 "manufacturer": "Realtime Control Systems",
 "manufacturer_slug": "realtime-controls",
 "model": "RTD-RA Modbus interface for Daikin room air conditioners",
 "model_slug": "rtd-ra",
 "short_model": "RTD-RA",
 "aliases": [
  "RTD-RA",
  "Daikin RTD-RA"
 ],
 "equipment_type": "VRF / split AC gateway",
 "applies_to": "RTD-RA plugged into the S21 port of a Daikin room air conditioner (split) indoor unit, installation instructions 21070-1.07.04.",
 "summary": "Interface that plugs into the S21 connector of a Daikin split / room air conditioner and exposes it as a Modbus RTU slave when its address is 1 or higher. Holding registers set setpoint, fan, mode, louvre, on/off, forced thermo-off and local limits; input registers report fault state, fault code, return-air and coil temperatures.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": null,
  "baud": 9600,
  "parity": "None",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "0-based",
  "note": "Register base 0: H0005 is holding register wire address 5 and I0123 is input register wire address 123."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "RTD-RA Installation Instructions",
  "doc_number": "21070-1.07.04",
  "revision_date": null,
  "url": "https://www.daikin.es/content/dam/MDM/TechnicalDrawings/Split/EN/RTD-RA%20Installation%20Instructions%2021070-1.07_EN.pdf",
  "pages": "pp. 8-13 (Modbus configuration, slave operation, control, limits, readback, fault codes)"
 },
 "notes": [
  "All registers are 16 bits. Readback temperatures are signed and x100; setpoint and limits are whole °C.",
  "Fault codes pack two ASCII characters (high byte, low byte). Daikin code table is published separately by Realtime Controls.",
  "Function codes 03, 04, 06 and 16 supported, 1..10 registers per request.",
  "With the SW1 address set to 0 the RTD-RA runs stand-alone (inputs S1/S2 control it) and is not a Modbus slave."
 ],
 "registers": [
  {
   "table": "input_register",
   "address": 121,
   "documented": "I0121",
   "name": "Is Fault",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No unit fault",
    "1": "Unit in fault"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 122,
   "documented": "I0122",
   "name": "Fault Code",
   "description": "Two ASCII characters, high byte first.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Waiting for data",
    "255": "No fault",
    "14384": "80 - group fault, no units found"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 123,
   "documented": "I0123",
   "name": "Return Air Temperature",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 130,
   "documented": "I0130",
   "name": "Thermo On",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Idle/Fan",
    "1": "Heating",
    "2": "Cooling"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 131,
   "documented": "I0131",
   "name": "Coil Inlet Temperature",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1,
   "documented": "H0001",
   "name": "Setpoint",
   "description": "Whole degrees; heat 10..30, cool 18..32 (model dependent).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "H0002",
   "name": "Fanspeed",
   "description": "Some models have fewer than 5 speeds.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Auto",
    "1": "Fan 1",
    "2": "Fan 2",
    "3": "Fan 3",
    "4": "Fan 4",
    "5": "Fan 5"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3,
   "documented": "H0003",
   "name": "Mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Auto",
    "1": "Heat",
    "2": "Fan",
    "3": "Cool",
    "4": "Dry"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4,
   "documented": "H0004",
   "name": "Louvre",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Stop",
    "1": "Swing"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5,
   "documented": "H0005",
   "name": "OnOff",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10,
   "documented": "H0010",
   "name": "Global Update",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Last Touch (unlocked)",
    "1": "Central (local control locked)",
    "2": "Local (writes not sent)",
    "3": "On Change (sent only on change)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 20,
   "documented": "H0020",
   "name": "Setpoint Min",
   "description": "16..32; 0 = no limit.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 21,
   "documented": "H0021",
   "name": "Setpoint Max",
   "description": "16..32; 0 = no limit.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 22,
   "documented": "H0022",
   "name": "Fanspeed Inhibit",
   "description": "Set bits block those speeds; 0 = no inhibit.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Auto (1)",
    "1": "Fan 1 (2)",
    "2": "Fan 2 (4)",
    "3": "Fan 3 (8)",
    "4": "Fan 4 (16)",
    "5": "Fan 5 (32)"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 23,
   "documented": "H0023",
   "name": "Mode Inhibit",
   "description": "Set bits block those modes; 0 = no inhibit.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Auto (1)",
    "1": "Heat (2)",
    "2": "Fan (4)",
    "3": "Cool (8)",
    "4": "Dry (16)"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 24,
   "documented": "H0024",
   "name": "Louvre Inhibit",
   "description": "Set bits block those louvre settings; 0 = no inhibit.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Stop (1)",
    "1": "Swing (2)"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 37,
   "documented": "H0037",
   "name": "Force Thermo Off",
   "description": "Holds the compressor off while the unit stays on.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Thermo enabled",
    "1": "Thermo off"
   },
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Set an address of 1..63 on SW1 so the unit becomes a Modbus slave, then write H0001-H0005 and poll I0121-I0131. H0010 decides whether the IR remote stays usable.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 5,
    "why": "On/off"
   },
   {
    "table": "holding_register",
    "address": 3,
    "why": "Mode"
   },
   {
    "table": "holding_register",
    "address": 1,
    "why": "Setpoint"
   },
   {
    "table": "holding_register",
    "address": 2,
    "why": "Fan speed"
   },
   {
    "table": "input_register",
    "address": 123,
    "why": "Return air temperature"
   },
   {
    "table": "input_register",
    "address": 121,
    "why": "Fault flag"
   },
   {
    "table": "input_register",
    "address": 122,
    "why": "Fault code"
   }
  ],
  "enable": "Modbus slave mode is active whenever the SW1 address is 1 or higher; address 0 selects stand-alone mode. Closing input S2 in slave mode selects clone mode, which disables Modbus control.",
  "watchdog": "Optional via SW1: with no holding-register write for 120 s the unit is switched on with its current settings and local control is unlocked or left as is, depending on the switch.",
  "quirks": [
   "Readback temperatures above 32767 are negative: subtract 65536 then divide by 100.",
   "Repeated identical writes in Last Touch mode override the user's remote; use On Change (3) for cyclic writers."
  ],
  "setup": [
   "9600 baud, no parity, 1 stop bit by default.",
   "Address on SW1 (0..63; 0 = stand-alone).",
   "RS485 3-wire: DB(+), DA(-), GND, daisy-chained."
  ],
  "gotchas": [
   "Supported setpoint range and number of fan speeds vary by indoor unit model."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/realtime-controls/rtd-ra",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}