 "manufacturer": "Radwag",
 "manufacturer_slug": "radwag",
 "model": "MW-01-A / MW-01-A7 mass converter",
 "model_slug": "mw-01-a",
 "short_model": "MW-01-A",
 "aliases": [
  "MW-01-A",
  "MW-01-A7"
 ],
 "equipment_type": "Sensor (weighing transmitter / mass converter)",
 "applies_to": "Radwag MW-01-A and MW-01-A7 mass converters per the November 2021 Modbus manual.",
 "summary": "The MW-01-A mass converter serves Modbus RTU on RS-485 and Modbus TCP (and RTU over TCP) on Ethernet. Input registers return mass, tare, unit, status, thresholds and dosing/adjustment state; holding registers take zero, tare, dosing and calibration commands plus threshold writes. Floats here are low word first, unlike Radwag's PUE indicators.",
 "transport": [
  "RTU",
  "TCP"
 ],
 "defaults": {
  "unit_id": null,
  "baud": null,
  "parity": null,
  "data_bits": null,
  "stop_bits": null,
  "tcp_port": null
 },
 "addressing": {
  "convention": "Modicon",
  "note": "The tables list a 0-based Offset next to a 30001/40001-style Modbus address; the offset goes on the wire (mass = offset 0 = 30001, Command = offset 256 = 40257)."
 },
 "default_word_order": "CDAB",
 "firmware": null,
 "source": {
  "title": "Software manual MODBUS - Communication Protocol of MW-01-A Mass Converter",
  "doc_number": "ITKP-41-01-11-21-EN",
  "revision_date": "2021-11",
  "url": "https://radwag.com/document/en/user-manual-modbus-communication-protocol-of-mw-01-a-mw-01-a7-mass-converter__MODBUS-MW-01-A-ITKP-41-01-11-21-EN.pdf",
  "pages": "Functions and data structure p. 4; input registers p. 5; meanings pp. 5-7; holding registers p. 7; command bits p. 8"
 },
 "notes": [
  "Floats are two registers with the low word first (CDAB): the manual's example has 30001 = 0x72B0 and 30002 = 0x3E68 giving 0.227, and its tare write example puts 0x0000 in the first register and 0x3F80 in the second.",
  "Left out: 'Precise dosing threshold' (input offset 40, holding offset 270) and 'Adjustment weight mass' (holding offset 272), because the table lists them as float with a length of 1 register, which cannot both be right.",
  "The manual's write examples label registers as 40000 + offset (40257 = 'command with parameter' at offset 257, tare at 40259/40260 = offsets 259-260), so they agree with the offset column on the wire; the output-mask example (40502/40507) is copied from another product and does not fit this map. This map follows the table's offset column.",
  "Settings (address, baud, IP) are made with Radwag's MwManager PC software; the Modbus manual gives no defaults."
 ],
 "registers": [
  {
   "table": "input_register",
   "address": 0,
   "documented": "30001",
   "name": "Mass",
   "description": "Mass in the currently displayed unit.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2,
   "documented": "30003",
   "name": "Tare",
   "description": "Tare in the adjustment (calibration) unit.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 4,
   "documented": "30005",
   "name": "Unit",
   "description": "Bit set shows the unit now displayed.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "gram [g]",
    "1": "kilogram [kg]",
    "2": "carat [ct]",
    "3": "pound [lb]",
    "4": "ounce [oz]",
    "5": "Newton [N]"
   },
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 5,
   "documented": "30006",
   "name": "Status",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Measurement correct (no error)",
    "1": "Measurement stable",
    "2": "Indicating zero",
    "3": "Tared",
    "4": "In weighing range II",
    "5": "In weighing range III",
    "6": "NULL error",
    "7": "LH error",
    "8": "FULL error"
   },
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 6,
   "documented": "30007",
   "name": "LO threshold",
   "description": "In the adjustment unit.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 32,
   "documented": "30033",
   "name": "Dosing status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Process disabled",
    "1": "Dosing in progress",
    "2": "Process stopped",
    "3": "Process finished"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 33,
   "documented": "30034",
   "name": "Input status",
   "description": "Bitmask of converter inputs; the 8 low bits are the inputs, bit 0 = input 1.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 34,
   "documented": "30035",
   "name": "Min",
   "description": "MIN threshold, adjustment unit.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 36,
   "documented": "30037",
   "name": "Max",
   "description": "MAX threshold, adjustment unit.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 38,
   "documented": "30039",
   "name": "Fast dosing threshold",
   "description": "Adjustment unit.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 50,
   "documented": "30051",
   "name": "Adjustment status",
   "description": "State of the adjustment (calibration) process.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Process finished correctly",
    "1": "Start mass / adjustment factor determination in progress",
    "2": "Range exceeded",
    "3": "Time exceeded",
    "4": "Process aborted",
    "5": "Awaiting data"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 256,
   "documented": "40257",
   "name": "Command",
   "description": "Set a bit to run that action once; clear it before repeating.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Zero the platform",
    "1": "Tare the platform",
    "5": "Process start",
    "6": "Process stop",
    "8": "Start mass determination",
    "9": "Adjustment factor determination",
    "10": "Record adjustment parameters"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 257,
   "documented": "40258",
   "name": "Command with parameter",
   "description": "Set a bit to apply the matching parameter register below.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Set tare value",
    "1": "Set LO threshold",
    "2": "Set outputs state",
    "3": "Set MIN threshold",
    "4": "Set MAX threshold",
    "5": "Set fast dosing threshold",
    "6": "Set precise dosing threshold",
    "9": "Set adjustment weight mass"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 258,
   "documented": "40259",
   "name": "Platform",
   "description": "Platform number for parameter commands (always 1).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 259,
   "documented": "40260",
   "name": "Tare",
   "description": "Tare to set, adjustment unit.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 261,
   "documented": "40262",
   "name": "LO threshold",
   "description": "LO threshold to set, adjustment unit.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 263,
   "documented": "40264",
   "name": "Output state",
   "description": "Output mask to apply, bit 0 = output 1.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 264,
   "documented": "40265",
   "name": "Min",
   "description": "MIN threshold to set.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 266,
   "documented": "40267",
   "name": "Max",
   "description": "MAX threshold to set.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 268,
   "documented": "40269",
   "name": "Fast dosing threshold",
   "description": "Fast dosing threshold to set.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Read input registers (FC04) from offset 0: mass is a low-word-first float at offset 0 and the status bits at offset 5. Write bit 0 or 1 of the Command register (offset 256) to zero or tare, clearing it before repeating.",
  "minimum_registers": [
   {
    "table": "input_register",
    "address": 0,
    "why": "Mass"
   },
   {
    "table": "input_register",
    "address": 5,
    "why": "Status (stable, zero, errors)"
   },
   {
    "table": "input_register",
    "address": 4,
    "why": "Displayed unit"
   },
   {
    "table": "input_register",
    "address": 32,
    "why": "Dosing status"
   },
   {
    "table": "holding_register",
    "address": 256,
    "why": "Zero / tare / dosing commands"
   }
  ],
  "enable": "Configure communication with the MwManager PC software under Parameters / Set Communication.",
  "watchdog": null,
  "quirks": [
   "Floats are CDAB (low word first).",
   "Commands act on a bit being set; write 0 first to repeat the same command."
  ],
  "setup": [
   "Use MwManager to set the RS-485 or Ethernet parameters."
  ],
  "gotchas": [
   "Do not reuse a PUE indicator template: the MW-01-A float word order and holding addresses differ."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/radwag/mw-01-a",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}