 "manufacturer": "Realtime Control Systems",
 "manufacturer_slug": "realtime-controls",
 "model": "RTD-W Modbus interface for Daikin Altherma HT hydrobox and small inverter chillers",
 "model_slug": "rtd-w",
 "short_model": "RTD-W",
 "aliases": [
  "RTD-W",
  "Daikin RTD-W"
 ],
 "equipment_type": "Heat pump / chiller Modbus interface",
 "applies_to": "RTD-W on the P1/P2 bus with a BRC21 controller as main: Daikin Altherma HT hydroboxes, small inverter chillers EWA/YQ16..64 and the heating-only VRV hydrobox; up to 16 units as one group. Instructions 20670-1.07.12.",
 "summary": "Small Modbus RTU slave that joins the P1/P2 bus of Daikin Altherma HT hydroboxes and small inverter chillers. Holding registers set leaving-water and room setpoints, mode, on/off, domestic hot water and quiet mode; input registers return group status, temperatures x100, pump and compressor state, run hours and per-PCB data.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": null,
  "baud": 9600,
  "parity": "None",
  "data_bits": null,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "0-based",
  "note": "The manual states register base 0 and writes H0010 / I0010 for holding / input register 10, so the number after H or I is the wire address. Per-PCB input registers are numbered xx00..xx99 with xx = PCB 01..16; this file lists PCB 01 (I0122..I0147)."
 },
 "default_word_order": "ABCD",
 "firmware": null,
 "source": {
  "title": "Instructions pour l'installation de RTD-W (RTD-W Installation Instructions, French)",
  "doc_number": "20670-1.07.12",
  "revision_date": null,
  "url": "https://res.cloudinary.com/sonepar-fr/raw/upload/s--ayUiJ1AJ--/v1/documents/121/RTD-W_Installation_Instructions_20670-1.07_FR.pdf",
  "pages": "pp. 8-11 (Modbus configuration, data types, control and read-back registers)",
  "unofficial": true
 },
 "notes": [
  "The source is the French edition of the Realtime Control Systems installation instructions, from a Sonepar (distributor) file host. The maker's own site (realtime-controls.co.uk) was offline and no Daikin-hosted copy was found, so the link is marked unofficial.",
  "All values are 16-bit unless stated. Temperatures marked 'x100' are signed: raw 2150 = 21.50 °C, raw 65036 = -5.00 °C. Holding-register setpoints are printed in whole °C with no x100 marking and are listed at scale 1.",
  "Fault codes are in the 'RTD ASCII' format described in the RTD-NET instructions (two characters packed high byte / low byte).",
  "Supported function codes: 03 and 04 (1..10 registers), 06, and 16 (1..10 registers).",
  "Only PCB 01 of the per-PCB block is listed. For PCB xx add (xx-1) x 100 (PCB 02 leaving water = I0223).",
  "The pump run-hour counter is 32-bit unsigned: the manual's data-type table says R holds the high word and R+1 the low word.",
  "Control fields that the connected unit does not support read 32767 and ignore writes.",
  "Sensor-input mirror registers I10001..I10006 are left out: their printed range (0..1) and values (0 / 100) disagree.",
  "The Modbus address is 0..63 on SW1.3..SW1.8. Baud and parity can be changed from the defaults if needed."
 ],
 "registers": [
  {
   "table": "input_register",
   "address": 20,
   "documented": "I0020",
   "name": "P1P2 PCB count",
   "description": "Units found, 0..16.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 21,
   "documented": "I0021",
   "name": "Group error",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No error",
    "1": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 22,
   "documented": "I0022",
   "name": "Group error code",
   "description": "RTD ASCII format.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 23,
   "documented": "I0023",
   "name": "Group average leaving water temperature",
   "description": "Signed °C x 100.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 36,
   "documented": "I0036",
   "name": "Group error sub-code",
   "description": "0..99.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 50,
   "documented": "I0050",
   "name": "Remote controller room temperature",
   "description": "Signed °C x 100.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 70,
   "documented": "I0070",
   "name": "Space heating/cooling on/off",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 71,
   "documented": "I0071",
   "name": "Circulation pump running",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 72,
   "documented": "I0072",
   "name": "Compressor running",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 74,
   "documented": "I0074",
   "name": "Disinfection operation",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Idle",
    "1": "Busy"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 75,
   "documented": "I0075",
   "name": "Setback operation",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Idle",
    "1": "Busy"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 76,
   "documented": "I0076",
   "name": "Defrost / start-up mode",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Idle",
    "1": "Busy"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 77,
   "documented": "I0077",
   "name": "DHW reheat",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Idle",
    "1": "Busy"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 78,
   "documented": "I0078",
   "name": "DHW storage",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Idle",
    "1": "Busy"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 80,
   "documented": "I0080 / I0081",
   "name": "Accumulated pump run hours",
   "description": "I0080 high word, I0081 low word. Non-volatile.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 122,
   "documented": "I0122",
   "name": "PCB 01 error code",
   "description": "RTD ASCII format. Per-PCB block; see notes.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 123,
   "documented": "I0123",
   "name": "PCB 01 leaving water temperature",
   "description": "Signed °C x 100.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 131,
   "documented": "I0131",
   "name": "PCB 01 return water temperature",
   "description": "Signed °C x 100.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 132,
   "documented": "I0132",
   "name": "PCB 01 DHW tank temperature",
   "description": "Signed °C x 100. Only if fitted.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 133,
   "documented": "I0133",
   "name": "PCB 01 outdoor temperature",
   "description": "Signed °C x 100.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 136,
   "documented": "I0136",
   "name": "PCB 01 error sub-code",
   "description": "0..99.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 144,
   "documented": "I0144",
   "name": "PCB 01 system code",
   "description": "ASCII character.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 145,
   "documented": "I0145",
   "name": "PCB 01 type code",
   "description": "ASCII character.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 146,
   "documented": "I0146",
   "name": "PCB 01 series code",
   "description": "ASCII character.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 147,
   "documented": "I0147",
   "name": "PCB 01 capacity code",
   "description": "0..251.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1,
   "documented": "H0001",
   "name": "Leaving water setpoint, heating",
   "description": "Whole °C: 25..80 HT hydrobox, 25..50 inverter chiller.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "H0002",
   "name": "Leaving water setpoint, cooling",
   "description": "Whole °C: 5..20 HT hydrobox, -10..20 inverter chiller.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3,
   "documented": "H0003",
   "name": "Operating mode",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Heating",
    "2": "Cooling"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4,
   "documented": "H0004",
   "name": "Space heating/cooling Modbus on/off",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5,
   "documented": "H0005",
   "name": "Room temperature setpoint",
   "description": "Whole °C, 16..32.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6,
   "documented": "H0006",
   "name": "DHW reheat Modbus on/off",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 7,
   "documented": "H0007",
   "name": "DHW storage start",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Inactive",
    "1": "Start"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8,
   "documented": "H0008",
   "name": "Control source for mode and on/off",
   "description": "External = Modbus and S inputs only; Local = remote controller only.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "External",
    "2": "Local",
    "3": "Changeover (default)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9,
   "documented": "H0009",
   "name": "Quiet mode operation",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disable",
    "1": "Enable"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10,
   "documented": "H0010",
   "name": "Weather-dependent setpoint operation",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disable",
    "1": "Enable"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11,
   "documented": "H0011",
   "name": "Weather-dependent leaving water setpoint offset",
   "description": "-5..+5 °C.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 12,
   "documented": "H0012",
   "name": "Pump run-hour counter reset",
   "description": "Write 55555 to reset (raw value above the signed 16-bit range).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": {
    "55555": "Reset"
   },
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Set the Modbus address on SW1, wire DB/DA/GND, set H0008 to External or Changeover, then write H0001-H0006 for setpoints, mode and on/off and poll I0020-I0078 for status.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 4,
    "why": "Space heating/cooling on/off"
   },
   {
    "table": "holding_register",
    "address": 3,
    "why": "Heating or cooling"
   },
   {
    "table": "holding_register",
    "address": 1,
    "why": "Heating leaving water setpoint"
   },
   {
    "table": "holding_register",
    "address": 8,
    "why": "Who may switch the unit"
   },
   {
    "table": "input_register",
    "address": 23,
    "why": "Leaving water temperature (x100)"
   },
   {
    "table": "input_register",
    "address": 21,
    "why": "Group error"
   },
   {
    "table": "input_register",
    "address": 22,
    "why": "Error code"
   },
   {
    "table": "input_register",
    "address": 20,
    "why": "Units found on P1/P2"
   }
  ],
  "enable": "H0008 = 1 (External) or 3 (Changeover, default) lets Modbus switch the unit; 2 (Local) ignores Modbus on/off.",
  "watchdog": "If P1/P2 communication is lost for one minute the RTD raises an alarm on the fault relay R2; an RS485 communication timeout is also shown on the LEDs.",
  "quirks": [
   "Temperatures in input registers are x100 and signed; setpoints in holding registers are whole °C.",
   "Read at most 10 registers per request."
  ],
  "setup": [
   "RS485 D-Bus: DB(+), DA(-) and common GND, daisy chain only, up to 500 m without repeaters.",
   "Factory serial settings 9600 baud, no parity, 1 stop bit.",
   "Power 15..24 V DC, e.g. from X9A on the A3P board."
  ],
  "gotchas": [
   "The RTD-W works as a SUB controller: a BRC21 must be configured as MAIN on the P1/P2 bus."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/realtime-controls/rtd-w",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}