 "manufacturer": "ProMinent",
 "manufacturer_slug": "prominent",
 "model": "DULCOMETER AEGIS II controller (Modbus RTU slave)",
 "model_slug": "aegis-ii",
 "short_model": "AEGIS II",
 "aliases": [
  "AEGIS II",
  "Aegis II",
  "DULCOMETER AEGIS II",
  "AEGIS II COM module"
 ],
 "equipment_type": "Sensor / multi-input controller",
 "applies_to": "AEGIS II controllers fitted with the COM module (Modbus RTU slave on XB21/XB22), per manual BA DM 229 08/18.",
 "summary": "The AEGIS II is a ProMinent DULCOMETER controller. Its COM module, fitted in module slot 3, adds a read-only Modbus RTU slave port on RS-485. Every 32-bit value is published twice, once low word first and once high word first; this map uses the high-word-first copy (registers 901-1123) and covers the input readings A-Z, relay and pulse outputs, alarm levels, totalisers, on/off setpoints and the input, output and system state words.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": 10,
  "baud": 19200,
  "parity": "Even",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "1-based",
  "note": "Each row gives a decimal 'Register' and its PDU address; the PDU address is the register minus 1 (ProMinent register 100 is fetched at PDU 99). Here 'address' is the PDU address, e.g. input A in the high-word-first block is register 901, PDU 900."
 },
 "default_word_order": "ABCD",
 "firmware": null,
 "source": {
  "title": "Software manual DULCOMETER Controller AEGIS II Modbus RTU",
  "doc_number": "982395 BA DM 229 08/18 EN",
  "revision_date": "2018-08",
  "url": "https://www.prominent.com/resources/OperatingInstructions/English/19079/982395-BA-DM-229-08-18-EN-Modbus-RTU-Aegis-II-EN.pdf",
  "pages": "pp. 5-6 (bus settings and defaults), p. 10 (commands, word order, numbering), pp. 11-17 (register table), pp. 18-20 (state bits)"
 },
 "notes": [
  "The manual publishes each 32-bit value twice: registers 501-723 carry bits 15-0 in the first register (low word first, CDAB) and registers 901-1123 carry bits 31-16 first (ABCD). Only the ABCD copy is listed; the CDAB copy is the same layout 400 registers lower.",
  "16-bit state registers for inputs A-Z also appear in both blocks (679-704 and 1079-1104).",
  "All values are read-only; any write, or a read of an unlisted register, returns an exception. The manual asks for no more than one query per second.",
  "Readings are floats in the user units configured for each input; the manual gives no units.",
  "Left out: the P7 control-state row, whose printed PDU address (1110) clashes with R4 while its register is 1117; PDU 1116 is likely but not stated.",
  "Inputs K-N, W-Z and the 'phantom' values depend on the AEGIS II configuration and plug-in modules."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 900,
   "documented": "901",
   "name": "A - Serial sensor 1 value",
   "description": "Input A reading in its configured user unit.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 902,
   "documented": "903",
   "name": "B - Serial sensor 2 value",
   "description": "Input B reading in its configured user unit.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 904,
   "documented": "905",
   "name": "C - Module slot 1 value 1",
   "description": "Input C reading in its configured user unit.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 906,
   "documented": "907",
   "name": "D - Module slot 1 value 2",
   "description": "Input D reading in its configured user unit.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 908,
   "documented": "909",
   "name": "E - Module slot 2 value 1",
   "description": "Input E reading in its configured user unit.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 910,
   "documented": "911",
   "name": "F - Module slot 2 value 2",
   "description": "Input F reading in its configured user unit.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 912,
   "documented": "913",
   "name": "G - 4-20 mA input value",
   "description": "Input G reading in its configured user unit.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 914,
   "documented": "915",
   "name": "H - 10 mV/°C temperature input value",
   "description": "Input H reading in its configured user unit.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 916,
   "documented": "917",
   "name": "I - Module slot 3 value 1",
   "description": "Input I reading in its configured user unit.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 918,
   "documented": "919",
   "name": "J - Module slot 3 value 2",
   "description": "Input J reading in its configured user unit.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 920,
   "documented": "921",
   "name": "K - Phantom sensor K (slot 3 COM plug-in value 1)",
   "description": "Input K reading in its configured user unit.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 922,
   "documented": "923",
   "name": "L - Phantom sensor L (slot 3 COM plug-in value 2)",
   "description": "Input L reading in its configured user unit.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 924,
   "documented": "925",
   "name": "M - Phantom sensor M (Pyxis ST-500 probe)",
   "description": "Input M reading in its configured user unit.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 926,
   "documented": "927",
   "name": "N - Phantom sensor N",
   "description": "Input N reading in its configured user unit.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 928,
   "documented": "929",
   "name": "O - Volume meter (daily) / contact input",
   "description": "Today's volume in user units, or 1.0 closed / 0.0 open for a contact input.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 930,
   "documented": "931",
   "name": "P - Volume meter (daily) / contact input",
   "description": "Today's volume in user units, or 1.0 closed / 0.0 open for a contact input.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 932,
   "documented": "933",
   "name": "Q - Volume meter (daily) / contact input",
   "description": "Today's volume in user units, or 1.0 closed / 0.0 open for a contact input.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 934,
   "documented": "935",
   "name": "R - Volume meter (daily) / contact input",
   "description": "Today's volume in user units, or 1.0 closed / 0.0 open for a contact input.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 936,
   "documented": "937",
   "name": "S - Volume meter (daily) / contact input",
   "description": "Today's volume in user units, or 1.0 closed / 0.0 open for a contact input.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 938,
   "documented": "939",
   "name": "T - Volume meter (daily) / contact input",
   "description": "Today's volume in user units, or 1.0 closed / 0.0 open for a contact input.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 940,
   "documented": "941",
   "name": "U - Volume meter (daily) / contact input",
   "description": "Today's volume in user units, or 1.0 closed / 0.0 open for a contact input.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 942,
   "documented": "943",
   "name": "V - Volume meter (daily) / contact input",
   "description": "Today's volume in user units, or 1.0 closed / 0.0 open for a contact input.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 944,
   "documented": "945",
   "name": "W - Phantom volume meter / contact input",
   "description": "1.0 = on, 0.0 = off for contact use.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 946,
   "documented": "947",
   "name": "X - Phantom volume meter / contact input",
   "description": "1.0 = on, 0.0 = off for contact use.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 948,
   "documented": "949",
   "name": "Y - Phantom volume meter / contact input",
   "description": "1.0 = on, 0.0 = off for contact use.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 950,
   "documented": "951",
   "name": "Z - Phantom volume meter / contact input",
   "description": "1.0 = on, 0.0 = off for contact use.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 952,
   "documented": "953",
   "name": "R1 - Line powered control relay state",
   "description": "Relay output state as a float.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 954,
   "documented": "955",
   "name": "R2 - Line powered control relay state",
   "description": "Relay output state as a float.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 956,
   "documented": "957",
   "name": "R3 - Dry or line powered control relay state",
   "description": "Relay output state as a float.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 958,
   "documented": "959",
   "name": "R4 - Dry or line powered control relay state",
   "description": "Relay output state as a float.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 960,
   "documented": "961",
   "name": "R5 - Dry or line powered control relay state",
   "description": "Relay output state as a float.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 962,
   "documented": "963",
   "name": "P6 - Pulse / on-off control output",
   "description": "Pulse control: dosing rate 0-100 % (0 = off).",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 964,
   "documented": "965",
   "name": "P7 - Pulse / on-off control output",
   "description": "Pulse control: dosing rate 0-100 % (0 = off).",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 966,
   "documented": "967",
   "name": "P8 - Pulse / on-off control output",
   "description": "Pulse control: dosing rate 0-100 % (0 = off).",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 968,
   "documented": "969",
   "name": "P9 - Pulse / on-off control output",
   "description": "Pulse control: dosing rate 0-100 % (0 = off).",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 970,
   "documented": "971",
   "name": "A - High alarm level",
   "description": "Reads 0 when the alarm is disabled.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 972,
   "documented": "973",
   "name": "A - Low alarm level",
   "description": "Reads 0 when the alarm is disabled.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 974,
   "documented": "975",
   "name": "B - High alarm level",
   "description": "Reads 0 when the alarm is disabled.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 976,
   "documented": "977",
   "name": "B - Low alarm level",
   "description": "Reads 0 when the alarm is disabled.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 978,
   "documented": "979",
   "name": "C - High alarm level",
   "description": "Reads 0 when the alarm is disabled.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 980,
   "documented": "981",
   "name": "C - Low alarm level",
   "description": "Reads 0 when the alarm is disabled.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 982,
   "documented": "983",
   "name": "D - High alarm level",
   "description": "Reads 0 when the alarm is disabled.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 984,
   "documented": "985",
   "name": "D - Low alarm level",
   "description": "Reads 0 when the alarm is disabled.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 986,
   "documented": "987",
   "name": "E - High alarm level",
   "description": "Reads 0 when the alarm is disabled.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 988,
   "documented": "989",
   "name": "E - Low alarm level",
   "description": "Reads 0 when the alarm is disabled.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 990,
   "documented": "991",
   "name": "F - High alarm level",
   "description": "Reads 0 when the alarm is disabled.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 992,
   "documented": "993",
   "name": "F - Low alarm level",
   "description": "Reads 0 when the alarm is disabled.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 994,
   "documented": "995",
   "name": "G - High alarm level",
   "description": "Reads 0 when the alarm is disabled.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 996,
   "documented": "997",
   "name": "G - Low alarm level",
   "description": "Reads 0 when the alarm is disabled.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 998,
   "documented": "999",
   "name": "H - High alarm level",
   "description": "Reads 0 when the alarm is disabled.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1000,
   "documented": "1001",
   "name": "H - Low alarm level",
   "description": "Reads 0 when the alarm is disabled.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1002,
   "documented": "1003",
   "name": "I - High alarm level",
   "description": "Reads 0 when the alarm is disabled.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1004,
   "documented": "1005",
   "name": "I - Low alarm level",
   "description": "Reads 0 when the alarm is disabled.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1006,
   "documented": "1007",
   "name": "J - High alarm level",
   "description": "Reads 0 when the alarm is disabled.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1008,
   "documented": "1009",
   "name": "J - Low alarm level",
   "description": "Reads 0 when the alarm is disabled.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1010,
   "documented": "1011",
   "name": "K - High alarm level",
   "description": "Reads 0 when the alarm is disabled.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1012,
   "documented": "1013",
   "name": "K - Low alarm level",
   "description": "Reads 0 when the alarm is disabled.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1014,
   "documented": "1015",
   "name": "L - High alarm level",
   "description": "Reads 0 when the alarm is disabled.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1016,
   "documented": "1017",
   "name": "L - Low alarm level",
   "description": "Reads 0 when the alarm is disabled.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1018,
   "documented": "1019",
   "name": "M - High alarm level",
   "description": "Reads 0 when the alarm is disabled.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1020,
   "documented": "1021",
   "name": "M - Low alarm level",
   "description": "Reads 0 when the alarm is disabled.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1022,
   "documented": "1023",
   "name": "N - High alarm level",
   "description": "Reads 0 when the alarm is disabled.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1024,
   "documented": "1025",
   "name": "N - Low alarm level",
   "description": "Reads 0 when the alarm is disabled.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1026,
   "documented": "1027",
   "name": "O - Total counter",
   "description": "Total volume; 0 if the input is disabled or a contact input.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1028,
   "documented": "1029",
   "name": "P - Total counter",
   "description": "Total volume; 0 if the input is disabled or a contact input.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1030,
   "documented": "1031",
   "name": "Q - Total counter",
   "description": "Total volume; 0 if the input is disabled or a contact input.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1032,
   "documented": "1033",
   "name": "R - Total counter",
   "description": "Total volume; 0 if the input is disabled or a contact input.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1034,
   "documented": "1035",
   "name": "S - Total counter",
   "description": "Total volume; 0 if the input is disabled or a contact input.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1036,
   "documented": "1037",
   "name": "T - Total counter",
   "description": "Total volume; 0 if the input is disabled or a contact input.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1038,
   "documented": "1039",
   "name": "U - Total counter",
   "description": "Total volume; 0 if the input is disabled or a contact input.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1040,
   "documented": "1041",
   "name": "V - Total counter",
   "description": "Total volume; 0 if the input is disabled or a contact input.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1042,
   "documented": "1043",
   "name": "R1 - Turn on setpoint",
   "description": "Reads 0 when the output is locked.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1044,
   "documented": "1045",
   "name": "R1 - Turn off setpoint",
   "description": "Reads 0 when the output is locked.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1046,
   "documented": "1047",
   "name": "R2 - Turn on setpoint",
   "description": "Reads 0 when the output is locked.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1048,
   "documented": "1049",
   "name": "R2 - Turn off setpoint",
   "description": "Reads 0 when the output is locked.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1050,
   "documented": "1051",
   "name": "R3 - Turn on setpoint",
   "description": "Reads 0 when the output is locked.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1052,
   "documented": "1053",
   "name": "R3 - Turn off setpoint",
   "description": "Reads 0 when the output is locked.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1054,
   "documented": "1055",
   "name": "R4 - Turn on setpoint",
   "description": "Reads 0 when the output is locked.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1056,
   "documented": "1057",
   "name": "R4 - Turn off setpoint",
   "description": "Reads 0 when the output is locked.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1058,
   "documented": "1059",
   "name": "R5 - Turn on setpoint",
   "description": "Reads 0 when the output is locked.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1060,
   "documented": "1061",
   "name": "R5 - Turn off setpoint",
   "description": "Reads 0 when the output is locked.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1062,
   "documented": "1063",
   "name": "P6 - Turn on setpoint",
   "description": "Reads 0 when the output is locked.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1064,
   "documented": "1065",
   "name": "P6 - Turn off setpoint",
   "description": "Reads 0 when the output is locked.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1066,
   "documented": "1067",
   "name": "P7 - Turn on setpoint",
   "description": "Reads 0 when the output is locked.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1068,
   "documented": "1069",
   "name": "P7 - Turn off setpoint",
   "description": "Reads 0 when the output is locked.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1070,
   "documented": "1071",
   "name": "P8 - Turn on setpoint",
   "description": "Reads 0 when the output is locked.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1072,
   "documented": "1073",
   "name": "P8 - Turn off setpoint",
   "description": "Reads 0 when the output is locked.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1074,
   "documented": "1075",
   "name": "P9 - Turn on setpoint",
   "description": "Reads 0 when the output is locked.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1076,
   "documented": "1077",
   "name": "P9 - Turn off setpoint",
   "description": "Reads 0 when the output is locked.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1078,
   "documented": "1079",
   "name": "A - State",
   "description": "Reads 0 when the parameter is disabled.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Parameter enabled",
    "1": "Alarmed (alarm action executing)",
    "3": "Trips the alarm relay on alarm",
    "10": "Calibration sample capture active",
    "11": "Linked: web user calibrating"
   }
  },
  {
   "table": "holding_register",
   "address": 1079,
   "documented": "1080",
   "name": "B - State",
   "description": "Reads 0 when the parameter is disabled.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Parameter enabled",
    "1": "Alarmed (alarm action executing)",
    "3": "Trips the alarm relay on alarm",
    "10": "Calibration sample capture active",
    "11": "Linked: web user calibrating"
   }
  },
  {
   "table": "holding_register",
   "address": 1080,
   "documented": "1081",
   "name": "C - State",
   "description": "Reads 0 when the parameter is disabled.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Parameter enabled",
    "1": "Alarmed (alarm action executing)",
    "3": "Trips the alarm relay on alarm",
    "10": "Calibration sample capture active",
    "11": "Linked: web user calibrating"
   }
  },
  {
   "table": "holding_register",
   "address": 1081,
   "documented": "1082",
   "name": "D - State",
   "description": "Reads 0 when the parameter is disabled.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Parameter enabled",
    "1": "Alarmed (alarm action executing)",
    "3": "Trips the alarm relay on alarm",
    "10": "Calibration sample capture active",
    "11": "Linked: web user calibrating"
   }
  },
  {
   "table": "holding_register",
   "address": 1082,
   "documented": "1083",
   "name": "E - State",
   "description": "Reads 0 when the parameter is disabled.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Parameter enabled",
    "1": "Alarmed (alarm action executing)",
    "3": "Trips the alarm relay on alarm",
    "10": "Calibration sample capture active",
    "11": "Linked: web user calibrating"
   }
  },
  {
   "table": "holding_register",
   "address": 1083,
   "documented": "1084",
   "name": "F - State",
   "description": "Reads 0 when the parameter is disabled.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Parameter enabled",
    "1": "Alarmed (alarm action executing)",
    "3": "Trips the alarm relay on alarm",
    "10": "Calibration sample capture active",
    "11": "Linked: web user calibrating"
   }
  },
  {
   "table": "holding_register",
   "address": 1084,
   "documented": "1085",
   "name": "G - State",
   "description": "Reads 0 when the parameter is disabled.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Parameter enabled",
    "1": "Alarmed (alarm action executing)",
    "3": "Trips the alarm relay on alarm",
    "10": "Calibration sample capture active",
    "11": "Linked: web user calibrating"
   }
  },
  {
   "table": "holding_register",
   "address": 1085,
   "documented": "1086",
   "name": "H - State",
   "description": "Reads 0 when the parameter is disabled.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Parameter enabled",
    "1": "Alarmed (alarm action executing)",
    "3": "Trips the alarm relay on alarm",
    "10": "Calibration sample capture active",
    "11": "Linked: web user calibrating"
   }
  },
  {
   "table": "holding_register",
   "address": 1086,
   "documented": "1087",
   "name": "I - State",
   "description": "Reads 0 when the parameter is disabled.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Parameter enabled",
    "1": "Alarmed (alarm action executing)",
    "3": "Trips the alarm relay on alarm",
    "10": "Calibration sample capture active",
    "11": "Linked: web user calibrating"
   }
  },
  {
   "table": "holding_register",
   "address": 1087,
   "documented": "1088",
   "name": "J - State",
   "description": "Reads 0 when the parameter is disabled.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Parameter enabled",
    "1": "Alarmed (alarm action executing)",
    "3": "Trips the alarm relay on alarm",
    "10": "Calibration sample capture active",
    "11": "Linked: web user calibrating"
   }
  },
  {
   "table": "holding_register",
   "address": 1088,
   "documented": "1089",
   "name": "K - State",
   "description": "Reads 0 when the parameter is disabled.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Parameter enabled",
    "1": "Alarmed (alarm action executing)",
    "3": "Trips the alarm relay on alarm",
    "10": "Calibration sample capture active",
    "11": "Linked: web user calibrating"
   }
  },
  {
   "table": "holding_register",
   "address": 1089,
   "documented": "1090",
   "name": "L - State",
   "description": "Reads 0 when the parameter is disabled.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Parameter enabled",
    "1": "Alarmed (alarm action executing)",
    "3": "Trips the alarm relay on alarm",
    "10": "Calibration sample capture active",
    "11": "Linked: web user calibrating"
   }
  },
  {
   "table": "holding_register",
   "address": 1090,
   "documented": "1091",
   "name": "M - State",
   "description": "Reads 0 when the parameter is disabled.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Parameter enabled",
    "1": "Alarmed (alarm action executing)",
    "3": "Trips the alarm relay on alarm",
    "10": "Calibration sample capture active",
    "11": "Linked: web user calibrating"
   }
  },
  {
   "table": "holding_register",
   "address": 1091,
   "documented": "1092",
   "name": "N - State",
   "description": "Reads 0 when the parameter is disabled.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Parameter enabled",
    "1": "Alarmed (alarm action executing)",
    "3": "Trips the alarm relay on alarm",
    "10": "Calibration sample capture active",
    "11": "Linked: web user calibrating"
   }
  },
  {
   "table": "holding_register",
   "address": 1092,
   "documented": "1093",
   "name": "O - State",
   "description": "Reads 0 when the parameter is disabled.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Parameter enabled",
    "1": "Alarmed (alarm action executing)",
    "3": "Trips the alarm relay on alarm",
    "10": "Calibration sample capture active",
    "11": "Linked: web user calibrating"
   }
  },
  {
   "table": "holding_register",
   "address": 1093,
   "documented": "1094",
   "name": "P - State",
   "description": "Reads 0 when the parameter is disabled.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Parameter enabled",
    "1": "Alarmed (alarm action executing)",
    "3": "Trips the alarm relay on alarm",
    "10": "Calibration sample capture active",
    "11": "Linked: web user calibrating"
   }
  },
  {
   "table": "holding_register",
   "address": 1094,
   "documented": "1095",
   "name": "Q - State",
   "description": "Reads 0 when the parameter is disabled.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Parameter enabled",
    "1": "Alarmed (alarm action executing)",
    "3": "Trips the alarm relay on alarm",
    "10": "Calibration sample capture active",
    "11": "Linked: web user calibrating"
   }
  },
  {
   "table": "holding_register",
   "address": 1095,
   "documented": "1096",
   "name": "R - State",
   "description": "Reads 0 when the parameter is disabled.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Parameter enabled",
    "1": "Alarmed (alarm action executing)",
    "3": "Trips the alarm relay on alarm",
    "10": "Calibration sample capture active",
    "11": "Linked: web user calibrating"
   }
  },
  {
   "table": "holding_register",
   "address": 1096,
   "documented": "1097",
   "name": "S - State",
   "description": "Reads 0 when the parameter is disabled.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Parameter enabled",
    "1": "Alarmed (alarm action executing)",
    "3": "Trips the alarm relay on alarm",
    "10": "Calibration sample capture active",
    "11": "Linked: web user calibrating"
   }
  },
  {
   "table": "holding_register",
   "address": 1097,
   "documented": "1098",
   "name": "T - State",
   "description": "Reads 0 when the parameter is disabled.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Parameter enabled",
    "1": "Alarmed (alarm action executing)",
    "3": "Trips the alarm relay on alarm",
    "10": "Calibration sample capture active",
    "11": "Linked: web user calibrating"
   }
  },
  {
   "table": "holding_register",
   "address": 1098,
   "documented": "1099",
   "name": "U - State",
   "description": "Reads 0 when the parameter is disabled.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Parameter enabled",
    "1": "Alarmed (alarm action executing)",
    "3": "Trips the alarm relay on alarm",
    "10": "Calibration sample capture active",
    "11": "Linked: web user calibrating"
   }
  },
  {
   "table": "holding_register",
   "address": 1099,
   "documented": "1100",
   "name": "V - State",
   "description": "Reads 0 when the parameter is disabled.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Parameter enabled",
    "1": "Alarmed (alarm action executing)",
    "3": "Trips the alarm relay on alarm",
    "10": "Calibration sample capture active",
    "11": "Linked: web user calibrating"
   }
  },
  {
   "table": "holding_register",
   "address": 1100,
   "documented": "1101",
   "name": "W - State",
   "description": "Reads 0 when the parameter is disabled.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Parameter enabled",
    "1": "Alarmed (alarm action executing)",
    "3": "Trips the alarm relay on alarm",
    "10": "Calibration sample capture active",
    "11": "Linked: web user calibrating"
   }
  },
  {
   "table": "holding_register",
   "address": 1101,
   "documented": "1102",
   "name": "X - State",
   "description": "Reads 0 when the parameter is disabled.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Parameter enabled",
    "1": "Alarmed (alarm action executing)",
    "3": "Trips the alarm relay on alarm",
    "10": "Calibration sample capture active",
    "11": "Linked: web user calibrating"
   }
  },
  {
   "table": "holding_register",
   "address": 1102,
   "documented": "1103",
   "name": "Y - State",
   "description": "Reads 0 when the parameter is disabled.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Parameter enabled",
    "1": "Alarmed (alarm action executing)",
    "3": "Trips the alarm relay on alarm",
    "10": "Calibration sample capture active",
    "11": "Linked: web user calibrating"
   }
  },
  {
   "table": "holding_register",
   "address": 1103,
   "documented": "1104",
   "name": "Z - State",
   "description": "Reads 0 when the parameter is disabled.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Parameter enabled",
    "1": "Alarmed (alarm action executing)",
    "3": "Trips the alarm relay on alarm",
    "10": "Calibration sample capture active",
    "11": "Linked: web user calibrating"
   }
  },
  {
   "table": "holding_register",
   "address": 1104,
   "documented": "1105",
   "name": "R1 - Control state",
   "description": "32-bit control state word; 0 when output disabled.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Output on (relay on or pulsing)",
    "1": "Interlocked by contact input U-Z",
    "2": "Locked out on time",
    "3": "Varying cycle control",
    "4": "Frequency output used as digital output",
    "5": "Turn off on alarm",
    "6": "Interlocked by another relay",
    "8": "Special control active",
    "9": "Second phase of a sequential volume control",
    "10": "Forced on by prebleed",
    "11": "Time owed",
    "13": "Blocking another output",
    "14": "Oxidant event active (assist, pH lockout or alternate control)",
    "15": "Flow switch delay active",
    "16": "Driver card communication timeout",
    "17": "Prebleed active",
    "18": "Test (key held)",
    "19": "Prime active",
    "20": "On setpoint tripped, waiting for off setpoint",
    "21": "Oxidant event setpoints override control setpoints",
    "22": "Alarm: phantom contact set auto-removed",
    "23": "Latched (contact set control holds state in dead time)"
   }
  },
  {
   "table": "holding_register",
   "address": 1106,
   "documented": "1107",
   "name": "R2 - Control state",
   "description": "32-bit control state word; 0 when output disabled.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Output on (relay on or pulsing)",
    "1": "Interlocked by contact input U-Z",
    "2": "Locked out on time",
    "3": "Varying cycle control",
    "4": "Frequency output used as digital output",
    "5": "Turn off on alarm",
    "6": "Interlocked by another relay",
    "8": "Special control active",
    "9": "Second phase of a sequential volume control",
    "10": "Forced on by prebleed",
    "11": "Time owed",
    "13": "Blocking another output",
    "14": "Oxidant event active (assist, pH lockout or alternate control)",
    "15": "Flow switch delay active",
    "16": "Driver card communication timeout",
    "17": "Prebleed active",
    "18": "Test (key held)",
    "19": "Prime active",
    "20": "On setpoint tripped, waiting for off setpoint",
    "21": "Oxidant event setpoints override control setpoints",
    "22": "Alarm: phantom contact set auto-removed",
    "23": "Latched (contact set control holds state in dead time)"
   }
  },
  {
   "table": "holding_register",
   "address": 1108,
   "documented": "1109",
   "name": "R3 - Control state",
   "description": "32-bit control state word; 0 when output disabled.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Output on (relay on or pulsing)",
    "1": "Interlocked by contact input U-Z",
    "2": "Locked out on time",
    "3": "Varying cycle control",
    "4": "Frequency output used as digital output",
    "5": "Turn off on alarm",
    "6": "Interlocked by another relay",
    "8": "Special control active",
    "9": "Second phase of a sequential volume control",
    "10": "Forced on by prebleed",
    "11": "Time owed",
    "13": "Blocking another output",
    "14": "Oxidant event active (assist, pH lockout or alternate control)",
    "15": "Flow switch delay active",
    "16": "Driver card communication timeout",
    "17": "Prebleed active",
    "18": "Test (key held)",
    "19": "Prime active",
    "20": "On setpoint tripped, waiting for off setpoint",
    "21": "Oxidant event setpoints override control setpoints",
    "22": "Alarm: phantom contact set auto-removed",
    "23": "Latched (contact set control holds state in dead time)"
   }
  },
  {
   "table": "holding_register",
   "address": 1110,
   "documented": "1111",
   "name": "R4 - Control state",
   "description": "32-bit control state word; 0 when output disabled.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Output on (relay on or pulsing)",
    "1": "Interlocked by contact input U-Z",
    "2": "Locked out on time",
    "3": "Varying cycle control",
    "4": "Frequency output used as digital output",
    "5": "Turn off on alarm",
    "6": "Interlocked by another relay",
    "8": "Special control active",
    "9": "Second phase of a sequential volume control",
    "10": "Forced on by prebleed",
    "11": "Time owed",
    "13": "Blocking another output",
    "14": "Oxidant event active (assist, pH lockout or alternate control)",
    "15": "Flow switch delay active",
    "16": "Driver card communication timeout",
    "17": "Prebleed active",
    "18": "Test (key held)",
    "19": "Prime active",
    "20": "On setpoint tripped, waiting for off setpoint",
    "21": "Oxidant event setpoints override control setpoints",
    "22": "Alarm: phantom contact set auto-removed",
    "23": "Latched (contact set control holds state in dead time)"
   }
  },
  {
   "table": "holding_register",
   "address": 1112,
   "documented": "1113",
   "name": "R5 - Control state",
   "description": "32-bit control state word; 0 when output disabled.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Output on (relay on or pulsing)",
    "1": "Interlocked by contact input U-Z",
    "2": "Locked out on time",
    "3": "Varying cycle control",
    "4": "Frequency output used as digital output",
    "5": "Turn off on alarm",
    "6": "Interlocked by another relay",
    "8": "Special control active",
    "9": "Second phase of a sequential volume control",
    "10": "Forced on by prebleed",
    "11": "Time owed",
    "13": "Blocking another output",
    "14": "Oxidant event active (assist, pH lockout or alternate control)",
    "15": "Flow switch delay active",
    "16": "Driver card communication timeout",
    "17": "Prebleed active",
    "18": "Test (key held)",
    "19": "Prime active",
    "20": "On setpoint tripped, waiting for off setpoint",
    "21": "Oxidant event setpoints override control setpoints",
    "22": "Alarm: phantom contact set auto-removed",
    "23": "Latched (contact set control holds state in dead time)"
   }
  },
  {
   "table": "holding_register",
   "address": 1114,
   "documented": "1115",
   "name": "P6 - Control state",
   "description": "32-bit control state word; 0 when output disabled.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Output on (relay on or pulsing)",
    "1": "Interlocked by contact input U-Z",
    "2": "Locked out on time",
    "3": "Varying cycle control",
    "4": "Frequency output used as digital output",
    "5": "Turn off on alarm",
    "6": "Interlocked by another relay",
    "8": "Special control active",
    "9": "Second phase of a sequential volume control",
    "10": "Forced on by prebleed",
    "11": "Time owed",
    "13": "Blocking another output",
    "14": "Oxidant event active (assist, pH lockout or alternate control)",
    "15": "Flow switch delay active",
    "16": "Driver card communication timeout",
    "17": "Prebleed active",
    "18": "Test (key held)",
    "19": "Prime active",
    "20": "On setpoint tripped, waiting for off setpoint",
    "21": "Oxidant event setpoints override control setpoints",
    "22": "Alarm: phantom contact set auto-removed",
    "23": "Latched (contact set control holds state in dead time)"
   }
  },
  {
   "table": "holding_register",
   "address": 1118,
   "documented": "1119",
   "name": "P8 - Control state",
   "description": "32-bit control state word; 0 when output disabled.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Output on (relay on or pulsing)",
    "1": "Interlocked by contact input U-Z",
    "2": "Locked out on time",
    "3": "Varying cycle control",
    "4": "Frequency output used as digital output",
    "5": "Turn off on alarm",
    "6": "Interlocked by another relay",
    "8": "Special control active",
    "9": "Second phase of a sequential volume control",
    "10": "Forced on by prebleed",
    "11": "Time owed",
    "13": "Blocking another output",
    "14": "Oxidant event active (assist, pH lockout or alternate control)",
    "15": "Flow switch delay active",
    "16": "Driver card communication timeout",
    "17": "Prebleed active",
    "18": "Test (key held)",
    "19": "Prime active",
    "20": "On setpoint tripped, waiting for off setpoint",
    "21": "Oxidant event setpoints override control setpoints",
    "22": "Alarm: phantom contact set auto-removed",
    "23": "Latched (contact set control holds state in dead time)"
   }
  },
  {
   "table": "holding_register",
   "address": 1120,
   "documented": "1121",
   "name": "P9 - Control state",
   "description": "32-bit control state word; 0 when output disabled.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Output on (relay on or pulsing)",
    "1": "Interlocked by contact input U-Z",
    "2": "Locked out on time",
    "3": "Varying cycle control",
    "4": "Frequency output used as digital output",
    "5": "Turn off on alarm",
    "6": "Interlocked by another relay",
    "8": "Special control active",
    "9": "Second phase of a sequential volume control",
    "10": "Forced on by prebleed",
    "11": "Time owed",
    "13": "Blocking another output",
    "14": "Oxidant event active (assist, pH lockout or alternate control)",
    "15": "Flow switch delay active",
    "16": "Driver card communication timeout",
    "17": "Prebleed active",
    "18": "Test (key held)",
    "19": "Prime active",
    "20": "On setpoint tripped, waiting for off setpoint",
    "21": "Oxidant event setpoints override control setpoints",
    "22": "Alarm: phantom contact set auto-removed",
    "23": "Latched (contact set control holds state in dead time)"
   }
  },
  {
   "table": "holding_register",
   "address": 1122,
   "documented": "1123",
   "name": "System state",
   "description": "Common controller state word.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "1": "Restart after software reset (watchdog, Ethernet, user)",
    "2": "I/O reset to factory",
    "6": "Midnight passed (also while off)",
    "7": "New year passed (also while off)",
    "9": "Software restart",
    "10": "USB host port active (pumps off)",
    "14": "Locked out after failed passwords (resets 07:00)",
    "15": "Real-time clock error",
    "16": "No Wi-Fi module response at power-on",
    "17": "microSD file system up",
    "21": "Running (power-on timer expired)",
    "22": "Loading new I/O configuration (outputs off)",
    "23": "Manufacturing mode",
    "26": "All digital inputs set to contact sets (manufacturing)",
    "27": "File system fault / no microSD",
    "29": "No fan: inputs powered down, outputs off",
    "30": "Manufacturing override of SD/fan alarms"
   }
  }
 ],
 "integration": {
  "summary": "Poll holding registers (function 03) in the 901-1123 block, at most once per second. Inputs A-N are the sensor readings as high-word-first floats; the state words tell you whether each input and output is enabled, alarmed or interlocked.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 900,
    "why": "Input A (serial sensor 1)"
   },
   {
    "table": "holding_register",
    "address": 904,
    "why": "Input C (module slot 1 value 1)"
   },
   {
    "table": "holding_register",
    "address": 912,
    "why": "Input G (4-20 mA input)"
   },
   {
    "table": "holding_register",
    "address": 1078,
    "why": "Input A state"
   },
   {
    "table": "holding_register",
    "address": 1104,
    "why": "R1 control state"
   },
   {
    "table": "holding_register",
    "address": 1122,
    "why": "System state"
   }
  ],
  "enable": "Fit the COM module in module slot 3 and set the slave address, baud rate and parity at MENU > System > Communications. Connect the master to XB21/XB22 (the XB1 port is the module's own master port for a Pyxis ST-500 probe).",
  "watchdog": null,
  "quirks": [
   "Two copies of every value: 501-723 low word first, 901-1123 high word first. Pick one and stay with it.",
   "Register numbers are 1-based; subtract 1 for the PDU address.",
   "Read-only: function 03 only."
  ],
  "setup": [
   "Defaults: slave address 10, 19200 baud, 8 data bits, even parity, 1 stop bit.",
   "Termination for the slave port is set with jumper XT2 on the COM module.",
   "With no parity, 2 stop bits are required."
  ],
  "gotchas": [
   "Poll no faster than once per second.",
   "Disabled inputs, alarms and outputs read 0 rather than an error."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/prominent/aegis-ii",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}