 "manufacturer": "Realtime Control Systems",
 "manufacturer_slug": "realtime-controls",
 "model": "RTD-NET Modbus interface for Daikin VRV / Sky Air",
 "model_slug": "rtd-net",
 "short_model": "RTD-NET",
 "aliases": [
  "RTD-NET",
  "RTD-10",
  "Daikin RTD-NET"
 ],
 "equipment_type": "VRF / split AC gateway",
 "applies_to": "RTD-NET on the Daikin P1/P2 bus (VRV, Sky Air, VAM/VKM), up to 16 indoor units as one group; RTD-10 with the same firmware uses the same layout.",
 "summary": "Small Modbus RTU slave that joins a Daikin P1/P2 remote-controller bus and controls up to 16 indoor units as one group. Holding registers carry setpoint, fan, mode, louvre and on/off plus keypad lock modes and limits; input registers return group and per-unit temperatures, faults, filter and defrost state.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": null,
  "baud": 9600,
  "parity": "None",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "0-based",
  "note": "The manual states register base 0 and writes registers as H0010 / I0010 meaning wire address 10. Per-unit input registers are numbered unit x 100 + offset (unit 1 = 0120..0132, unit 16 = 1620..1632)."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "RTD-NET Installation Instructions",
  "doc_number": "18870-1.06.03",
  "revision_date": null,
  "url": "https://www.daikin.eu/content/dam/document-library/installation-manuals/ctrl/RTD-NET%20installation%20instructions_18870-1.06%20EN_Installation%20manuals_English.pdf",
  "pages": "pp. 6-11 (Modbus configuration, control, limits, VAM, readback, fault codes)"
 },
 "notes": [
  "Every register is 16 bits. Temperatures in input registers are signed and multiplied by 100; setpoint and setpoint limits are whole °C (16..32).",
  "Only unit 1 of the per-unit block is listed. For unit n add (n-1) x 100 to each address (e.g. unit 2 return air = 223).",
  "Fanspeed inhibit (H0022) is listed without bit meanings: the manual's fan inhibit table (Low 2, High 13) does not follow the powers-of-two pattern of the mode and louvre tables, so it is not decoded here.",
  "Fault codes are two ASCII characters packed high byte / low byte (e.g. 16697 = 'A9'). The full Daikin code table is published by Realtime Controls separately.",
  "Function codes 03, 04, 06 and 16 are supported, 1..10 registers per request.",
  "The Modbus slave address is set 0..63 on DIP switch SW1."
 ],
 "registers": [
  {
   "table": "input_register",
   "address": 20,
   "documented": "I0020",
   "name": "Unit Count",
   "description": "Indoor units found on the P1/P2 bus, 0..16.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 21,
   "documented": "I0021",
   "name": "Is Fault (group)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No fault",
    "1": "At least one unit in fault"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 22,
   "documented": "I0022",
   "name": "Fault Code (group)",
   "description": "Code of the first faulted unit; two ASCII characters, high byte first.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Waiting for data",
    "255": "No fault",
    "14384": "80 - group fault, no units found",
    "14388": "84 - unit missing"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 23,
   "documented": "I0023",
   "name": "Return Air Average",
   "description": "Mean of all unit return-air temperatures.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 24,
   "documented": "I0024",
   "name": "Filter Alarm (group)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No alarm",
    "1": "At least one unit with filter alarm"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 25,
   "documented": "I0025",
   "name": "Return Air Min",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 26,
   "documented": "I0026",
   "name": "Return Air Max",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 30,
   "documented": "I0030",
   "name": "Thermo On (group)",
   "description": "Summary of what the group is doing.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Idle/Fan",
    "1": "Heating",
    "2": "Cooling",
    "3": "Heat and Cool"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 35,
   "documented": "I0035",
   "name": "Defrost",
   "description": "Also set during pressure equalisation and hot start.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No defrost",
    "1": "At least one unit in defrost"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 50,
   "documented": "I0050",
   "name": "RC Temperature",
   "description": "Remote controller sensor; only with one indoor unit and RC as MAIN.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 51,
   "documented": "I0051",
   "name": "RC Operation Mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Idle/Fan",
    "1": "Heating",
    "2": "Cooling",
    "3": "Heat and Cool"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 120,
   "documented": "0120",
   "name": "Unit 1 Unit Exists",
   "description": "Unit n: register n*100+20.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No unit found",
    "1": "Unit found"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 121,
   "documented": "0121",
   "name": "Unit 1 Is Fault",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No unit fault",
    "1": "Unit in fault"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 122,
   "documented": "0122",
   "name": "Unit 1 Fault Code",
   "description": "Two ASCII characters, high byte first; 255 = no fault.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "255": "No fault"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 123,
   "documented": "0123",
   "name": "Unit 1 Return Air Temperature",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 124,
   "documented": "0124",
   "name": "Unit 1 Filter Alarm",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No alarm",
    "1": "Filter alarm"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 130,
   "documented": "0130",
   "name": "Unit 1 Thermo On",
   "description": "Only when the RTD runs as P1/P2 MAIN.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Idle/Fan",
    "1": "Heating",
    "2": "Cooling"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 131,
   "documented": "0131",
   "name": "Unit 1 Coil In Temperature",
   "description": "Only when the RTD runs as P1/P2 MAIN.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 132,
   "documented": "0132",
   "name": "Unit 1 Coil Out Temperature",
   "description": "Only when the RTD runs as P1/P2 MAIN.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1,
   "documented": "H0001",
   "name": "Setpoint",
   "description": "Group setpoint, whole degrees 16..32.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "H0002",
   "name": "Fanspeed",
   "description": "High2 is HighHigh only where that speed is enabled.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Low",
    "2": "High1",
    "3": "High2"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3,
   "documented": "H0003",
   "name": "Mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Auto",
    "1": "Heat",
    "2": "Fan",
    "3": "Cool",
    "4": "Dry"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4,
   "documented": "H0004",
   "name": "Louvre",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Swing",
    "2": "0 degrees",
    "3": "20 degrees",
    "4": "45 degrees",
    "5": "70 degrees",
    "6": "90 degrees"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5,
   "documented": "H0005",
   "name": "OnOff",
   "description": "Also switches VAM/VKM ventilation units.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10,
   "documented": "H0010",
   "name": "Global Update",
   "description": "Writes the same update mode to all update registers.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Last Touch (keypad unlocked)",
    "1": "Central (keypad locked, value re-sent)",
    "2": "Local (keypad unlocked, writes not sent)",
    "3": "On Change (sent only when value changes)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11,
   "documented": "H0011",
   "name": "Setpoint Update",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Last Touch (keypad unlocked)",
    "1": "Central (keypad locked, value re-sent)",
    "2": "Local (keypad unlocked, writes not sent)",
    "3": "On Change (sent only when value changes)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 12,
   "documented": "H0012",
   "name": "Fanspeed Update",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Last Touch (keypad unlocked)",
    "1": "Central (keypad locked, value re-sent)",
    "2": "Local (keypad unlocked, writes not sent)",
    "3": "On Change (sent only when value changes)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 13,
   "documented": "H0013",
   "name": "Mode Update",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Last Touch (keypad unlocked)",
    "1": "Central (keypad locked, value re-sent)",
    "2": "Local (keypad unlocked, writes not sent)",
    "3": "On Change (sent only when value changes)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14,
   "documented": "H0014",
   "name": "Louvre Update",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Last Touch (keypad unlocked)",
    "1": "Central (keypad locked, value re-sent)",
    "2": "Local (keypad unlocked, writes not sent)",
    "3": "On Change (sent only when value changes)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 15,
   "documented": "H0015",
   "name": "OnOff Update",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Last Touch (keypad unlocked)",
    "1": "Central (keypad locked, value re-sent)",
    "2": "Local (keypad unlocked, writes not sent)",
    "3": "On Change (sent only when value changes)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 20,
   "documented": "H0020",
   "name": "Setpoint Min",
   "description": "Lowest setpoint allowed locally, 16..32; 0 = no limit.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 21,
   "documented": "H0021",
   "name": "Setpoint Max",
   "description": "Highest setpoint allowed locally, 16..32; 0 = no limit.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 22,
   "documented": "H0022",
   "name": "Fanspeed Inhibit",
   "description": "Sum of inhibit values of speeds to block; 0 = none. See notes.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 23,
   "documented": "H0023",
   "name": "Mode Inhibit",
   "description": "Set bits block those modes; 0 = no inhibit.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Auto (1)",
    "1": "Heat (2)",
    "2": "Fan (4)",
    "3": "Cool (8)",
    "4": "Dry (16)"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 24,
   "documented": "H0024",
   "name": "Louvre Inhibit",
   "description": "Set bits block those louvre settings; 0 = no inhibit.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "1": "Swing (2)",
    "2": "0 degrees (4)",
    "3": "20 degrees (8)",
    "4": "45 degrees (16)",
    "5": "70 degrees (32)",
    "6": "90 degrees (64)"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 30,
   "documented": "H0030",
   "name": "VAM Damper Control",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Auto",
    "1": "Cross flow / heat recovery",
    "2": "Bypass"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 31,
   "documented": "H0031",
   "name": "VAM Fanspeed",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Low",
    "2": "High"
   },
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Set the slave address on SW1, wire DB/DA/GND, then write H0001-H0005 for setpoint, fan, mode, louvre and on/off and poll I0020-I0035 for group status. Use the update registers to decide whether the wall controller stays usable.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 5,
    "why": "Group on/off"
   },
   {
    "table": "holding_register",
    "address": 3,
    "why": "Mode"
   },
   {
    "table": "holding_register",
    "address": 1,
    "why": "Setpoint"
   },
   {
    "table": "holding_register",
    "address": 2,
    "why": "Fan speed"
   },
   {
    "table": "input_register",
    "address": 23,
    "why": "Average return air"
   },
   {
    "table": "input_register",
    "address": 21,
    "why": "Any unit faulted"
   },
   {
    "table": "input_register",
    "address": 22,
    "why": "Fault code"
   },
   {
    "table": "input_register",
    "address": 20,
    "why": "Units found"
   }
  ],
  "enable": "No enable step: holding-register writes act on the group straight away. The update registers (H0010-H0015) choose Last Touch (default), Central (locks keypad buttons), Local or On Change behaviour.",
  "watchdog": "Optional, set by a SW1 DIP switch: if no holding-register write arrives for 120 s all units are switched on with their current settings, and remote controllers are either unlocked or left as they are depending on the switch.",
  "quirks": [
   "Temperatures above 32767 are negative: subtract 65536, then divide by 100.",
   "In Last Touch mode a master that rewrites the same value every scan overrides the wall controller; use On Change (3) if your master writes cyclically.",
   "Coil and per-unit thermo readings exist only when the RTD is the P1/P2 MAIN controller."
  ],
  "setup": [
   "9600 baud, no parity, 1 stop bit by default (other rates available on request from the maker).",
   "Slave address 0..63 on SW1.",
   "Daisy-chain DB(+), DA(-) and GND; no star or ring wiring; up to 500 m without repeaters.",
   "Power 15-24 V DC from the indoor unit PCB (X18A/X35A) or a separate supply."
  ],
  "gotchas": [
   "Infra-red BRC receivers must be set to SUB when the RTD is MAIN.",
   "If the P1/P2 bus is not found within 1 minute the RTD raises an alarm on its fault output."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/realtime-controls/rtd-net",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}