 "manufacturer": "PVI Industries",
 "manufacturer_slug": "pvi-industries",
 "model": "XR10CX water heater digital operating controller (Modbus RTU)",
 "model_slug": "xr10cx",
 "short_model": "XR10CX",
 "aliases": [
  "XR10CX",
  "PV500-67"
 ],
 "equipment_type": "Boiler (water heater controller)",
 "applies_to": "PVI XR10CX digital operating controls on RS-485 Modbus RTU, per PVI manual PV500-67 (06/2014).",
 "summary": "The XR10CX is a digital operating control used on PVI water heaters. It is a Modbus RTU slave on 2-wire RS-485 at a fixed 9600 8N1, with a handful of holding registers for temperature and set points and output coils for on/off, keypad lock, alarms and the call-for-heat relay.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": null,
  "baud": 9600,
  "parity": "None",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "Modicon",
  "note": "The manual uses register numbers: holding register 40001 is address 0 on the wire, so subtract 40001 (40769 -> 768). Coils are numbered from 00001 the same way, so coil 513 is wire address 512."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "MODBUS-RTU Applied to the XR10CX Control",
  "doc_number": "PV500-67 06/2014",
  "revision_date": "2014-06",
  "url": "https://www.ccontrols.com/support/dp/PV500-67.pdf",
  "pages": "p. 4 (register numbering), p. 12 (Table 2), p. 13 (typical parameters, port setup)",
  "unofficial": true
 },
 "notes": [
  "PVI does not host this manual publicly that we could find; this copy is served by a controls distributor and is the unaltered PVI document (PVI Industries footer, document number on every page).",
  "Temperatures are whole degrees F per section 4.2.",
  "The manual is inconsistent about coil 513: Table 2 lists it as a Read/Write coil, while section 4.2 says ON/OFF is written as 257/1 and calls it write-only. Treat it as a standard on/off coil and confirm on site.",
  "Units for the differential and alarm delays are not stated in the table."
 ],
 "registers": [
  {
   "table": "coil",
   "address": 512,
   "documented": "513",
   "name": "On/off for control",
   "description": "Enables or disables the controller.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 515,
   "documented": "516",
   "name": "Keypad lock",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 516,
   "documented": "517",
   "name": "Mute buzzer and any-alarm",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 519,
   "documented": "520",
   "name": "Digital input pin 9",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 520,
   "documented": "521",
   "name": "Probe 1 error",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 521,
   "documented": "522",
   "name": "Probe 2 error",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 522,
   "documented": "523",
   "name": "Probe 3 error",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 523,
   "documented": "524",
   "name": "Probe 4 error",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 524,
   "documented": "525",
   "name": "High temperature alarm Pb1",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 525,
   "documented": "526",
   "name": "Low temperature alarm Pb1",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 528,
   "documented": "529",
   "name": "Alarm from external input",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 531,
   "documented": "532",
   "name": "EEPROM failure",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 537,
   "documented": "538",
   "name": "Any-alarm (can be muted)",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 542,
   "documented": "543",
   "name": "Relay call for heat",
   "description": "On = burner signal on.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 544,
   "documented": "545",
   "name": "Buzzer on with external or high alarm",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 256,
   "documented": "40257",
   "name": "Probe 1 temperature (PRB1)",
   "description": "Operating probe; degrees F.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°F",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 768,
   "documented": "40769",
   "name": "Differential (HY)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 829,
   "documented": "40830",
   "name": "Temperature alarm delay (ALd)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 830,
   "documented": "40831",
   "name": "Temperature alarm delay at startup (dAo)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 846,
   "documented": "40847",
   "name": "Digital input alarm delay (did)",
   "description": "0-255 min.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 851,
   "documented": "40852",
   "name": "Modbus address (Adr)",
   "description": "1-247.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 863,
   "documented": "40864",
   "name": "System set point (Set)",
   "description": "Main set point.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°F",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Poll 9600 8N1. Read probe 1 at 40257 and the set point at 40864 with FC03; read status coils 513-545 with FC01, and switch the control on/off with coil 513.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 256,
    "why": "Probe 1 temperature"
   },
   {
    "table": "holding_register",
    "address": 863,
    "why": "System set point"
   },
   {
    "table": "coil",
    "address": 542,
    "why": "Call for heat relay"
   },
   {
    "table": "coil",
    "address": 537,
    "why": "Any-alarm"
   },
   {
    "table": "coil",
    "address": 512,
    "why": "On/off for control"
   },
   {
    "table": "coil",
    "address": 520,
    "why": "Probe 1 error"
   }
  ],
  "enable": "Modbus RTU is available through the XJ485 serial interface connected to the XR10CX programming port.",
  "watchdog": null,
  "quirks": [
   "Maximum 5 registers per request.",
   "Register and coil numbers are Modicon-style; subtract 40001 for registers and 1 for coils.",
   "Coils can be read up to 80 at a time but written only one at a time."
  ],
  "setup": [
   "Fixed serial settings: 9600 baud, 8 data bits, no parity, 1 stop bit (not adjustable).",
   "Set the slave address (1-247) on the keypad; each unit on the bus needs its own address.",
   "Leave at least 500 ms before a retry. The controller has no bias resistors; bias the line at the master."
  ],
  "gotchas": [
   "In OFF the display shows OFF and outputs are open, but temperatures can still be read."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/pvi-industries/xr10cx",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}