{
 "manufacturer": "Rishabh Instruments",
 "manufacturer_slug": "rishabh-instruments",
 "model": "RISH ED11XX / EC11XX / ER11XX single-phase DIN-rail energy meters",
 "model_slug": "rish-ed-ec-er11xx",
 "short_model": "EC11XX",
 "aliases": [
  "RISH ED11X1",
  "RISH EC11X1",
  "RISH ER11X1",
  "ED1111",
  "EC1111",
  "ER1111",
  "RISH ED11XX",
  "RISH EC11XX",
  "RISH ER11XX"
 ],
 "equipment_type": "Energy meter",
 "applies_to": "Rishabh RISH ED11XX (direct), EC11XX (CT) and ER11XX (RJ12 CT) single-phase DIN-rail meters in their Modbus (x1) versions, per operating manual DMAN-00IM-1071 Rev. M.",
 "summary": "Single-phase DIN-rail energy meters from Rishabh in direct-connected (ED), CT-connected (EC) and RJ12 CT (ER) versions; the Modbus variants have an RS-485 port speaking Modbus RTU. Every measured value is an IEEE 754 float in two registers, readable as input registers from 30001 or as holding registers at the same offset from 40001. This map covers voltage, current, power, PF, frequency, demands, total/tariff/partial energies and the main setup registers.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": 1,
  "baud": 9600,
  "parity": "None",
  "data_bits": 8,
  "stop_bits": null,
  "tcp_port": null
 },
 "addressing": {
  "convention": "Modicon",
  "note": "Table 4 prints 3X and 4X numbers next to the hex start address (30001 = 00 00, 30071 = 00 46). Wire address = number - 30001 (FC04) or - 40001 (FC03); every row was checked against the printed hex and parameter number. The setup example reads 46007 at 17 76."
 },
 "default_word_order": "ABCD",
 "firmware": null,
 "source": {
  "title": "Operating Manual RISH ED11XX / EC11XX / ER11XX DIN rail mount Single Phase AC Energy Meter",
  "doc_number": "DMAN-00IM-1071 Rev. M",
  "revision_date": "09/26",
  "url": "https://rishabh.co.in/uploads/product/rish-ed11x1-66/RISH%20ED_EC_ER_11XX_Operating_Manual%20-%20REV_M.pdf",
  "pages": "pp. 16-21 (protocol, data format, examples, Table 4), pp. 24-32 (4X examples, Tables 6-8)"
 },
 "notes": [
  "The data-format table states IEEE 754 floats, most significant byte first. The voltage example returns 43 66 00 00 (230 V) and the current example 40 A0 00 00 (5 A), so word order is ABCD.",
  "Every 3X value is also a 4X holding register at the same offset (30001 -> 40001); only the 3X copies are listed.",
  "Left out: parameter 42 (printed with the same name as 43), parameter 108 'Partial Active Import Energy' (unit printed as Wh, unlike its kWh siblings), the 'long energy' Table 5 (30513-30655, format not described) and the user-assignable registers (31025-31051).",
  "Units are as printed (Volts -> V, Amp -> A). Energy overflow counts increase each time the matching energy passes 99999.999.",
  "Up to 40 parameters per read request.",
  "Table 4 prints 'Total Apparent Energy' (and its overflow count) twice in each block: at 30123/30125 and again at 30139/30141 (same for T1 30159/30161 vs 30175/30177, T2 30195/30197 vs 30211/30213, partial 30231/30233 vs 30247/30249). The first copy of each pair is left out because its real meaning is unclear; the second copy sits where the long-energy Table 5 puts total apparent energy.",
  "Default stop bits are not settled: the front-panel section gives nonE1 (no parity, 1 stop) but Table 6 prints Comsetup default 9 (9600, no parity, 2 stop). Both agree on 9600 baud and no parity. Some setup rows also differ between ED and EC/ER models; only the clearly described rows are listed."
 ],
 "registers": [
  {
   "table": "input_register",
   "address": 0,
   "documented": "30001",
   "name": "Voltage",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 6,
   "documented": "30007",
   "name": "Current",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 12,
   "documented": "30013",
   "name": "Active Power",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 18,
   "documented": "30019",
   "name": "Apparent Power",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 24,
   "documented": "30025",
   "name": "Reactive Power",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "VAr",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 30,
   "documented": "30031",
   "name": "Power Factor",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 70,
   "documented": "30071",
   "name": "Frequency",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 72,
   "documented": "30073",
   "name": "W Import Demand",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 74,
   "documented": "30075",
   "name": "W Import Max Demand",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 76,
   "documented": "30077",
   "name": "W Export Demand",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 78,
   "documented": "30079",
   "name": "W Exp. Max Demand",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 80,
   "documented": "30081",
   "name": "var Imp.\\ Ind Demand",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "VAr",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 82,
   "documented": "30083",
   "name": "var Imp.\\ Ind Max Demand",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "VAr",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 86,
   "documented": "30087",
   "name": "var Exp. \\ Cap Max Demand",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "VAr",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 88,
   "documented": "30089",
   "name": "va Imp. Demand",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 90,
   "documented": "30091",
   "name": "va Imp. Max Demand",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 92,
   "documented": "30093",
   "name": "va Exp. Demand",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 94,
   "documented": "30095",
   "name": "va Exp. Max Demand",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 96,
   "documented": "30097",
   "name": "Current Imp. Demand",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 98,
   "documented": "30099",
   "name": "Current Imp Max. Demand",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 106,
   "documented": "30107",
   "name": "Active Import Energy Overflow Count",
   "description": "Roll-overs of the matching energy register.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 108,
   "documented": "30109",
   "name": "Active Import Energy",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 110,
   "documented": "30111",
   "name": "Active Export Energy Overflow Count",
   "description": "Roll-overs of the matching energy register.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 112,
   "documented": "30113",
   "name": "Active Export Energy",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 114,
   "documented": "30115",
   "name": "Reactive Import Energy Overflow Count",
   "description": "Roll-overs of the matching energy register.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 116,
   "documented": "30117",
   "name": "Reactive Import Energy",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "kVArh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 118,
   "documented": "30119",
   "name": "Reactive Export Energy Overflow Count",
   "description": "Roll-overs of the matching energy register.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 120,
   "documented": "30121",
   "name": "Reactive Export Energy",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "kVArh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 130,
   "documented": "30131",
   "name": "Total Active Energy Overflow Count",
   "description": "Roll-overs of the matching energy register.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 132,
   "documented": "30133",
   "name": "Total Active Energy",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 134,
   "documented": "30135",
   "name": "Total Reactive Energy Overflow Count",
   "description": "Roll-overs of the matching energy register.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 136,
   "documented": "30137",
   "name": "Total Reactive Energy",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "kVArh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 138,
   "documented": "30139",
   "name": "Total Apparent Energy Overflow Count",
   "description": "Roll-overs of the matching energy register.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 140,
   "documented": "30141",
   "name": "Total Apparent Energy",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "kVAh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 142,
   "documented": "30143",
   "name": "T1 Active Import Energy Overflow Count",
   "description": "Roll-overs of the matching energy register.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 144,
   "documented": "30145",
   "name": "T1 Active Import Energy",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 146,
   "documented": "30147",
   "name": "T1 Active Export Energy Overflow Count",
   "description": "Roll-overs of the matching energy register.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 148,
   "documented": "30149",
   "name": "T1 Active Export Energy",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 150,
   "documented": "30151",
   "name": "T1 Reactive Import Energy Overflow Count",
   "description": "Roll-overs of the matching energy register.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 152,
   "documented": "30153",
   "name": "T1 Reactive Import Energy",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "kVArh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 154,
   "documented": "30155",
   "name": "T1 Reactive Export Energy Overflow Count",
   "description": "Roll-overs of the matching energy register.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 156,
   "documented": "30157",
   "name": "T1 Reactive Export Energy",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "kVArh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 166,
   "documented": "30167",
   "name": "T1 Total Active Energy Overflow Count",
   "description": "Roll-overs of the matching energy register.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 168,
   "documented": "30169",
   "name": "T1 Total Active Energy",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 170,
   "documented": "30171",
   "name": "T1 Total Reactive Energy Overflow Count",
   "description": "Roll-overs of the matching energy register.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 172,
   "documented": "30173",
   "name": "T1 Total Reactive Energy",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "kVArh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 174,
   "documented": "30175",
   "name": "T1 Total Apparent Energy Overflow Count",
   "description": "Roll-overs of the matching energy register.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 176,
   "documented": "30177",
   "name": "T1 Total Apparent Energy",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "kVAh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 178,
   "documented": "30179",
   "name": "T2 Active Import Energy Overflow Count",
   "description": "Roll-overs of the matching energy register.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 180,
   "documented": "30181",
   "name": "T2 Active Import Energy",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 182,
   "documented": "30183",
   "name": "T2 Active Export Energy Overflow Count",
   "description": "Roll-overs of the matching energy register.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 184,
   "documented": "30185",
   "name": "T2 Active Export Energy",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 186,
   "documented": "30187",
   "name": "T2 Reactive Import Energy Overflow Count",
   "description": "Roll-overs of the matching energy register.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 188,
   "documented": "30189",
   "name": "T2 Reactive Import Energy",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "kVArh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 190,
   "documented": "30191",
   "name": "T2 Reactive Export Energy Overflow Count",
   "description": "Roll-overs of the matching energy register.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 192,
   "documented": "30193",
   "name": "T2 Reactive Export Energy",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "kVArh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 202,
   "documented": "30203",
   "name": "T2 Total Active Energy Overflow Count",
   "description": "Roll-overs of the matching energy register.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 204,
   "documented": "30205",
   "name": "T2 Total Active Energy",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 206,
   "documented": "30207",
   "name": "T2 Total Reactive Energy Overflow Count",
   "description": "Roll-overs of the matching energy register.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 208,
   "documented": "30209",
   "name": "T2 Total Reactive Energy",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "kVArh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 210,
   "documented": "30211",
   "name": "T2 Total Apparent Energy Overflow Count",
   "description": "Roll-overs of the matching energy register.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 212,
   "documented": "30213",
   "name": "T2 Total Apparent Energy",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "kVAh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 214,
   "documented": "30215",
   "name": "Partial Active Import Energy Overflow Count",
   "description": "Roll-overs of the matching energy register.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 218,
   "documented": "30219",
   "name": "Partial Active Export Energy Overflow Count",
   "description": "Roll-overs of the matching energy register.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 220,
   "documented": "30221",
   "name": "Partial Active Export Energy",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 222,
   "documented": "30223",
   "name": "Partial Reactive Import Energy Overflow Count",
   "description": "Roll-overs of the matching energy register.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 224,
   "documented": "30225",
   "name": "Partial Reactive Import Energy",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "kVArh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 226,
   "documented": "30227",
   "name": "Partial Reactive Export Energy Overflow Count",
   "description": "Roll-overs of the matching energy register.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 228,
   "documented": "30229",
   "name": "Partial Reactive Export Energy",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "kVArh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 238,
   "documented": "30239",
   "name": "Partial Total Active Energy Overflow Count",
   "description": "Roll-overs of the matching energy register.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 240,
   "documented": "30241",
   "name": "Partial Total Active Energy",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 242,
   "documented": "30243",
   "name": "Partial Total Reactive Energy Overflow Count",
   "description": "Roll-overs of the matching energy register.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 244,
   "documented": "30245",
   "name": "Partial Total Reactive Energy",
   "description": "Unit misprinted in the manual; reactive energy.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 246,
   "documented": "30247",
   "name": "Partial Total Apparent Energy Overflow Count",
   "description": "Roll-overs of the matching energy register.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 248,
   "documented": "30249",
   "name": "Partial Total Apparent Energy",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "kVAh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 254,
   "documented": "30255",
   "name": "No of Interrupts",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 256,
   "documented": "30257",
   "name": "Impulse Rate",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 260,
   "documented": "30261",
   "name": "Tariff Status",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 262,
   "documented": "30263",
   "name": "Current Direction",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Current in the marked direction",
    "1": "Current reversed"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 6002,
   "documented": "46003",
   "name": "Demand integration time",
   "description": "Demand period in minutes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "5": "5 min",
    "10": "10 min",
    "15": "15 min",
    "30": "30 min"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 6006,
   "documented": "46007",
   "name": "Total energy counter formula",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Import only",
    "2": "Export only",
    "3": "Import + export"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 6008,
   "documented": "46009",
   "name": "Import/export reactive energy formula",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Import/export (Q1+Q2 / Q3+Q4)",
    "2": "Inductive/capacitive (Q1+Q3 / Q2+Q4)"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 6024,
   "documented": "46025",
   "name": "Modbus address",
   "description": "1-247.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 6026,
   "documented": "46027",
   "name": "Comsetup",
   "description": "Baud, parity and stop bits in one code.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "2400 bps, no parity, 1 stop",
    "1": "2400 bps, no parity, 2 stop",
    "2": "2400 bps, even, 1 stop",
    "3": "2400 bps, odd, 1 stop",
    "4": "4800 bps, no parity, 1 stop",
    "5": "4800 bps, no parity, 2 stop",
    "6": "4800 bps, even, 1 stop",
    "7": "4800 bps, odd, 1 stop",
    "8": "9600 bps, no parity, 1 stop",
    "9": "9600 bps, no parity, 2 stop",
    "10": "9600 bps, even, 1 stop",
    "11": "9600 bps, odd, 1 stop",
    "12": "19200 bps, no parity, 1 stop",
    "13": "19200 bps, no parity, 2 stop",
    "14": "19200 bps, even, 1 stop",
    "15": "19200 bps, odd, 1 stop",
    "16": "38400 bps, no parity, 1 stop",
    "17": "38400 bps, no parity, 2 stop",
    "18": "38400 bps, even, 1 stop",
    "19": "38400 bps, odd, 1 stop"
   },
   "bits": null
  }
 ],
 "integration": {
  "summary": "Read 30001-30038 for instantaneous values and 30107-30142 for energies with FC04 (or FC03 at 40001+) and decode each register pair as a big-endian float.",
  "minimum_registers": [
   {
    "table": "input_register",
    "address": 0,
    "why": "Voltage"
   },
   {
    "table": "input_register",
    "address": 6,
    "why": "Current"
   },
   {
    "table": "input_register",
    "address": 12,
    "why": "Active power"
   },
   {
    "table": "input_register",
    "address": 30,
    "why": "Power factor"
   },
   {
    "table": "input_register",
    "address": 70,
    "why": "Frequency"
   },
   {
    "table": "input_register",
    "address": 108,
    "why": "Active import energy (kWh)"
   }
  ],
  "enable": "Only the x1 (Modbus) variants have RS-485. Set address and baud/parity from the front-panel setup (address 001 and 9600 baud, no parity by default; check stop bits, see notes) or via 46025/46027.",
  "watchdog": null,
  "quirks": [
   "Setup values are floats too: total energy formula 1 reads back as 3F 80 00 00.",
   "Reading or writing half a float returns exception 02."
  ],
  "setup": [
   "Comsetup (46027) codes 0-19 pack baud 2400-38400, parity and stop bits."
  ],
  "gotchas": [
   "Changing CT settings on EC/ER models locks after a countdown (46021); plan CT changes during commissioning."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/rishabh-instruments/rish-ed-ec-er11xx",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}
