111,
    "why": "Power factor"
   },
   {
    "table": "holding_register",
    "address": 112,
    "why": "Frequency"
   }
  ],
  "enable": "Protocol defaults to MEWTOCOL; change it to MODBUS(RTU) in setting Mode 3 together with station number, speed, format and response time.",
  "watchdog": null,
  "quirks": [
   "Modbus RTU only works with the 8-bit formats; the default format 8bit-o is odd parity.",
   "Out-of-range writes are acknowledged but ignored."
  ],
  "setup": [
   "Defaults: station 1, 19200 bps, 8bit-o, response time 5 ms.",
   "Set phase/wire, CT type and voltage range in Mode 1 before reading values."
  ],
  "gotchas": [
   "AKW8111H: switch the backup battery ON and initialise the main-unit memory (Mode 4) after setting the calendar timer (Mode 5), or log data may be wrong.",
   "Settings written over Modbus are stored in EEPROM; avoid cyclic writes."
  ]
 },
 "registers": [
  {
   "table": "holding_register",
   "address": 1,
   "documented": "0001H",
   "name": "Contact output status",
   "description": "AKW8111H only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 48,
   "documented": "0030H",
   "name": "Hysteresis for demand alarm off",
   "description": "AKW8111H only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 49,
   "documented": "0031H",
   "name": "Demand monitor start time",
   "description": "AKW8111H only. 1-30.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 50,
   "documented": "0032H",
   "name": "Rate",
   "description": "Electricity rate per kWh used for the charge display.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 60,
   "documented": "003CH",
   "name": "CT type",
   "description": "Dedicated CT rating: 5, 50, 100, 250, 400 or 600.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "A",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 61,
   "documented": "003DH",
   "name": "Unit for pulse output",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "0.001 kWh",
    "10": "0.01 kWh",
    "100": "0.1 kWh",
    "1000": "1 kWh",
    "10000": "10 kWh",
    "100000": "100 kWh",
    "999": "Power alarm (alarm value 0040H)",
    "777": "Current alarm (ratio 0045H)",
    "555": "Preset count output (preset 009EH)",
    "333": "Stand-by alarm (004DH/004EH)",
    "222": "Demand alarm (00CDH)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 63,
   "documented": "003FH",
   "name": "CT primary current (5 A CT)",
   "description": "For a commercial 5 A secondary CT, 1-4000.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "A",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64,
   "documented": "0040H",
   "name": "Alarm value (instantaneous active power)",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.01,
   "units": "kW",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 66,
   "documented": "0042H",
   "name": "VT ratio",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 67,
   "documented": "0043H",
   "name": "Current threshold for time measurement",
   "description": "Load on/off-time threshold.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 68,
   "documented": "0044H",
   "name": "Cut-off current",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 69,
   "documented": "0045H",
   "name": "Current alarm value",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 70,
   "documented": "0046H",
   "name": "Voltage range",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "400 V",
    "2": "200 V"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 77,
   "documented": "004DH",
   "name": "Current ratio for stand-by alarm",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 78,
   "documented": "004EH",
   "name": "Time for stand-by alarm",
   "description": "1-9999; unit not printed in the table.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 80,
   "documented": "0050H",
   "name": "SRAM initialize",
   "description": "AKW8111H only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 98,
   "documented": "0062H",
   "name": "Active energy for arbitrary period",
   "description": "AKW8111H only. Table unit reads 0.01kW.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.01,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 100,
   "documented": "0064H",
   "name": "Integral active energy",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.01,
   "units": "kWh",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 102,
   "documented": "0066H",
   "name": "Integral reactive energy",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.01,
   "units": "kvarh",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 104,
   "documented": "0068H",
   "name": "Integral apparent energy",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.01,
   "units": "kVAh",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 107,
   "documented": "006BH",
   "name": "Current L1 (CT1)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 108,
   "documented": "006CH",
   "name": "Current L2 (CT2)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 109,
   "documented": "006DH",
   "name": "Current L3 (CT3)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 111,
   "documented": "006FH",
   "name": "Power factor",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 112,
   "documented": "0070H",
   "name": "Frequency",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 150,
   "documented": "0096H",
   "name": "Load ON-time",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.1,
   "units": "h",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 152,
   "documented": "0098H",
   "name": "Load OFF-time",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.1,
   "units": "h",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 154,
   "documented": "009AH",
   "name": "Pulse count value",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 158,
   "documented": "009EH",
   "name": "Preset value",
   "description": "Pulse count preset for the count output.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 160,
   "documented": "00A0H",
   "name": "Prescale value",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.001,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 162,
   "documented": "00A2H",
   "name": "Max. counting speed",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "Hz",
   "access": "RW",
   "values": {
    "30": "30 Hz",
    "2000": "2000 Hz"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 163,
   "documented": "00A3H",
   "name": "Auto-off time",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 170,
   "documented": "00AAH",
   "name": "Voltage L1 (P1-P0)",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 172,
   "documented": "00ACH",
   "name": "Voltage L2 (P2-P0)",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 174,
   "documented": "00AEH",
   "name": "Voltage L3 (P3-P0)",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 176,
   "documented": "00B0H",
   "name": "Instantaneous active power",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.01,
   "units": "kW",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 178,
   "documented": "00B2H",
   "name": "Instantaneous reactive power",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.01,
   "units": "kvar",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 180,
   "documented": "00B4H",
   "name": "Instantaneous apparent power",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.01,
   "units": "kVA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 200,
   "documented": "00C8H",
   "name": "Present demand",
   "description": "AKW8111H only.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.01,
   "units": "kW",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 203,
   "documented": "00CBH",
   "name": "Estimated demand",
   "description": "AKW8111H only.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.01,
   "units": "kW",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 205,
   "documented": "00CDH",
   "name": "Demand setting value",
   "description": "AKW8111H only.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.01,
   "units": "kW",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "page": "https://easymodbus.com/modbus-register-maps/panasonic/kw8m",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}