 "model": "DULCOMETER diaLog DACb multi-parameter controller (Modbus RTU)",
 "model_slug": "dialog-dacb",
 "short_model": "diaLog DACb",
 "aliases": [
  "DACb",
  "diaLog DACb",
  "DULCOMETER DACb"
 ],
 "applies_to": "diaLog DACb controllers with the Modbus RTU interface option, per software manual BA DM 232 01/19.",
 "summary": "The diaLog DACb is ProMinent's multi-parameter measuring and control controller with up to three measuring and control channels plus a calculated (mathematic) channel. With the Modbus RTU option it is an RS-485 or RS-232 slave. This map covers the measured values, setpoints, status, warning and error words per channel, output states, device information, stop/pause commands, the per-channel control configuration (setpoints, limits, PID terms) and calibration values.",
 "source": {
  "title": "Software manual DULCOMETER Multi-parameter controller diaLog DACb Modbus RTU",
  "doc_number": "982017 BA DM 232 01/19 EN",
  "revision_date": "2019-01",
  "url": "https://www.prominent.com/resources/OperatingInstructions/English/19397/982017-BA-DM-232-01-19-EN-Modbus-RTU-DACb-EN.pdf",
  "pages": "pp. 4-8 (settings, commands, word order, numbering), pp. 8-12 (register table), pp. 13-17 (bit fields)"
 },
 "manufacturer": "ProMinent",
 "manufacturer_slug": "prominent",
 "equipment_type": "Sensor / multi-parameter controller",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": 1,
  "baud": 19200,
  "parity": "Odd",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "1-based",
  "note": "The manual prints a decimal 'Register' number plus the hex PDU address; the PDU address is the register minus 1 (register 100 is requested at PDU address 99, hex 63). The 'address' field here is the PDU address."
 },
 "default_word_order": "ABCD",
 "firmware": null,
 "notes": [
  "32-bit values (FLOAT32 and UINT32) put bits 31-16 in the first register and bits 15-0 in the second, so the word order is ABCD; bytes are sent high byte first. Register 198 (PDU 197) always reads 0xAABBCCDD as a check.",
  "Measured value, setpoint, limits and Xp are floats in whatever unit the channel is configured for (pH, mV, ppm and so on); the manual does not list units for them.",
  "Left out: Pump relay 4 (register 139), because its printed PDU address (hex 90) does not match register 139 (which would be hex 8A); the identity-code registers 150-161, because their text encoding is not described; the math-channel error registers 130/131, which the manual marks as reserved for later use; and channel 1 'Additive basic load' (215), printed as UINT16 although its range is -100 to +100 % (channels 2 and 3 are INT16).",
  "Channel 1 temperature is printed as INT16 and the other channels' temperature as UINT16; both are in 0.1 °C steps and are listed exactly as printed.",
  "Configuration word bits 3-6 (channels 1 and 2 only, valid only when bit 15 = 1) hold the control type: 0 off, 1 manual, 2 P one-way increase, 3 P one-way decrease, 4 P two-way standard, 5 P two-way dead zone, 6 PID one-way increase, 7 PID one-way decrease, 8 PID two-way standard, 9 PID two-way dead zone.",
  "Left out: registers 291 and 293, which the manual labels 'Slope Channel 1' and 'Zero point Channel 1' a second time (probably channel 3).",
  "The text of section 1.7 calls the byte-order test register 'Register 199', but the register table prints it as register 198 (PDU hex C5); the table value is used here."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 99,
   "documented": "100",
   "name": "Ch1 measured value",
   "description": "Actual measured value in the channel's configured unit.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 101,
   "documented": "102",
   "name": "Ch1 controller actuating value",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 102,
   "documented": "103",
   "name": "Ch1 temperature",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 103,
   "documented": "104",
   "name": "Ch1 actual setpoint",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 105,
   "documented": "106",
   "name": "Ch1 external disturbance value",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 106,
   "documented": "107",
   "name": "Ch1 status",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Channel active (0 = inactive or not connectable)",
    "1": "Local stop active",
    "8": "Local control set 2 active (0 = set 1)",
    "9": "SD card present",
    "10": "SD card less than 20 % free",
    "11": "SD card full",
    "12": "Warning present",
    "13": "Error present",
    "15": "Channel uses bus control parameters (0 = internal)"
   }
  },
  {
   "table": "holding_register",
   "address": 107,
   "documented": "108",
   "name": "Ch1 warnings",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Warning 1: below limit",
    "1": "Warning 2: limit exceeded",
    "2": "Warning 3: wash timer expired, maintenance due",
    "3": "Warning 4: channel not calibrated",
    "4": "Warning 71: replace battery",
    "5": "Warning 72: check the clock",
    "6": "Warning 73: fan fault"
   }
  },
  {
   "table": "holding_register",
   "address": 108,
   "documented": "109",
   "name": "Ch1 existing errors",
   "description": "32-bit error word, high word first.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Error 1: mV input too low",
    "1": "Error 2: mV input too high",
    "2": "Error 3: temperature too low",
    "3": "Error 4: temperature too high",
    "4": "Error 5: calibration error",
    "5": "Error 6: no sensor",
    "6": "Error 7: check sensor for glass breakage",
    "7": "Error 8: check time exceeded",
    "8": "Error 9: mA input above 20 mA",
    "9": "Error 10: mA input below 4 mA",
    "10": "Error 11: limit error still present after delay",
    "11": "Error 12: sample water fault (e.g. no flow)",
    "12": "Error 13: controller in PAUSE",
    "13": "Error 14: controller in PAUSE/HOLD",
    "14": "Error 15: mA input supply overloaded",
    "15": "Error 16: mA input overloaded",
    "16": "Error 17: tank 1 level low",
    "17": "Error 18: tank 2 level low",
    "18": "Error 19: tank 3 level low",
    "19": "Error 34: wrong correction variable",
    "20": "Error 88: expansion module connection fault",
    "31": "Error 99: system error"
   }
  },
  {
   "table": "holding_register",
   "address": 110,
   "documented": "111",
   "name": "Ch1 unconfirmed errors",
   "description": "Errors not yet acknowledged; same bit layout.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Error 1: mV input too low",
    "1": "Error 2: mV input too high",
    "2": "Error 3: temperature too low",
    "3": "Error 4: temperature too high",
    "4": "Error 5: calibration error",
    "5": "Error 6: no sensor",
    "6": "Error 7: check sensor for glass breakage",
    "7": "Error 8: check time exceeded",
    "8": "Error 9: mA input above 20 mA",
    "9": "Error 10: mA input below 4 mA",
    "10": "Error 11: limit error still present after delay",
    "11": "Error 12: sample water fault (e.g. no flow)",
    "12": "Error 13: controller in PAUSE",
    "13": "Error 14: controller in PAUSE/HOLD",
    "14": "Error 15: mA input supply overloaded",
    "15": "Error 16: mA input overloaded",
    "16": "Error 17: tank 1 level low",
    "17": "Error 18: tank 2 level low",
    "18": "Error 19: tank 3 level low",
    "19": "Error 34: wrong correction variable",
    "20": "Error 88: expansion module connection fault",
    "31": "Error 99: system error"
   }
  },
  {
   "table": "holding_register",
   "address": 112,
   "documented": "113",
   "name": "Ch2 measured value",
   "description": "Actual measured value in the channel's configured unit.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 114,
   "documented": "115",
   "name": "Ch2 controller actuating value",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 115,
   "documented": "116",
   "name": "Ch2 temperature",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 116,
   "documented": "117",
   "name": "Ch2 actual setpoint",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 118,
   "documented": "119",
   "name": "Ch2 external disturbance value",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 119,
   "documented": "120",
   "name": "Ch2 status",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Channel active (0 = inactive or not connectable)",
    "1": "Local stop active",
    "8": "Local control set 2 active (0 = set 1)",
    "9": "SD card present",
    "10": "SD card less than 20 % free",
    "11": "SD card full",
    "12": "Warning present",
    "13": "Error present",
    "15": "Channel uses bus control parameters (0 = internal)"
   }
  },
  {
   "table": "holding_register",
   "address": 120,
   "documented": "121",
   "name": "Ch2 warnings",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Warning 1: below limit",
    "1": "Warning 2: limit exceeded",
    "2": "Warning 3: wash timer expired, maintenance due",
    "3": "Warning 4: channel not calibrated",
    "4": "Warning 71: replace battery",
    "5": "Warning 72: check the clock",
    "6": "Warning 73: fan fault"
   }
  },
  {
   "table": "holding_register",
   "address": 121,
   "documented": "122",
   "name": "Ch2 existing errors",
   "description": "32-bit error word, high word first.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Error 1: mV input too low",
    "1": "Error 2: mV input too high",
    "2": "Error 3: temperature too low",
    "3": "Error 4: temperature too high",
    "4": "Error 5: calibration error",
    "5": "Error 6: no sensor",
    "6": "Error 7: check sensor for glass breakage",
    "7": "Error 8: check time exceeded",
    "8": "Error 9: mA input above 20 mA",
    "9": "Error 10: mA input below 4 mA",
    "10": "Error 11: limit error still present after delay",
    "11": "Error 12: sample water fault (e.g. no flow)",
    "12": "Error 13: controller in PAUSE",
    "13": "Error 14: controller in PAUSE/HOLD",
    "14": "Error 15: mA input supply overloaded",
    "15": "Error 16: mA input overloaded",
    "16": "Error 17: tank 1 level low",
    "17": "Error 18: tank 2 level low",
    "18": "Error 19: tank 3 level low",
    "19": "Error 34: wrong correction variable",
    "20": "Error 88: expansion module connection fault",
    "31": "Error 99: system error"
   }
  },
  {
   "table": "holding_register",
   "address": 123,
   "documented": "124",
   "name": "Ch2 unconfirmed errors",
   "description": "Errors not yet acknowledged; same bit layout.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Error 1: mV input too low",
    "1": "Error 2: mV input too high",
    "2": "Error 3: temperature too low",
    "3": "Error 4: temperature too high",
    "4": "Error 5: calibration error",
    "5": "Error 6: no sensor",
    "6": "Error 7: check sensor for glass breakage",
    "7": "Error 8: check time exceeded",
    "8": "Error 9: mA input above 20 mA",
    "9": "Error 10: mA input below 4 mA",
    "10": "Error 11: limit error still present after delay",
    "11": "Error 12: sample water fault (e.g. no flow)",
    "12": "Error 13: controller in PAUSE",
    "13": "Error 14: controller in PAUSE/HOLD",
    "14": "Error 15: mA input supply overloaded",
    "15": "Error 16: mA input overloaded",
    "16": "Error 17: tank 1 level low",
    "17": "Error 18: tank 2 level low",
    "18": "Error 19: tank 3 level low",
    "19": "Error 34: wrong correction variable",
    "20": "Error 88: expansion module connection fault",
    "31": "Error 99: system error"
   }
  },
  {
   "table": "holding_register",
   "address": 125,
   "documented": "126",
   "name": "Math channel measured value",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 127,
   "documented": "128",
   "name": "Math channel status",
   "description": "Status word of the mathematic channel (no bit list given).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 128,
   "documented": "129",
   "name": "Math channel warnings",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Warning 1: below limit",
    "1": "Warning 2: limit exceeded",
    "2": "Warning 3: wash timer expired, maintenance due",
    "3": "Warning 4: channel not calibrated",
    "4": "Warning 71: replace battery",
    "5": "Warning 72: check the clock",
    "6": "Warning 73: fan fault"
   }
  },
  {
   "table": "holding_register",
   "address": 131,
   "documented": "132",
   "name": "Current output 1",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "mA",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 132,
   "documented": "133",
   "name": "Current output 2",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "mA",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 133,
   "documented": "134",
   "name": "Current output 3",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "mA",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 134,
   "documented": "135",
   "name": "Dry contact relays",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Relay 1 (XR1) active",
    "1": "Relay 2 (XR2) active",
    "2": "Alarm relay (XR3) active"
   }
  },
  {
   "table": "holding_register",
   "address": 135,
   "documented": "136",
   "name": "Pump relay 1 (MOSFET)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "pulses/min",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 136,
   "documented": "137",
   "name": "Pump relay 2 (MOSFET)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "pulses/min",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 137,
   "documented": "138",
   "name": "Pump relay 3 (MOSFET)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "pulses/min",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 139,
   "documented": "140",
   "name": "Firmware",
   "description": "Firmware version, raw 32-bit value.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 141,
   "documented": "142",
   "name": "Firmware channel 2",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 143,
   "documented": "144",
   "name": "Firmware Modbus interface",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 145,
   "documented": "146",
   "name": "Serial number",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 147,
   "documented": "148",
   "name": "Revision",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 148,
   "documented": "149",
   "name": "Revision channel 2",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 197,
   "documented": "198",
   "name": "Endian test value",
   "description": "Always reads 0xAABBCCDD; use it to check word order.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 199,
   "documented": "200",
   "name": "Ch1 stop",
   "description": "Write 0xFFFF to stop the channel's control.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "65535": "Stop"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 200,
   "documented": "201",
   "name": "Ch1 pause",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Pause",
    "2": "Pause/HOLD"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 201,
   "documented": "202",
   "name": "Ch2 stop",
   "description": "Write 0xFFFF to stop the channel's control.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "65535": "Stop"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 202,
   "documented": "203",
   "name": "Ch2 pause",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Pause",
    "2": "Pause/HOLD"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 203,
   "documented": "204",
   "name": "Ch1 configuration",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Limit 1 configured high (0 = low)",
    "1": "Limit 2 configured high (0 = low)",
    "3": "Bits 3-6: control type code (only when bit 15 = 1, see notes)",
    "7": "Limit 1 configuration on",
    "8": "Limit 2 configuration on",
    "14": "Use internal parameter set 2 (0 = set 1; only when bit 15 = 0)",
    "15": "Use remote (bus) control parameters (0 = internal)"
   }
  },
  {
   "table": "holding_register",
   "address": 204,
   "documented": "205",
   "name": "Ch1 remote setpoint",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 206,
   "documented": "207",
   "name": "Ch1 limit 1",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 208,
   "documented": "209",
   "name": "Ch1 limit 2",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 210,
   "documented": "211",
   "name": "Ch1 Xp",
   "description": "Proportional band.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 212,
   "documented": "213",
   "name": "Ch1 Ti",
   "description": "Integral time, 0-9999 s.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 213,
   "documented": "214",
   "name": "Ch1 Td",
   "description": "Derivative time, 0-999 s.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 215,
   "documented": "216",
   "name": "Ch1 control output limitation",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "1": "On"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 216,
   "documented": "217",
   "name": "Ch1 delay after stop",
   "description": "0-9999 s.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 217,
   "documented": "218",
   "name": "Ch1 delay after reboot",
   "description": "0-9999 s.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 218,
   "documented": "219",
   "name": "Ch1 remote setpoint 2",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 220,
   "documented": "221",
   "name": "Ch2 configuration",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Limit 1 configured high (0 = low)",
    "1": "Limit 2 configured high (0 = low)",
    "3": "Bits 3-6: control type code (only when bit 15 = 1, see notes)",
    "7": "Limit 1 configuration on",
    "8": "Limit 2 configuration on",
    "14": "Use internal parameter set 2 (0 = set 1; only when bit 15 = 0)",
    "15": "Use remote (bus) control parameters (0 = internal)"
   }
  },
  {
   "table": "holding_register",
   "address": 221,
   "documented": "222",
   "name": "Ch2 remote setpoint",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 223,
   "documented": "224",
   "name": "Ch2 limit 1",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 225,
   "documented": "226",
   "name": "Ch2 limit 2",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 227,
   "documented": "228",
   "name": "Ch2 Xp",
   "description": "Proportional band.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 229,
   "documented": "230",
   "name": "Ch2 Ti",
   "description": "Integral time, 0-9999 s.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 230,
   "documented": "231",
   "name": "Ch2 Td",
   "description": "Derivative time, 0-999 s.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 231,
   "documented": "232",
   "name": "Ch2 additive basic load",
   "description": "-100 to +100 %.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 232,
   "documented": "233",
   "name": "Ch2 control output limitation",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "1": "On"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 233,
   "documented": "234",
   "name": "Ch2 delay after stop",
   "description": "0-9999 s.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 234,
   "documented": "235",
   "name": "Ch2 delay after reboot",
   "description": "0-9999 s.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 235,
   "documented": "236",
   "name": "Ch2 remote setpoint 2",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 237,
   "documented": "238",
   "name": "Math channel configuration",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Limit 1 configured high (0 = low)",
    "1": "Limit 2 configured high (0 = low)",
    "7": "Limit 1 configuration on",
    "8": "Limit 2 configuration on"
   }
  },
  {
   "table": "holding_register",
   "address": 238,
   "documented": "239",
   "name": "Math channel limit 1",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 240,
   "documented": "241",
   "name": "Math channel limit 2",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 242,
   "documented": "243",
   "name": "Error confirmation channel 1",
   "description": "Error acknowledgement word for channel 1, same bit layout as the error word.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Error 1: mV input too low",
    "1": "Error 2: mV input too high",
    "2": "Error 3: temperature too low",
    "3": "Error 4: temperature too high",
    "4": "Error 5: calibration error",
    "5": "Error 6: no sensor",
    "6": "Error 7: check sensor for glass breakage",
    "7": "Error 8: check time exceeded",
    "8": "Error 9: mA input above 20 mA",
    "9": "Error 10: mA input below 4 mA",
    "10": "Error 11: limit error still present after delay",
    "11": "Error 12: sample water fault (e.g. no flow)",
    "12": "Error 13: controller in PAUSE",
    "13": "Error 14: controller in PAUSE/HOLD",
    "14": "Error 15: mA input supply overloaded",
    "15": "Error 16: mA input overloaded",
    "16": "Error 17: tank 1 level low",
    "17": "Error 18: tank 2 level low",
    "18": "Error 19: tank 3 level low",
    "19": "Error 34: wrong correction variable",
    "20": "Error 88: expansion module connection fault",
    "31": "Error 99: system error"
   }
  },
  {
   "table": "holding_register",
   "address": 244,
   "documented": "245",
   "name": "Error confirmation channel 2",
   "description": "Error acknowledgement word for channel 2.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Error 1: mV input too low",
    "1": "Error 2: mV input too high",
    "2": "Error 3: temperature too low",
    "3": "Error 4: temperature too high",
    "4": "Error 5: calibration error",
    "5": "Error 6: no sensor",
    "6": "Error 7: check sensor for glass breakage",
    "7": "Error 8: check time exceeded",
    "8": "Error 9: mA input above 20 mA",
    "9": "Error 10: mA input below 4 mA",
    "10": "Error 11: limit error still present after delay",
    "11": "Error 12: sample water fault (e.g. no flow)",
    "12": "Error 13: controller in PAUSE",
    "13": "Error 14: controller in PAUSE/HOLD",
    "14": "Error 15: mA input supply overloaded",
    "15": "Error 16: mA input overloaded",
    "16": "Error 17: tank 1 level low",
    "17": "Error 18: tank 2 level low",
    "18": "Error 19: tank 3 level low",
    "19": "Error 34: wrong correction variable",
    "20": "Error 88: expansion module connection fault",
    "31": "Error 99: system error"
   }
  },
  {
   "table": "holding_register",
   "address": 246,
   "documented": "247",
   "name": "Error confirmation channel 3",
   "description": "Error acknowledgement word for channel 3.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Error 1: mV input too low",
    "1": "Error 2: mV input too high",
    "2": "Error 3: temperature too low",
    "3": "Error 4: temperature too high",
    "4": "Error 5: calibration error",
    "5": "Error 6: no sensor",
    "6": "Error 7: check sensor for glass breakage",
    "7": "Error 8: check time exceeded",
    "8": "Error 9: mA input above 20 mA",
    "9": "Error 10: mA input below 4 mA",
    "10": "Error 11: limit error still present after delay",
    "11": "Error 12: sample water fault (e.g. no flow)",
    "12": "Error 13: controller in PAUSE",
    "13": "Error 14: controller in PAUSE/HOLD",
    "14": "Error 15: mA input supply overloaded",
    "15": "Error 16: mA input overloaded",
    "16": "Error 17: tank 1 level low",
    "17": "Error 18: tank 2 level low",
    "18": "Error 19: tank 3 level low",
    "19": "Error 34: wrong correction variable",
    "20": "Error 88: expansion module connection fault",
    "31": "Error 99: system error"
   }
  },
  {
   "table": "holding_register",
   "address": 248,
   "documented": "249",
   "name": "Ch3 measured value",
   "description": "Actual measured value in the channel's configured unit.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 250,
   "documented": "251",
   "name": "Ch3 controller actuating value",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 251,
   "documented": "252",
   "name": "Ch3 temperature",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 252,
   "documented": "253",
   "name": "Ch3 actual setpoint",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 254,
   "documented": "255",
   "name": "Ch3 external disturbance value",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 255,
   "documented": "256",
   "name": "Ch3 status",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Channel active (0 = inactive or not connectable)",
    "1": "Local stop active",
    "8": "Local control set 2 active (0 = set 1)",
    "9": "SD card present",
    "10": "SD card less than 20 % free",
    "11": "SD card full",
    "12": "Warning present",
    "13": "Error present",
    "15": "Channel uses bus control parameters (0 = internal)"
   }
  },
  {
   "table": "holding_register",
   "address": 256,
   "documented": "257",
   "name": "Ch3 warnings",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Warning 1: below limit",
    "1": "Warning 2: limit exceeded",
    "2": "Warning 3: wash timer expired, maintenance due",
    "3": "Warning 4: channel not calibrated",
    "4": "Warning 71: replace battery",
    "5": "Warning 72: check the clock",
    "6": "Warning 73: fan fault"
   }
  },
  {
   "table": "holding_register",
   "address": 257,
   "documented": "258",
   "name": "Ch3 existing errors",
   "description": "32-bit error word, high word first.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Error 1: mV input too low",
    "1": "Error 2: mV input too high",
    "2": "Error 3: temperature too low",
    "3": "Error 4: temperature too high",
    "4": "Error 5: calibration error",
    "5": "Error 6: no sensor",
    "6": "Error 7: check sensor for glass breakage",
    "7": "Error 8: check time exceeded",
    "8": "Error 9: mA input above 20 mA",
    "9": "Error 10: mA input below 4 mA",
    "10": "Error 11: limit error still present after delay",
    "11": "Error 12: sample water fault (e.g. no flow)",
    "12": "Error 13: controller in PAUSE",
    "13": "Error 14: controller in PAUSE/HOLD",
    "14": "Error 15: mA input supply overloaded",
    "15": "Error 16: mA input overloaded",
    "16": "Error 17: tank 1 level low",
    "17": "Error 18: tank 2 level low",
    "18": "Error 19: tank 3 level low",
    "19": "Error 34: wrong correction variable",
    "20": "Error 88: expansion module connection fault",
    "31": "Error 99: system error"
   }
  },
  {
   "table": "holding_register",
   "address": 259,
   "documented": "260",
   "name": "Ch3 unconfirmed errors",
   "description": "Errors not yet acknowledged; same bit layout.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Error 1: mV input too low",
    "1": "Error 2: mV input too high",
    "2": "Error 3: temperature too low",
    "3": "Error 4: temperature too high",
    "4": "Error 5: calibration error",
    "5": "Error 6: no sensor",
    "6": "Error 7: check sensor for glass breakage",
    "7": "Error 8: check time exceeded",
    "8": "Error 9: mA input above 20 mA",
    "9": "Error 10: mA input below 4 mA",
    "10": "Error 11: limit error still present after delay",
    "11": "Error 12: sample water fault (e.g. no flow)",
    "12": "Error 13: controller in PAUSE",
    "13": "Error 14: controller in PAUSE/HOLD",
    "14": "Error 15: mA input supply overloaded",
    "15": "Error 16: mA input overloaded",
    "16": "Error 17: tank 1 level low",
    "17": "Error 18: tank 2 level low",
    "18": "Error 19: tank 3 level low",
    "19": "Error 34: wrong correction variable",
    "20": "Error 88: expansion module connection fault",
    "31": "Error 99: system error"
   }
  },
  {
   "table": "holding_register",
   "address": 261,
   "documented": "262",
   "name": "Ch3 stop",
   "description": "Write 0xFFFF to stop the channel's control.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "65535": "Stop"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 262,
   "documented": "263",
   "name": "Ch3 pause",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Pause",
    "2": "Pause/HOLD"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 263,
   "documented": "264",
   "name": "Ch3 configuration",
   "description": "Bits 3-6, 14 and 15 exist only on channels 1 and 2.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Limit 1 configured high (0 = low)",
    "1": "Limit 2 configured high (0 = low)",
    "7": "Limit 1 configuration on",
    "8": "Limit 2 configuration on"
   }
  },
  {
   "table": "holding_register",
   "address": 264,
   "documented": "265",
   "name": "Ch3 remote setpoint",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 266,
   "documented": "267",
   "name": "Ch3 limit 1",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 268,
   "documented": "269",
   "name": "Ch3 limit 2",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 270,
   "documented": "271",
   "name": "Ch3 Xp",
   "description": "Proportional band.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 272,
   "documented": "273",
   "name": "Ch3 Ti",
   "description": "Integral time, 0-9999 s.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 273,
   "documented": "274",
   "name": "Ch3 Td",
   "description": "Derivative time, 0-999 s.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 274,
   "documented": "275",
   "name": "Ch3 additive basic load",
   "description": "-100 to +100 %.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 275,
   "documented": "276",
   "name": "Ch3 control output limitation",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "1": "On"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 276,
   "documented": "277",
   "name": "Ch3 delay after stop",
   "description": "0-9999 s.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 277,
   "documented": "278",
   "name": "Ch3 delay after reboot",
   "description": "0-9999 s.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 278,
   "documented": "279",
   "name": "Ch3 remote setpoint 2",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 282,
   "documented": "283",
   "name": "Slope channel 1",
   "description": "Calibration slope.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 284,
   "documented": "285",
   "name": "Zero point channel 1",
   "description": "Calibration zero point.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 286,
   "documented": "287",
   "name": "Slope channel 2",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 288,
   "documented": "289",
   "name": "Zero point channel 2",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  }
 ],
 "integration": {
  "summary": "Read holding registers (function 03) from PDU 99: each channel block gives the measured value and setpoint as floats followed by status, warnings and the 32-bit error words. Check the endian test value at PDU 197 first. Writes use function 06 for single registers and 16 for floats.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 99,
    "why": "Channel 1 measured value"
   },
   {
    "table": "holding_register",
    "address": 103,
    "why": "Channel 1 setpoint"
   },
   {
    "table": "holding_register",
    "address": 106,
    "why": "Channel 1 status"
   },
   {
    "table": "holding_register",
    "address": 108,
    "why": "Channel 1 existing errors"
   },
   {
    "table": "holding_register",
    "address": 112,
    "why": "Channel 2 measured value"
   },
   {
    "table": "holding_register",
    "address": 197,
    "why": "Endian test (0xAABBCCDD)"
   },
   {
    "table": "holding_register",
    "address": 199,
    "why": "Channel 1 stop command"
   }
  ],
  "enable": "Set the slave address, baud rate, serial format, interface mode and termination in SETUP > BUS configuration (access code needed). Bus control parameters are used when bit 15 of the channel configuration word is set.",
  "watchdog": null,
  "quirks": [
   "Register numbers are 1-based; subtract 1 for the PDU address.",
   "32-bit values are high word first (ABCD).",
   "Byte-sized parameters use only the low 8 bits of the register; write the top 8 bits as 0.",
   "If one register in a multi-register write raises an exception, the rest of that write is ignored."
  ],
  "setup": [
   "Factory settings: RS-485, slave address 1, 19200 baud, 8 data bits, odd parity, 1 stop bit; termination off.",
   "Turn on active termination in the menu when the controller is the last device on the RS-485 line.",
   "With no parity, 2 stop bits are required."
  ],
  "gotchas": [
   "Keep responses short at low baud rates: the manual warns that replies over about 100 bytes at 9600 baud (200 at 19200) may be corrupted.",
   "Read-only registers answer only to function 03."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/prominent/dialog-dacb",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}