 "manufacturer": "Red Lion",
 "manufacturer_slug": "red-lion",
 "model": "PAXI counter / rate panel meter (Modbus)",
 "model_slug": "paxi",
 "short_model": "PAXI",
 "aliases": [
  "PAXI",
  "PAX I",
  "Red Lion PAXI counter"
 ],
 "equipment_type": "Sensor (counter / rate panel meter)",
 "applies_to": "PAXI counter/rate meters with a Modbus serial card, per register table LP0897A (revised 7/10/12).",
 "summary": "The PAXI is a counter and rate indicator with three counters (A, B, C), a rate channel, up to four setpoint outputs and an optional linear output card. Its serial port can run Modbus RTU or Modbus ASCII; this map covers the frequently used block (counts, rate, min/max, scale factors, count loads, setpoints, manual output control) plus counter A and rate settings.",
 "transport": [
  "RTU",
  "ASCII"
 ],
 "defaults": {
  "unit_id": 247,
  "baud": 38400,
  "parity": "None",
  "data_bits": 8,
  "stop_bits": null,
  "tcp_port": null
 },
 "addressing": {
  "convention": "Modicon",
  "note": "Registers are listed as 4xxxx holding registers (40001 = first). Request 40001 as address 0."
 },
 "default_word_order": "ABCD",
 "firmware": null,
 "source": {
  "title": "PAXI Modbus Register Table",
  "doc_number": "LP0897A",
  "revision_date": "2012-07-10",
  "url": "https://cdn.logic-control.com/docs/red-lion/Datasheets/PAXI%20Modbus%20Register%20Table.pdf",
  "pages": "p. 1 (frequently used, manual mode, A/B lists), p. 2 (counter A settings), p. 3-4 (lock-outs, rate settings)",
  "unofficial": true
 },
 "notes": [
  "No direct Red Lion download of this table was found; the link is an unaltered copy of the Red Lion table (LP0897A) on a distributor's file host.",
  "32-bit values are listed as a Hi word register followed by a Lo word register, so high word first (ABCD). Limits such as -99999999 show they are signed.",
  "'1 = 1 display unit' means the integer is the displayed value without its decimal point; apply the counter or rate decimal point setting yourself.",
  "Scale factor scaling (1 = 0.00001) is printed in the A/B list section (40051+) for the same parameter and applied here to the active-list copies at 40013-40018.",
  "Left out: A/B list copies 40051-40090, counter B/C settings, user input and function key actions, display lock-outs, linearizer points and setpoint output settings (40221+)."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 0,
   "documented": "40001",
   "name": "Counter A value",
   "description": "In display units without the decimal point (see the decimal point setting).",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "40003",
   "name": "Counter B value",
   "description": "In display units without the decimal point (see the decimal point setting).",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 4,
   "documented": "40005",
   "name": "Counter C value",
   "description": "In display units without the decimal point (see the decimal point setting).",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 6,
   "documented": "40007",
   "name": "Rate value",
   "description": "In display units without the decimal point (see the decimal point setting).",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 8,
   "documented": "40009",
   "name": "Minimum (Lo) value",
   "description": "In display units without the decimal point (see the decimal point setting).",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 10,
   "documented": "40011",
   "name": "Maximum (Hi) value",
   "description": "In display units without the decimal point (see the decimal point setting).",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 12,
   "documented": "40013",
   "name": "Counter A scale factor",
   "description": "Active list (A or B); 1-999999, factory 100000 = 1.00000.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1e-05,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 14,
   "documented": "40015",
   "name": "Counter B scale factor",
   "description": "Active list (A or B); 1-999999, factory 100000 = 1.00000.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1e-05,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 16,
   "documented": "40017",
   "name": "Counter C scale factor",
   "description": "Active list (A or B); 1-999999, factory 100000 = 1.00000.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1e-05,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 18,
   "documented": "40019",
   "name": "Counter A count load",
   "description": "Active list (A or B); display units without the decimal point.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 20,
   "documented": "40021",
   "name": "Counter B count load",
   "description": "Active list (A or B); display units without the decimal point.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 22,
   "documented": "40023",
   "name": "Counter C count load",
   "description": "Active list (A or B); display units without the decimal point.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 24,
   "documented": "40025",
   "name": "Setpoint 1 value",
   "description": "Active list (A or B); display units without the decimal point.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 26,
   "documented": "40027",
   "name": "Setpoint 2 value",
   "description": "Active list (A or B); display units without the decimal point.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 28,
   "documented": "40029",
   "name": "Setpoint 3 value",
   "description": "Active list (A or B); display units without the decimal point.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 30,
   "documented": "40031",
   "name": "Setpoint 4 value",
   "description": "Active list (A or B); display units without the decimal point.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 35,
   "documented": "40036",
   "name": "Manual mode register (MMR)",
   "description": "1 = manual, 0 = auto for each output.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "4": "S1 manual",
    "3": "S2 manual",
    "2": "S3 manual",
    "1": "S4 manual",
    "0": "Linear output manual"
   }
  },
  {
   "table": "holding_register",
   "address": 36,
   "documented": "40037",
   "name": "Analog output register (AOR)",
   "description": "0-4095; drives the linear output card only when MMR bit 0 = 1.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 37,
   "documented": "40038",
   "name": "Setpoint output register (SOR)",
   "description": "Output states; writable only for outputs in manual (MMR).",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "3": "S1 on",
    "2": "S2 on",
    "1": "S3 on",
    "0": "S4 on"
   }
  },
  {
   "table": "holding_register",
   "address": 38,
   "documented": "40039",
   "name": "Reset output register",
   "description": "Write 1 to reset an output; the bit self-clears.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "3": "Reset S1",
    "2": "Reset S2",
    "1": "Reset S3",
    "0": "Reset S4"
   }
  },
  {
   "table": "holding_register",
   "address": 100,
   "documented": "40101",
   "name": "Counter A operating mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "None",
    "1": "Count",
    "2": "Count up/down",
    "3": "Dual count up/down",
    "4": "Quad x1",
    "5": "Quad x2",
    "6": "Quad x4",
    "7": "Dual quad x1",
    "8": "Dual quad x2",
    "9": "Count x2",
    "10": "Count up/down x2",
    "11": "Dual count up/down x2"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 101,
   "documented": "40102",
   "name": "Counter A reset action",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Reset to zero",
    "1": "Reset to count load value"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 102,
   "documented": "40103",
   "name": "Counter A decimal point",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "0",
    "1": "0.0",
    "2": "0.00",
    "3": "0.000",
    "4": "0.0000",
    "5": "0.00000"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 103,
   "documented": "40104",
   "name": "Counter A scale multiplier",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "x1",
    "1": "x0.1",
    "2": "x0.01"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 104,
   "documented": "40105",
   "name": "Counter A reset at power-up",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 105,
   "documented": "40106",
   "name": "Prescaler output enable",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 106,
   "documented": "40107",
   "name": "Prescaler scale value",
   "description": "1-10000.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.0001,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 158,
   "documented": "40159",
   "name": "Security code",
   "description": "0-999.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 160,
   "documented": "40161",
   "name": "Rate assignment",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Rate A",
    "2": "Rate B"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 161,
   "documented": "40162",
   "name": "Rate low update time",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 162,
   "documented": "40163",
   "name": "Rate high update time",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 163,
   "documented": "40164",
   "name": "Rate decimal point",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "0",
    "1": "0.0",
    "2": "0.00",
    "3": "0.000",
    "4": "0.0000"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 167,
   "documented": "40168",
   "name": "Max (Hi) capture delay",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 168,
   "documented": "40169",
   "name": "Min (Lo) capture delay",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null
  }
 ],
 "integration": {
  "summary": "Read 40001-40012 in one request for counts, rate and min/max (high word first). Change setpoints or count loads by writing both words of 40019-40032; take direct control of outputs by setting MMR bits and then writing the SOR.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 0,
    "why": "Counter A value"
   },
   {
    "table": "holding_register",
    "address": 6,
    "why": "Rate value"
   },
   {
    "table": "holding_register",
    "address": 24,
    "why": "Setpoint 1"
   },
   {
    "table": "holding_register",
    "address": 37,
    "why": "Setpoint output states"
   },
   {
    "table": "holding_register",
    "address": 102,
    "why": "Counter A decimal point"
   },
   {
    "table": "holding_register",
    "address": 163,
    "why": "Rate decimal point"
   }
  ],
  "enable": "Set Serial Protocol (40301) to 1 for Modbus RTU or 2 for Modbus ASCII (factory setting is RTU). Serial settings 40301-40306 only take effect after writing 1 to Load Serial Settings (40309).",
  "watchdog": null,
  "quirks": [
   "Values carry no decimal point; read the decimal point registers to scale them.",
   "The Slave ID block (41001+) reports a maximum of 64 registers per read or write."
  ],
  "setup": [
   "Factory settings: Modbus RTU, 38400 baud, 8 data bits, no parity, address 247 (Modbus range 1-247).",
   "Baud (40302), data bits (40303), parity (40304), address (40305) and transmit delay (40306, 1 = 1 ms) are registers in this table; write 1 to 40309 to apply them, then switch the master to the new settings."
  ],
  "gotchas": [
   "Counter values are read/write: a write overwrites the count."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/red-lion/paxi",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}