 "manufacturer": "Red Lion",
 "manufacturer_slug": "red-lion",
 "model": "PAX2D counter / rate panel meter (Modbus)",
 "model_slug": "pax2d",
 "short_model": "PAX2D",
 "aliases": [
  "PAX2D",
  "PAX2 D",
  "Red Lion PAX2D counter"
 ],
 "equipment_type": "Sensor (counter / rate panel meter)",
 "applies_to": "PAX2D dual counter / rate meter, per register table LP0930A (4/11/13).",
 "summary": "The PAX2D is a counter and rate meter with three counters, three rate channels, up to four setpoint outputs and an optional linear output card. Its serial port runs Modbus RTU or Modbus ASCII. This map covers the frequently used block (counts, rates, min/max, setpoints, scale factors, count loads, manual output control) and the counter mode, decimal point and scaling settings.",
 "transport": [
  "RTU",
  "ASCII"
 ],
 "defaults": {
  "unit_id": 247,
  "baud": 38400,
  "parity": "None",
  "data_bits": 8,
  "stop_bits": null,
  "tcp_port": null
 },
 "addressing": {
  "convention": "Modicon",
  "note": "Registers are listed as 4xxxx holding registers (40001 = first). Request 40001 as address 0."
 },
 "default_word_order": "ABCD",
 "firmware": null,
 "source": {
  "title": "PAX2D Modbus Register Table",
  "doc_number": "LP0930A",
  "revision_date": "2013-04-11",
  "url": "https://cdn.logic-control.com/docs/red-lion/Datasheets/PAX2D%20Modbus%20Register%20Table.pdf",
  "pages": "p. 1 (frequently used), p. 2 (output registers, A/B lists, counter A), p. 3 (counters B and C)",
  "unofficial": true
 },
 "notes": [
  "No direct Red Lion download of this table was found; the link is an unaltered copy of the Red Lion table (LP0930A) on a distributor's file host.",
  "32-bit values are a Hi word register followed by a Lo word register (ABCD); limits such as -999999999 show they are signed.",
  "Counts, rates, setpoints and count loads are the displayed digits without the decimal point (the A/B list section says 1 = 1 in the least significant digit, decimal point disregarded).",
  "Scale factor scaling (1 = 0.00001, decimal point fixed) is printed in the A/B list section for the same parameter and applied here to the active-list copies.",
  "Left out: A/B list copies 40041-40100, rate, user input, setpoint output, display and port settings later in the table (the serial port registers 40482-40490 are described under integration)."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 0,
   "documented": "40001",
   "name": "Counter A value",
   "description": "Display digits without the decimal point; see the decimal point setting.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "40003",
   "name": "Counter B value",
   "description": "Display digits without the decimal point; see the decimal point setting.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 4,
   "documented": "40005",
   "name": "Counter C value",
   "description": "Display digits without the decimal point; see the decimal point setting.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 6,
   "documented": "40007",
   "name": "Rate A value",
   "description": "Display digits without the decimal point; see the decimal point setting.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 8,
   "documented": "40009",
   "name": "Rate B value",
   "description": "Display digits without the decimal point; see the decimal point setting.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 10,
   "documented": "40011",
   "name": "Rate C value",
   "description": "Display digits without the decimal point; see the decimal point setting.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 12,
   "documented": "40013",
   "name": "Maximum (Hi) value",
   "description": "Display digits without the decimal point; see the decimal point setting.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 14,
   "documented": "40015",
   "name": "Minimum (Lo) value",
   "description": "Display digits without the decimal point; see the decimal point setting.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 16,
   "documented": "40017",
   "name": "Setpoint 1 value",
   "description": "Active list (A or B). Display digits without the decimal point; see the decimal point setting.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 18,
   "documented": "40019",
   "name": "Setpoint 2 value",
   "description": "Active list (A or B). Display digits without the decimal point; see the decimal point setting.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 20,
   "documented": "40021",
   "name": "Setpoint 3 value",
   "description": "Active list (A or B). Display digits without the decimal point; see the decimal point setting.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 22,
   "documented": "40023",
   "name": "Setpoint 4 value",
   "description": "Active list (A or B). Display digits without the decimal point; see the decimal point setting.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 24,
   "documented": "40025",
   "name": "Counter A scale factor",
   "description": "Active list (A or B); 1-999999, 100000 = 1.00000.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1e-05,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 26,
   "documented": "40027",
   "name": "Counter B scale factor",
   "description": "Active list (A or B); 1-999999, 100000 = 1.00000.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1e-05,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 28,
   "documented": "40029",
   "name": "Counter C scale factor",
   "description": "Active list (A or B); 1-999999, 100000 = 1.00000.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1e-05,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 30,
   "documented": "40031",
   "name": "Counter A count load",
   "description": "Active list (A or B). Display digits without the decimal point; see the decimal point setting.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 32,
   "documented": "40033",
   "name": "Counter B count load",
   "description": "Active list (A or B). Display digits without the decimal point; see the decimal point setting.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 34,
   "documented": "40035",
   "name": "Counter C count load",
   "description": "Active list (A or B). Display digits without the decimal point; see the decimal point setting.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 36,
   "documented": "40037",
   "name": "Setpoint output register (SOR)",
   "description": "Output states; writable only for outputs in manual (MMR).",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "3": "S1 on",
    "2": "S2 on",
    "1": "S3 on",
    "0": "S4 on"
   }
  },
  {
   "table": "holding_register",
   "address": 37,
   "documented": "40038",
   "name": "Manual mode register (MMR)",
   "description": "1 = manual, 0 = auto.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "4": "S1 manual",
    "3": "S2 manual",
    "2": "S3 manual",
    "1": "S4 manual",
    "0": "Linear output manual"
   }
  },
  {
   "table": "holding_register",
   "address": 38,
   "documented": "40039",
   "name": "Reset output register",
   "description": "Write 1 to reset an output; the bit self-clears.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "3": "Reset S1",
    "2": "Reset S2",
    "1": "Reset S3",
    "0": "Reset S4"
   }
  },
  {
   "table": "holding_register",
   "address": 39,
   "documented": "40040",
   "name": "Analog output register (AOR)",
   "description": "0-4095; used only when MMR bit 0 = 1.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 120,
   "documented": "40121",
   "name": "Counter A operating mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "None",
    "1": "Count",
    "2": "Count up/down",
    "3": "Dual count up/down",
    "4": "Add/Add",
    "5": "Add/Sub",
    "6": "Quad x1",
    "7": "Quad x2",
    "8": "Quad x4",
    "9": "Dual quad x1",
    "10": "Dual quad x2",
    "11": "Count x2",
    "12": "Count up/down x2",
    "13": "Dual count up/down x2"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 121,
   "documented": "40122",
   "name": "Counter A decimal point",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "0",
    "1": "0.0",
    "2": "0.00",
    "3": "0.000",
    "4": "0.0000",
    "5": "0.00000"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 122,
   "documented": "40123",
   "name": "Counter A scale multiplier",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "x1",
    "1": "x0.1",
    "2": "x0.01",
    "3": "x10"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 123,
   "documented": "40124",
   "name": "Counter A reset action",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Reset to zero",
    "1": "Reset to count load"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 124,
   "documented": "40125",
   "name": "Counter A reset at power-up",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 125,
   "documented": "40126",
   "name": "Input A active count edge",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Falling edge",
    "1": "Rising edge"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 130,
   "documented": "40131",
   "name": "Counter B operating mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "None",
    "1": "Batch",
    "2": "Count",
    "3": "Dual count up/down",
    "4": "Dual quad x1",
    "5": "Dual quad x2",
    "6": "Count x2",
    "7": "Dual count up/down x2"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 131,
   "documented": "40132",
   "name": "Counter B decimal point",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "0",
    "1": "0.0",
    "2": "0.00",
    "3": "0.000",
    "4": "0.0000",
    "5": "0.00000"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 132,
   "documented": "40133",
   "name": "Counter B scale multiplier",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "x1",
    "1": "x0.1",
    "2": "x0.01",
    "3": "x10"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 140,
   "documented": "40141",
   "name": "Counter C operating mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "None",
    "1": "Counter A",
    "2": "Counter B",
    "3": "Add (A+B)",
    "4": "Subtract (A-B)",
    "5": "Batch",
    "6": "Slave"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 141,
   "documented": "40142",
   "name": "Counter C decimal point",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "0",
    "1": "0.0",
    "2": "0.00",
    "3": "0.000",
    "4": "0.0000",
    "5": "0.00000"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 142,
   "documented": "40143",
   "name": "Counter C scale multiplier",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "x1",
    "1": "x0.1",
    "2": "x0.01",
    "3": "x10"
   },
   "bits": null
  }
 ],
 "integration": {
  "summary": "Read 40001-40016 in one request for counts, rates and min/max, then apply the decimal point settings. Write setpoints as two registers, high word first; take manual control of outputs through the MMR and SOR.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 0,
    "why": "Counter A value"
   },
   {
    "table": "holding_register",
    "address": 6,
    "why": "Rate A value"
   },
   {
    "table": "holding_register",
    "address": 16,
    "why": "Setpoint 1"
   },
   {
    "table": "holding_register",
    "address": 36,
    "why": "Setpoint output states"
   },
   {
    "table": "holding_register",
    "address": 121,
    "why": "Counter A decimal point"
   }
  ],
  "enable": "Set the serial Type register (40482) to 1 for Modbus RTU or 2 for Modbus ASCII. The factory setting is 2 (Modbus ASCII), so change it for an RTU master. Port settings 40481-40487 only take effect after writing 1 to Load Serial Settings (40490).",
  "watchdog": null,
  "quirks": [
   "Values carry no decimal point; scale them with the decimal point registers.",
   "The Slave ID block (41001+) reports a maximum of 64 registers per read or write."
  ],
  "setup": [
   "Factory settings: Modbus ASCII, 38400 baud, 8 data bits, no parity, address 247 (Modbus range 1-247).",
   "Baud (40483), data bits (40484), parity (40485), address (40486) and transmit delay (40487, 1 = 1 ms) are registers; write 1 to 40490 to apply them, then switch the master to the new settings."
  ],
  "gotchas": [
   "Counter values are writable; a write overwrites the count.",
   "Out of the box the port speaks Modbus ASCII, not RTU."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/red-lion/pax2d",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}