 "manufacturer": "Rishabh Instruments",
 "manufacturer_slug": "rishabh-instruments",
 "model": "RISH Delta Power NX multifunction power meter",
 "model_slug": "rish-delta-power-nx",
 "short_model": "Delta Power NX",
 "aliases": [
  "RISH Delta Power NX",
  "Delta Power NX",
  "RISH Delta Power"
 ],
 "equipment_type": "Power meter",
 "applies_to": "Rishabh RISH Delta Power NX programmable panel meters with RS-485 Modbus RTU, per operating manual AMAN-00IM-0117 Rev. E.",
 "summary": "The RISH Delta Power NX is a 96 x 96 mm multifunction meter that measures voltage, current, power, power factor, frequency and demand (no energy counters) on 1-phase and 3-phase networks, with an RS-485 Modbus RTU port. Every value is an IEEE 754 float in two registers: measurements are input registers (FC04) from 30001, mirrored as holding registers at 40001+, and setup parameters sit at 46003-46085. This map covers the measured values, demands, run/on hours and the setup block.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": 1,
  "baud": 9600,
  "parity": "None",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "Modicon",
  "note": "The manual prints 3X/4X register numbers. Wire address = number - 30001 (FC04) or - 40001 (FC03/FC16): the Volts 3 example (30005) starts at 00 04 and the system-type example (46003) starts at 17 72 (6002)."
 },
 "default_word_order": "ABCD",
 "firmware": null,
 "source": {
  "title": "Operating Manual RISH Delta Power NX",
  "doc_number": "AMAN-00IM-0117 Rev. E",
  "revision_date": "2024-02",
  "url": "https://rishabh.co.in/uploads/product/rish-delta-power-nx-72/RISH_Delta_POWER_NX__Manual_REV_E.pdf",
  "pages": "pp. 25-29 (data format, examples, Table 3 3X registers), pp. 31-36 (4X examples, Table 4, explanations, RS485 set-up code)"
 },
 "notes": [
  "The data-format table states IEEE 754 floats, most significant byte first; the Volts 3 example returns 43 5B 41 21 (219.25 V), so ABCD is the default. 46049 can switch to reversed order.",
  "Every 3X value can also be read with FC03 at the number plus 10000; only the 3X copies are listed.",
  "The register table has no unit column, so units are left blank.",
  "Left out: the min/max history from 31301 and the user-assignable registers. Demand time (46015) is printed as seconds in Table 4 and minutes in the explanation, so no unit is given.",
  "Up to 40 parameters (80 registers) per read request."
 ],
 "registers": [
  {
   "table": "input_register",
   "address": 0,
   "documented": "30001",
   "name": "V1",
   "description": "L1 voltage (L-N on 4-wire, L-L on 3-wire).",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 2,
   "documented": "30003",
   "name": "V2",
   "description": "Not on 1P2W.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 4,
   "documented": "30005",
   "name": "V3",
   "description": "3P4W and 3P3W only.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 6,
   "documented": "30007",
   "name": "I1",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 8,
   "documented": "30009",
   "name": "I2",
   "description": "Not on 1P2W.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 10,
   "documented": "30011",
   "name": "I3",
   "description": "3P4W and 3P3W only.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 12,
   "documented": "30013",
   "name": "W1",
   "description": "Not on 3P3W.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 14,
   "documented": "30015",
   "name": "W2",
   "description": "3P4W and 1P3W only.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 16,
   "documented": "30017",
   "name": "W3",
   "description": "3P4W only.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 18,
   "documented": "30019",
   "name": "VA1",
   "description": "Not on 3P3W.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 20,
   "documented": "30021",
   "name": "VA2",
   "description": "3P4W and 1P3W only.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 22,
   "documented": "30023",
   "name": "VA3",
   "description": "3P4W only.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 24,
   "documented": "30025",
   "name": "VAR1",
   "description": "Not on 3P3W.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 26,
   "documented": "30027",
   "name": "VAR2",
   "description": "3P4W and 1P3W only.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 28,
   "documented": "30029",
   "name": "VAR3",
   "description": "3P4W only.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 30,
   "documented": "30031",
   "name": "PF1",
   "description": "Not on 3P3W.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 32,
   "documented": "30033",
   "name": "PF2",
   "description": "3P4W and 1P3W only.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 34,
   "documented": "30035",
   "name": "PF3",
   "description": "3P4W only.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 36,
   "documented": "30037",
   "name": "Angle1",
   "description": "Not on 3P3W.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 38,
   "documented": "30039",
   "name": "Angle2",
   "description": "3P4W and 1P3W only.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 40,
   "documented": "30041",
   "name": "Angle3",
   "description": "3P4W only.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 42,
   "documented": "30043",
   "name": "Volt average",
   "description": "Not on 1P2W.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 44,
   "documented": "30045",
   "name": "Volt sum",
   "description": "Not on 1P2W.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 46,
   "documented": "30047",
   "name": "Current average",
   "description": "Not on 1P2W.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 48,
   "documented": "30049",
   "name": "Current sum",
   "description": "Not on 1P2W.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 50,
   "documented": "30051",
   "name": "Watt average",
   "description": "Not on 1P2W.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 52,
   "documented": "30053",
   "name": "Watt sum",
   "description": "Not on 1P2W.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 54,
   "documented": "30055",
   "name": "VA average",
   "description": "Not on 1P2W.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 56,
   "documented": "30057",
   "name": "VA sum",
   "description": "Not on 1P2W.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 58,
   "documented": "30059",
   "name": "VAR average",
   "description": "Not on 1P2W.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 60,
   "documented": "30061",
   "name": "VAR sum",
   "description": "Not on 1P2W.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 62,
   "documented": "30063",
   "name": "PF average",
   "description": "Not on 1P2W.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 64,
   "documented": "30065",
   "name": "PF sum",
   "description": "3P4W and 1P3W only.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 66,
   "documented": "30067",
   "name": "Phase angle average",
   "description": "Not on 1P2W.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 68,
   "documented": "30069",
   "name": "Phase angle sum",
   "description": "Not on 1P2W.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 70,
   "documented": "30071",
   "name": "System frequency",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 82,
   "documented": "30083",
   "name": "kW import demand",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 84,
   "documented": "30085",
   "name": "Max kW import demand",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 86,
   "documented": "30087",
   "name": "kW export demand",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 88,
   "documented": "30089",
   "name": "Max kW export demand",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 98,
   "documented": "30099",
   "name": "KVA demand",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 100,
   "documented": "30101",
   "name": "Max KVA demand",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 102,
   "documented": "30103",
   "name": "Current demand",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 104,
   "documented": "30105",
   "name": "Max current demand",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 136,
   "documented": "30137",
   "name": "System voltage max",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 138,
   "documented": "30139",
   "name": "System voltage min",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 140,
   "documented": "30141",
   "name": "System RPM",
   "description": "Generator speed from 46039 poles.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 142,
   "documented": "30143",
   "name": "Impulse rate",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 144,
   "documented": "30145",
   "name": "System current max",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 146,
   "documented": "30147",
   "name": "System current min",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 200,
   "documented": "30201",
   "name": "V12",
   "description": "3P4W and 1P3W only.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 202,
   "documented": "30203",
   "name": "V23",
   "description": "3P4W only.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 204,
   "documented": "30205",
   "name": "V31",
   "description": "3P4W only.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 224,
   "documented": "30225",
   "name": "Neutral current",
   "description": "3P4W only.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 226,
   "documented": "30227",
   "name": "Run hour",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 228,
   "documented": "30229",
   "name": "On hour",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 230,
   "documented": "30231",
   "name": "Number of interrupts",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 262,
   "documented": "30263",
   "name": "Relay 1 status",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 500,
   "documented": "30501",
   "name": "System kW import demand",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 502,
   "documented": "30503",
   "name": "System kW export demand",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 508,
   "documented": "30509",
   "name": "System KVA demand",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 510,
   "documented": "30511",
   "name": "System current demand",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 512,
   "documented": "30513",
   "name": "System kW import max demand",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 514,
   "documented": "30515",
   "name": "System kW export max demand",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 520,
   "documented": "30521",
   "name": "System KVA max demand",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 522,
   "documented": "30523",
   "name": "System current max demand",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 6002,
   "documented": "46003",
   "name": "System type",
   "description": "Default 3.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "1": "1-phase 2-wire",
    "2": "3-phase 3-wire",
    "3": "3-phase 4-wire",
    "4": "1-phase 3-wire"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 6004,
   "documented": "46005",
   "name": "PT primary",
   "description": "100 V to 1200 kV L-L; default 415.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 6006,
   "documented": "46007",
   "name": "CT primary",
   "description": "1-9999; default 5.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 6008,
   "documented": "46009",
   "name": "PT secondary",
   "description": "100-500 V L-L; default 415.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 6010,
   "documented": "46011",
   "name": "CT secondary",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "1": "1 A",
    "5": "5 A"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 6014,
   "documented": "46015",
   "name": "Demand time",
   "description": "Demand period 5-60; default 8.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 6030,
   "documented": "46031",
   "name": "Reset parameters",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "W",
   "values": {
    "1": "Lo (min)",
    "2": "Hi (max)",
    "3": "Demand",
    "4": "Run hour",
    "5": "On hour",
    "6": "No. of interrupts",
    "7": "Reset all"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 6032,
   "documented": "46033",
   "name": "Password",
   "description": "0000-9999; reads 0 when locked, 1 when unlocked.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 6034,
   "documented": "46035",
   "name": "Factory reset",
   "description": "Write 5555 to restore factory defaults.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 6038,
   "documented": "46039",
   "name": "No. of poles",
   "description": "Generator poles for RPM, 2-40 even.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 6040,
   "documented": "46041",
   "name": "Autoscroll",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 6042,
   "documented": "46043",
   "name": "Noise cutoff",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "0 mA",
    "30": "30 mA"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 6044,
   "documented": "46045",
   "name": "Comsetup (RS485 set-up code)",
   "description": "Default 8 (9600 bps, no parity, 1 stop).",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "4": "4800 bps, no parity, 1 stop",
    "5": "4800 bps, no parity, 2 stop",
    "6": "4800 bps, even, 1 stop",
    "7": "4800 bps, odd, 1 stop",
    "8": "9600 bps, no parity, 1 stop",
    "9": "9600 bps, no parity, 2 stop",
    "10": "9600 bps, even, 1 stop",
    "11": "9600 bps, odd, 1 stop",
    "12": "19200 bps, no parity, 1 stop",
    "13": "19200 bps, no parity, 2 stop",
    "14": "19200 bps, even, 1 stop",
    "15": "19200 bps, odd, 1 stop",
    "16": "38400 bps, no parity, 1 stop",
    "17": "38400 bps, no parity, 2 stop",
    "18": "38400 bps, even, 1 stop",
    "19": "38400 bps, odd, 1 stop",
    "20": "57600 bps, no parity, 1 stop",
    "21": "57600 bps, no parity, 2 stop",
    "22": "57600 bps, even, 1 stop",
    "23": "57600 bps, odd, 1 stop"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 6046,
   "documented": "46047",
   "name": "Modbus address",
   "description": "1-247; default 1.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 6048,
   "documented": "46049",
   "name": "Register order / word order",
   "description": "Write 2141.0 in the wanted order to switch normal/reversed float word order.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 6054,
   "documented": "46055",
   "name": "Relay 1 output select",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "None",
    "2": "Limit output"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 6056,
   "documented": "46057",
   "name": "Limit 1 parameter select",
   "description": "Parameter number per manual Table 2.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 6058,
   "documented": "46059",
   "name": "Limit 1 configuration",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Hi-alarm, energized relay",
    "1": "Hi-alarm, de-energized relay",
    "2": "Lo-alarm, energized relay",
    "3": "Lo-alarm, de-energized relay"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 6060,
   "documented": "46061",
   "name": "Limit 1 trip point",
   "description": "Percent; values per manual Table 2.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 6062,
   "documented": "46063",
   "name": "Limit 1 hysteresis",
   "description": "0.5-50 %; default 50.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 6064,
   "documented": "46065",
   "name": "Limit 1 on delay",
   "description": "1-10.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 6066,
   "documented": "46067",
   "name": "Limit 1 off delay",
   "description": "1-10.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 6084,
   "documented": "46085",
   "name": "Version no.",
   "description": "Firmware version.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  }
 ],
 "integration": {
  "summary": "Read 30001-30072 (and the demand block 30083-30106) with FC04 and decode each register pair as a big-endian float. Settings are floats at 46003+ written with FC16.",
  "minimum_registers": [
   {
    "table": "input_register",
    "address": 0,
    "why": "Voltage L1"
   },
   {
    "table": "input_register",
    "address": 6,
    "why": "Current L1"
   },
   {
    "table": "input_register",
    "address": 52,
    "why": "Total active power"
   },
   {
    "table": "input_register",
    "address": 62,
    "why": "Average power factor"
   },
   {
    "table": "input_register",
    "address": 70,
    "why": "Frequency"
   }
  ],
  "enable": "Set the Modbus address (46047, default 1) and Comsetup code (46045, default 8 = 9600 8N1) from the front panel or over Modbus.",
  "watchdog": null,
  "quirks": [
   "Setup values are floats too: system type 3 reads back as 40 40 00 00.",
   "Reading or writing half a float returns exception 02.",
   "If a password is set, write it to 46033 before changing setup registers."
  ],
  "setup": [
   "Comsetup (46045) packs baud 4800-57600, parity and stop bits into one code; see the value list."
  ],
  "gotchas": [
   "Per-phase PF and line-to-line voltages are only valid for the wiring types noted in each description."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/rishabh-instruments/rish-delta-power-nx",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}