 "manufacturer": "PVI Industries",
 "manufacturer_slug": "pvi-industries",
 "model": "TempTrac water heater electronic controller (Modbus RTU)",
 "model_slug": "temptrac",
 "short_model": "TempTrac",
 "aliases": [
  "TempTrac",
  "PV500-42"
 ],
 "equipment_type": "Boiler (water heater controller)",
 "applies_to": "PVI TempTrac thermostatic controllers (firmware 0.3 and 0.5) on RS-485 Modbus RTU, per PVI manual PV500-42 (06/2014).",
 "summary": "TempTrac is PVI's electronic operating control for its water heaters. It is a Modbus RTU slave on 2-wire RS-485 at a fixed 9600 8N1 and uses only holding registers (FC03/06/16, up to 5 registers per request). This map covers the registers PVI lists for typical BMS use: probe temperatures, set point, modulation rate, burner hours, relay status, alarms and the on/off command.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": null,
  "baud": 9600,
  "parity": "None",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "Modicon",
  "note": "The manual uses register numbers: holding register 40001 is address 0 on the wire, so subtract 40001 (40769 -> 768). Coils are numbered from 00001 the same way, so coil 513 is wire address 512."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "MODBUS-RTU Applied to the TempTrac Control",
  "doc_number": "PV500-42 06/2014",
  "revision_date": "2014-06",
  "url": "https://www.ccontrols.com/support/dp/PV500-42.pdf",
  "pages": "p. 4 (register numbering), pp. 10-14 (Table 2), pp. 15-16 (typical parameters, port setup)",
  "unofficial": true
 },
 "notes": [
  "PVI does not host this manual publicly that we could find; this copy is served by a controls distributor and is the unaltered PVI document (PVI Industries footer, document number on every page).",
  "Only the registers in section 4.2 'Typical parameters' and the clearly readable status/alarm rows are included; the long parameter list in Table 2 (pp. 10-14) did not extract cleanly and is left out.",
  "Temperatures are whole degrees F per section 4.2. The display resolution option (rES) applies only to Celsius; its effect on Modbus values is not documented, so Celsius operation is not covered here.",
  "Alarm bits follow the decimal values and bit numbers in the manual (bit 0 = 1). The manual's hex values for Alarm 2 (0x1000) and Alarm 3 (0x0800) disagree with their decimal values (2048, 4096); the decimal/bit numbers are used.",
  "Register 41281 also accepts keypad lock/unlock and buzzer-silence codes; PVI notes that only the on/off command is normally needed.",
  "Table 2 gives a hex base-0 address next to each register number (e.g. St1 0x300 = 40769), which confirms the 40001 = address 0 rule."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 256,
   "documented": "40257",
   "name": "Probe 1 temperature (TP1)",
   "description": "Operating probe that set point St1 controls to; degrees F.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°F",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 258,
   "documented": "40259",
   "name": "Probe 2 temperature (TP2)",
   "description": "Returns an exception if probe 2 is disabled.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°F",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 260,
   "documented": "40261",
   "name": "Probe 3 temperature (TP3)",
   "description": "Returns an exception if probe 3 is disabled.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°F",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 262,
   "documented": "40263",
   "name": "Modulation rate output",
   "description": "Firmware 0.5 only: 4-20 mA modulation output, 0-100 % (0 = low fire on most units).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 768,
   "documented": "40769",
   "name": "Set point 1 (St1)",
   "description": "Main system set point.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°F",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 848,
   "documented": "40849",
   "name": "Working hours relay 1 (ou1)",
   "description": "Burner run hours, rolls over at 9999.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "h",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 857,
   "documented": "40858",
   "name": "Serial address (Adr)",
   "description": "Modbus slave address 1-247.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1280,
   "documented": "41281",
   "name": "Control command (on/off)",
   "description": "Write-only command word; 257 = ON, 1 = OFF. Reads are invalid.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": {
    "257": "On",
    "1": "Off",
    "2056": "Keypad lock",
    "8": "Keypad unlock",
    "4112": "Silence buzzer"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2049,
   "documented": "42050",
   "name": "Relay status",
   "description": "Relay 1 bit = call for heat (burner on).",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Relay 1 (burner on)",
    "1": "Relay 2",
    "2": "Relay 3"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3328,
   "documented": "43329",
   "name": "Alarm register",
   "description": "Bit meanings listed are the firmware 0.5 rows; on firmware 0.3, bit 12 flags input 2/3 alarms.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Low temperature alarm (LA)",
    "1": "High temperature alarm (HA)",
    "2": "Probe 1 error",
    "8": "Probe 2 error",
    "9": "Probe 3 error",
    "10": "Alarm 1 (input 1)",
    "11": "Alarm 2 (lockout, input 2)",
    "12": "Alarm 3 (lockout, alarm on any failure)",
    "13": "Maintenance relay 1",
    "14": "Maintenance relay 2",
    "15": "Maintenance relay 3"
   },
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Poll 9600 8N1 with FC03, no more than 5 registers per request. Read probe 1 (40257), relay status (42050) and alarms (43329); write the set point at 40769 and turn the heater on/off by writing 257/1 to 41281.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 256,
    "why": "Probe 1 temperature"
   },
   {
    "table": "holding_register",
    "address": 768,
    "why": "Set point 1"
   },
   {
    "table": "holding_register",
    "address": 2049,
    "why": "Relay / burner status"
   },
   {
    "table": "holding_register",
    "address": 3328,
    "why": "Alarm flags"
   },
   {
    "table": "holding_register",
    "address": 1280,
    "why": "On/off command"
   },
   {
    "table": "holding_register",
    "address": 848,
    "why": "Burner hours"
   }
  ],
  "enable": "Modbus RTU is available through the XJ485 serial interface (TTL to RS-485) connected to the TempTrac's programming port.",
  "watchdog": null,
  "quirks": [
   "Maximum 5 registers per read or write.",
   "Register numbers are Modicon-style; subtract 40001.",
   "41281 is write-only; reading it returns invalid data."
  ],
  "setup": [
   "Fixed serial settings: 9600 baud, 8 data bits, no parity, 1 stop bit (not adjustable).",
   "Set the slave address (1-247) on the keypad; each unit on the bus needs its own address.",
   "Leave at least 500 ms before a retry. The controller has no bias resistors; bias the line at the master."
  ],
  "gotchas": [
   "Reading probe 2 or 3 returns an exception when that probe is disabled.",
   "In OFF the display shows OFF and outputs are open, but temperatures can still be read."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/pvi-industries/temptrac",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}