 "manufacturer": "Red Lion",
 "manufacturer_slug": "red-lion",
 "model": "PAX2C temperature/process PID controller (Modbus RTU/ASCII)",
 "model_slug": "pax2c",
 "short_model": "PAX2C",
 "aliases": [
  "PAX2CHZVR",
  "PAX2C00000",
  "PX2FCA0",
  "PX2FCA1"
 ],
 "equipment_type": "Thermostat / temperature and process PID controller",
 "applies_to": "PAX2C version 2.0 register table (LP0905F, 2017-02-27); the FlexCard (PX2FCA0/PX2FCA1) blocks of the same table are not included.",
 "summary": "The PAX2C is Red Lion's PID temperature and process controller. Its Modbus table starts with a block of frequently used registers (process value, setpoints, output power, tuning, alarms and status) followed by full configuration. This map covers that frequently used block, profile status and the serial settings.",
 "transport": [
  "RTU",
  "ASCII"
 ],
 "defaults": {
  "unit_id": 247,
  "baud": 38400,
  "parity": "None",
  "data_bits": 8,
  "stop_bits": null,
  "tcp_port": null
 },
 "addressing": {
  "convention": "1-based",
  "note": "Registers are numbered from 1; the table's own example reads register 2 with start address 00 01, and its notes refer to 41701-41710 for registers 1701-1710. Request register N at wire address N-1."
 },
 "default_word_order": "ABCD",
 "firmware": "PAX2C Ver 2.0",
 "source": {
  "title": "PAX2C, PX2FCA0, and PX2FCA1 Modbus Register Tables",
  "doc_number": "LP0905F",
  "revision_date": "2017-02-27",
  "url": "https://cdn.logic-control.com/docs/red-lion/Datasheets/PAX2CHZVR%20Modbus%20Register%20Table.pdf",
  "unofficial": true,
  "pages": "p. 1 (example query, frequently used registers 1-31), p. 2 (32-73), p. 19 (serial settings 1701-1710)"
 },
 "notes": [
  "Red Lion's site hosts only the older Ver 1.5 table (PAX2C8H8V, marked reference only); this file uses the unaltered Ver 2.0 table (LP0905F) from a distributor's file host.",
  "Registers can be read as holding (4x) or input (3x) registers; they are listed as holding registers.",
  "Values marked 1 = 1 display unit are the displayed digits without the decimal point; apply the controller's decimal point setting yourself.",
  "The only 32-bit value listed (segment time remaining) is printed as a Hi word register followed by a Lo word register, so it is ABCD.",
  "Factory serial settings: Modbus ASCII (type 2), 38400 baud, 8 data bits, no parity, address 247. Stop bits are not given in the table.",
  "Serial setting changes (1701-1709) take effect only after writing 1 to register 1710, and the master must then switch to the new settings.",
  "Do not power the unit down while parameters are being written; the table warns this can corrupt non-volatile memory.",
  "Profile definitions (5001 and up), the A/B parameter lists, input/output configuration and FlexCard registers are documented in the table but left out."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 0,
   "documented": "01",
   "name": "Input process value",
   "description": "Display units, decimal point not sent.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1,
   "documented": "02",
   "name": "Maximum value",
   "description": "Highest reading captured. Display units, decimal point not sent.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "03",
   "name": "Minimum value",
   "description": "Lowest reading captured. Display units, decimal point not sent.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 3,
   "documented": "04",
   "name": "Active setpoint value",
   "description": "Limited by setpoint low/high limits.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 4,
   "documented": "05",
   "name": "Setpoint 1 value",
   "description": "Limited by setpoint low/high limits.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 5,
   "documented": "06",
   "name": "Setpoint 2 value",
   "description": "Limited by setpoint low/high limits.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 6,
   "documented": "07",
   "name": "Setpoint deviation",
   "description": "Deviation from the active setpoint, display units.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 7,
   "documented": "08",
   "name": "Output power",
   "description": "Heat/cool output, -100.0 to 100.0 %; writable only in manual mode.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 8,
   "documented": "09",
   "name": "Active proportional band",
   "description": "Display units, decimal point not sent.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 9,
   "documented": "10",
   "name": "Active integral time",
   "description": "0-6500.0 s.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 10,
   "documented": "11",
   "name": "Active derivative time",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 11,
   "documented": "12",
   "name": "Active power filter",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 12,
   "documented": "13",
   "name": "Auto-tune code",
   "description": "Tuning aggressiveness.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Very aggressive",
    "1": "Aggressive",
    "2": "Default",
    "3": "Conservative",
    "4": "Very conservative"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 13,
   "documented": "14",
   "name": "Auto-tune request",
   "description": "Write to start an auto-tune.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "Invoke auto-tune",
    "2": "Auto-tune CS1",
    "3": "Auto-tune CS2",
    "4": "Auto-tune CS3",
    "5": "Auto-tune CS4",
    "6": "Auto-tune CS5",
    "7": "Auto-tune CS6"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 14,
   "documented": "15",
   "name": "Auto-tune phase",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "4": "Last phase of auto-tune"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 15,
   "documented": "16",
   "name": "Auto-tune done",
   "description": "1 after a successful auto-tune since power-up.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 16,
   "documented": "17",
   "name": "Auto-tune fail",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "Auto-tune failed"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 17,
   "documented": "18",
   "name": "Control mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Automatic",
    "1": "Manual"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 18,
   "documented": "19",
   "name": "Setpoint selection",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Setpoint 1",
    "1": "Setpoint 2",
    "2": "Setpoint 3",
    "3": "Setpoint 4",
    "4": "Setpoint 5",
    "5": "Setpoint 6"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 19,
   "documented": "20",
   "name": "Remote/local setpoint selection",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Local",
    "1": "Remote"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 20,
   "documented": "21",
   "name": "PID set selection",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "PID set 1 (primary)",
    "1": "PID set 2 (alternate)",
    "2": "PID set 3",
    "3": "PID set 4",
    "4": "PID set 5",
    "5": "PID set 6",
    "6": "SPSL",
    "7": "Auto"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 21,
   "documented": "22",
   "name": "Disable integral action",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Enabled",
    "1": "Disabled"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 22,
   "documented": "23",
   "name": "Disable setpoint ramping",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Enabled",
    "1": "Disabled"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 23,
   "documented": "24",
   "name": "Setpoint ramping in process",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "In process"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 24,
   "documented": "25",
   "name": "Setpoint ramp rate value",
   "description": "Ramp rate per the configured timebase.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 25,
   "documented": "26",
   "name": "Alarm (1-16) status register",
   "description": "Bit 0 = alarm 1 ... bit 15 = alarm 16.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Alarm 1",
    "1": "Alarm 2",
    "2": "Alarm 3",
    "3": "Alarm 4",
    "4": "Alarm 5",
    "5": "Alarm 6",
    "6": "Alarm 7",
    "7": "Alarm 8",
    "8": "Alarm 9",
    "9": "Alarm 10",
    "10": "Alarm 11",
    "11": "Alarm 12",
    "12": "Alarm 13",
    "13": "Alarm 14",
    "14": "Alarm 15",
    "15": "Alarm 16"
   }
  },
  {
   "table": "holding_register",
   "address": 26,
   "documented": "27",
   "name": "PID stop/run",
   "description": "Stop forces output power to 0 %.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Run PID",
    "1": "Stop PID"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 27,
   "documented": "28",
   "name": "User input status",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "User input 1",
    "1": "User input 2"
   }
  },
  {
   "table": "holding_register",
   "address": 28,
   "documented": "29",
   "name": "Digital output status",
   "description": "Writable only for outputs set to manual in register 30.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Out4",
    "1": "Out3",
    "2": "Out2",
    "3": "Out1"
   }
  },
  {
   "table": "holding_register",
   "address": 29,
   "documented": "30",
   "name": "Output manual mode register (MMR)",
   "description": "Bit set = output in manual mode.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Linear output",
    "1": "DO4",
    "2": "DO3",
    "3": "DO2",
    "4": "DO1"
   }
  },
  {
   "table": "holding_register",
   "address": 30,
   "documented": "31",
   "name": "Alarm reset register",
   "description": "Write 1 to a bit to reset that alarm.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Reset alarm 1",
    "1": "Reset alarm 2",
    "2": "Reset alarm 3",
    "3": "Reset alarm 4",
    "4": "Reset alarm 5",
    "5": "Reset alarm 6",
    "6": "Reset alarm 7",
    "7": "Reset alarm 8",
    "8": "Reset alarm 9",
    "9": "Reset alarm 10",
    "10": "Reset alarm 11",
    "11": "Reset alarm 12",
    "12": "Reset alarm 13",
    "13": "Reset alarm 14",
    "14": "Reset alarm 15",
    "15": "Reset alarm 16"
   }
  },
  {
   "table": "holding_register",
   "address": 31,
   "documented": "32",
   "name": "Analog output register (AOR)",
   "description": "0-4095; used only when linear output is in manual (MMR bit 0).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 32,
   "documented": "33",
   "name": "Active alarm 1 value",
   "description": "Active list (A or B). Display units, decimal point not sent.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 33,
   "documented": "34",
   "name": "Active alarm 2 value",
   "description": "Active list (A or B). Display units, decimal point not sent.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 34,
   "documented": "35",
   "name": "Active alarm 3 value",
   "description": "Active list (A or B). Display units, decimal point not sent.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 35,
   "documented": "36",
   "name": "Active alarm 4 value",
   "description": "Active list (A or B). Display units, decimal point not sent.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 36,
   "documented": "37",
   "name": "Active alarm 5 value",
   "description": "Active list (A or B). Display units, decimal point not sent.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 37,
   "documented": "38",
   "name": "Active alarm 6 value",
   "description": "Active list (A or B). Display units, decimal point not sent.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 38,
   "documented": "39",
   "name": "Active alarm 7 value",
   "description": "Active list (A or B). Display units, decimal point not sent.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 39,
   "documented": "40",
   "name": "Active alarm 8 value",
   "description": "Active list (A or B). Display units, decimal point not sent.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40,
   "documented": "41",
   "name": "Active alarm 9 value",
   "description": "Active list (A or B). Display units, decimal point not sent.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 41,
   "documented": "42",
   "name": "Active alarm 10 value",
   "description": "Active list (A or B). Display units, decimal point not sent.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 42,
   "documented": "43",
   "name": "Active alarm 11 value",
   "description": "Active list (A or B). Display units, decimal point not sent.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 43,
   "documented": "44",
   "name": "Active alarm 12 value",
   "description": "Active list (A or B). Display units, decimal point not sent.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 44,
   "documented": "45",
   "name": "Active alarm 13 value",
   "description": "Active list (A or B). Display units, decimal point not sent.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 45,
   "documented": "46",
   "name": "Active alarm 14 value",
   "description": "Active list (A or B). Display units, decimal point not sent.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 46,
   "documented": "47",
   "name": "Active alarm 15 value",
   "description": "Active list (A or B). Display units, decimal point not sent.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 47,
   "documented": "48",
   "name": "Active alarm 16 value",
   "description": "Active list (A or B). Display units, decimal point not sent.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 64,
   "documented": "65",
   "name": "Remote SP value",
   "description": "Display units, decimal point not sent.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 65,
   "documented": "66",
   "name": "Profile operating status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Profile control off",
    "1": "End profile",
    "2": "Pause",
    "3": "Error delay (status only)",
    "4": "Run/resume/start",
    "5": "Advance profile segment"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 66,
   "documented": "67",
   "name": "Active profile",
   "description": "0 = stop, 1-16 = profile.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 67,
   "documented": "68",
   "name": "Active segment",
   "description": "0 = stop, 1-20 = segment.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 68,
   "documented": "69",
   "name": "Profile segment type",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Ramp",
    "1": "Hold"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 69,
   "documented": "70",
   "name": "Active profile cycle count remaining",
   "description": "0 = continuous cycling.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 70,
   "documented": "71-72",
   "name": "Active profile segment time remaining",
   "description": "Hi word at 71, Lo word at 72.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 72,
   "documented": "73",
   "name": "Profile event status",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Event 1",
    "1": "Event 2",
    "2": "Event 3",
    "3": "Event 4"
   }
  },
  {
   "table": "holding_register",
   "address": 1700,
   "documented": "1701",
   "name": "USB mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Configuration",
    "1": "Serial"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1701,
   "documented": "1702",
   "name": "Comms type",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "RLC protocol (ASCII)",
    "1": "Modbus RTU",
    "2": "Modbus ASCII"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1702,
   "documented": "1703",
   "name": "Baud rate",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "1200",
    "1": "2400",
    "2": "4800",
    "3": "9600",
    "4": "19200",
    "5": "38400"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1703,
   "documented": "1704",
   "name": "Data bits",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "7 bits",
    "1": "8 bits"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1704,
   "documented": "1705",
   "name": "Parity",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "None",
    "1": "Even",
    "2": "Odd"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1705,
   "documented": "1706",
   "name": "Modbus unit address",
   "description": "Modbus 1-247.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1706,
   "documented": "1707",
   "name": "Transmit delay",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.001,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1709,
   "documented": "1710",
   "name": "Load serial settings",
   "description": "Write 1 to apply changes made in 1701-1709.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  }
 ],
 "integration": {
  "summary": "Read registers 1-8 in one request (wire 0-7) for process value, min/max, setpoints, deviation and output power. Write setpoint 1 at wire 4 and switch auto/manual at wire 17.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 0,
    "why": "Process value"
   },
   {
    "table": "holding_register",
    "address": 3,
    "why": "Active setpoint"
   },
   {
    "table": "holding_register",
    "address": 4,
    "why": "Setpoint 1 (write)"
   },
   {
    "table": "holding_register",
    "address": 7,
    "why": "Output power"
   },
   {
    "table": "holding_register",
    "address": 17,
    "why": "Auto/manual control mode"
   },
   {
    "table": "holding_register",
    "address": 25,
    "why": "Alarm status bits"
   }
  ],
  "enable": "Set the comms type register (1702) to Modbus RTU or ASCII, set baud, data bits, parity and address in 1703-1706, then write 1 to 1710 to load the new settings.",
  "watchdog": null,
  "quirks": [
   "Factory comms type is Modbus ASCII, not RTU.",
   "Display-unit values carry no decimal point."
  ],
  "setup": [
   "Default address 247, 38400 baud, 8 data bits, no parity.",
   "Write 1 to register 1710 after changing serial registers."
  ],
  "gotchas": [
   "Output power can only be written in manual mode.",
   "Digital outputs can only be forced through register 29 when their MMR bit (register 30) is set."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/red-lion/pax2c",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}