 "manufacturer": "RKC Instrument",
 "manufacturer_slug": "rkc-instrument",
 "model": "SRV module type controller, TIO temperature control module (Modbus RTU)",
 "model_slug": "srv-tio",
 "short_model": "SRV TIO",
 "aliases": [
  "SRV",
  "SRV TIO module",
  "RKC SRV"
 ],
 "equipment_type": "Sensor (modular temperature controller)",
 "applies_to": "RKC SRV two-channel temperature control (TIO) modules, basic and extension type, with Modbus selected.",
 "summary": "The SRV is a DIN-rail modular controller whose TIO modules each run two heat or heat/cool PID loops; extension modules share the bus of a basic module. With DIP switch 6 set to Modbus, each module answers Modbus RTU on RS-485 with channel 1 data at 0000H and channel 2 data at 1000H. This map covers measured values, events, setpoints, PID, manual output, module DI/DO and the key input setup items.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": 1,
  "baud": 38400,
  "parity": "None",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "hex 0-based",
  "note": "The data map prints each register in hex and decimal; the value is the address sent on the wire. The manual's read example asks for 0000H-0002H, so 0000H is a real register (CH1 measured value)."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "SRV Communication Instruction Manual (Module Type Controller)",
  "doc_number": "IMS01P01-E7",
  "revision_date": null,
  "url": "https://flw.com/rkc/pdf/ims01p01e7.pdf",
  "pages": "Settings pp. 14-15; Modbus frames pp. 45-48; decimal handling pp. 49-51; data map pp. 52-62",
  "unofficial": true
 },
 "notes": [
  "RKC's own download center does not offer this manual publicly; the linked copy is the unaltered RKC manual hosted by a US distributor (a distributor stamp on the cover only).",
  "All registers are 16-bit; FFFFH is -1. Values are sent without a decimal point: PV/SV-type items follow the input range (temperature ranges with or without one decimal, or the 0873H setting for voltage/current inputs); other items have the fixed decimals shown (scale).",
  "Items marked (module) exist once per module (channel 1 address only); all others repeat for channel 2 at +1000H.",
  "DI/DO function settings, input error actions, AT bias, differential gaps and event action bits are left out.",
  "Initial-setting items (0870H onward) can only be written in initial setting mode (0860H = 1), which needs control stopped (0030H = 0)."
 ],
 "integration": {
  "summary": "Set DIP switch 6 ON (Modbus) and the rotary address, then read 0000H-0006H for CH1 PV, event state, outputs and SV monitor (1000H onward for CH2). Write the setpoint to 0010H/1010H and start control with 0030H = 1.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 0,
    "why": "CH1 measured value"
   },
   {
    "table": "holding_register",
    "address": 1,
    "why": "CH1 event state"
   },
   {
    "table": "holding_register",
    "address": 2,
    "why": "CH1 heat-side output"
   },
   {
    "table": "holding_register",
    "address": 16,
    "why": "CH1 set value"
   },
   {
    "table": "holding_register",
    "address": 48,
    "why": "Control RUN/STOP"
   },
   {
    "table": "holding_register",
    "address": 4096,
    "why": "CH2 measured value"
   },
   {
    "table": "holding_register",
    "address": 4112,
    "why": "CH2 set value"
   }
  ],
  "enable": "The protocol is set when ordering but can be changed with DIP switch 6 (ON = Modbus). Speed is set by DIP switches 1-2, data/parity by 3-5; changes apply after power-up or a RUN/STOP change.",
  "watchdog": null,
  "quirks": [
   "The Modbus slave address is the rotary switch setting plus 1 (switch 00 = slave 1).",
   "Each module (slave address) carries at most two channels.",
   "With a data error part-way through a multi-write, the values before the error still take effect."
  ],
  "setup": [
   "Factory DIP settings for Modbus: 38400 bps, 8 data bits, no parity, 1 stop bit (fixed). Speeds 2400-38400 bps.",
   "Give the basic TIO module the lowest address when extension modules share its bus. DIP switches 7 and 8 stay OFF."
  ],
  "gotchas": [
   "Wait 30 bit times after a response before the next request.",
   "Do not write to addresses not in the data map; items for functions that are not fitted return no error response."
  ]
 },
 "registers": [
  {
   "table": "holding_register",
   "address": 0,
   "documented": "0000",
   "name": "Measured value (PV) (CH1)",
   "description": "Raw integer; decimals follow the input range (0873H for voltage/current inputs).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1,
   "documented": "0001",
   "name": "Comprehensive event state (CH1)",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Burnout",
    "1": "Event 1",
    "2": "Event 2",
    "3": "Heater break alarm",
    "4": "Control loop break alarm (LBA)"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "0002",
   "name": "Heat-side manipulated output value (CH1)",
   "description": "-5.0 to +105.0 %.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3,
   "documented": "0003",
   "name": "Set value monitor (CH1)",
   "description": "Raw integer; decimals follow the input range (0873H for voltage/current inputs).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4,
   "documented": "0004",
   "name": "Error code (module)",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Memory backup error",
    "2": "Internal communication error",
    "3": "Adjustment data error",
    "4": "Input error",
    "5": "Current transformer input error",
    "6": "Temperature compensation error"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5,
   "documented": "0005",
   "name": "Cool-side manipulated output value (CH1)",
   "description": "-5.0 to +105.0 %.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6,
   "documented": "0006",
   "name": "Current transformer input measured value (CH1)",
   "description": "0.0 to 30.0 A or 0.0 to 100.0 A depending on CT.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8,
   "documented": "0008",
   "name": "Burnout state (CH1)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9,
   "documented": "0009",
   "name": "Event 1 state (CH1)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10,
   "documented": "000A",
   "name": "Event 2 state (CH1)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11,
   "documented": "000B",
   "name": "Heater break alarm (HBA) state (CH1)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "OFF",
    "1": "Heater break",
    "2": "Relay welding"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 12,
   "documented": "000C",
   "name": "Control loop break alarm (LBA) state (CH1)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 13,
   "documented": "000D",
   "name": "Temperature rise completion state (CH1)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Not complete",
    "1": "Temperature rise complete"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 15,
   "documented": "000F",
   "name": "Operation mode (CH1)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Unused",
    "1": "Monitor 1",
    "2": "Monitor 2",
    "3": "Control"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16,
   "documented": "0010",
   "name": "Set value (SV) (CH1)",
   "description": "Raw integer; decimals follow the input range (0873H for voltage/current inputs).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 17,
   "documented": "0011",
   "name": "Heat-side proportional band (CH1)",
   "description": "0 = ON/OFF action. Decimal places follow the input range; V/I inputs are in % of span.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 18,
   "documented": "0012",
   "name": "Integral time (CH1)",
   "description": "1 to 3600 s.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 19,
   "documented": "0013",
   "name": "Derivative time (CH1)",
   "description": "0 to 3600 s; 0 = PI action.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 20,
   "documented": "0014",
   "name": "Control response parameters (CH1)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Slow",
    "1": "Medium",
    "2": "Fast"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 21,
   "documented": "0015",
   "name": "PV bias (CH1)",
   "description": "Raw integer; decimals follow the input range (0873H for voltage/current inputs).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 22,
   "documented": "0016",
   "name": "Event 1 set value (CH1)",
   "description": "Raw integer; decimals follow the input range (0873H for voltage/current inputs).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 23,
   "documented": "0017",
   "name": "Event 2 set value (CH1)",
   "description": "Raw integer; decimals follow the input range (0873H for voltage/current inputs).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 28,
   "documented": "001C",
   "name": "Cool-side proportional band (CH1)",
   "description": "Decimal places follow the input range; V/I inputs are in % of span.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 30,
   "documented": "001E",
   "name": "Overlap/Deadband (CH1)",
   "description": "Raw integer; decimals follow the input range (0873H for voltage/current inputs).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 31,
   "documented": "001F",
   "name": "Setting change rate limiter (CH1)",
   "description": "Input span per minute, 0 = off; decimal places follow the input range.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 32,
   "documented": "0020",
   "name": "PID/AT transfer (CH1)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "PID control",
    "1": "Autotuning (AT)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 33,
   "documented": "0021",
   "name": "Auto/Manual transfer (CH1)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Auto",
    "1": "Manual"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 34,
   "documented": "0022",
   "name": "Manual output value (CH1)",
   "description": "-5.0 to +105.0 %.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 35,
   "documented": "0023",
   "name": "Output limiter (high) (CH1)",
   "description": "Output limiter (low) to 105.0 %.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 36,
   "documented": "0024",
   "name": "Output limiter (low) (CH1)",
   "description": "-5.0 % to output limiter (high).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 37,
   "documented": "0025",
   "name": "Heat-side proportional cycle time (CH1)",
   "description": "1 to 100 s.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 38,
   "documented": "0026",
   "name": "Cool-side proportional cycle time (CH1)",
   "description": "1 to 100 s.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 39,
   "documented": "0027",
   "name": "Digital filter (CH1)",
   "description": "0 to 100 s; 0 = off.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 40,
   "documented": "0028",
   "name": "Heater break alarm (HBA) set value (CH1)",
   "description": "0.0 to 30.0 A or 0.0 to 100.0 A.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "A",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 48,
   "documented": "0030",
   "name": "Control RUN/STOP transfer (module)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Control STOP",
    "1": "Control RUN"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 53,
   "documented": "0035",
   "name": "Manipulated output value at input error (CH1)",
   "description": "-105.0 to +105.0 %.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 62,
   "documented": "003E",
   "name": "DI state (module)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Contact open (OFF)",
    "1": "Contact closed (ON)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 65,
   "documented": "0041",
   "name": "DO state (module)",
   "description": "Writable only when DO1 and DO2 settings are 0.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "DO1 open, DO2 open",
    "1": "DO1 closed, DO2 open",
    "2": "DO1 open, DO2 closed",
    "3": "DO1 closed, DO2 closed"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 66,
   "documented": "0042",
   "name": "Event interlock release (module)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Normal state",
    "1": "Execute interlock release"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 67,
   "documented": "0043",
   "name": "Temperature rise completion zone (CH1)",
   "description": "0 = unused. Raw integer; decimals follow the input range (0873H for voltage/current inputs).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 68,
   "documented": "0044",
   "name": "Temperature rise completion soak time (CH1)",
   "description": "0 to 360 min.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2137,
   "documented": "0859",
   "name": "Control loop break alarm (LBA) use selection (CH1)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Unused",
    "1": "Used"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2138,
   "documented": "085A",
   "name": "Control loop break alarm (LBA) time (CH1)",
   "description": "1 to 7200 s.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2144,
   "documented": "0860",
   "name": "Initial setting mode (module)",
   "description": "Stop control before entering initial setting mode.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Normal setting mode",
    "1": "Initial setting mode"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2160,
   "documented": "0870",
   "name": "Input range number (CH1)",
   "description": "Input type code 0-37, e.g. 0 = type K, 23 = Pt100, 37 = 4-20 mA.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2161,
   "documented": "0871",
   "name": "Input scale high limit (CH1)",
   "description": "Voltage/current input only. Raw integer; decimals follow the input range (0873H for voltage/current inputs).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2162,
   "documented": "0872",
   "name": "Input scale low limit (CH1)",
   "description": "Voltage/current input only. Raw integer; decimals follow the input range (0873H for voltage/current inputs).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2163,
   "documented": "0873",
   "name": "Input range decimal point position (CH1)",
   "description": "Voltage/current input only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No decimal place",
    "1": "One decimal place",
    "2": "Two decimal places",
    "3": "Three decimal places"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2164,
   "documented": "0874",
   "name": "Temperature unit selection (CH1)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "°C",
    "1": "°F"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2165,
   "documented": "0875",
   "name": "Control type selection (CH1)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Heat control, direct action",
    "1": "Heat control, reverse action",
    "2": "Heat/cool control, water cooling",
    "3": "Heat/cool control, air cooling"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2170,
   "documented": "087A",
   "name": "Event 1 type selection (CH1)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Not provided",
    "1": "Process high",
    "2": "Process low",
    "3": "Deviation high",
    "4": "Deviation low",
    "5": "Deviation high/low",
    "6": "Band"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2171,
   "documented": "087B",
   "name": "Event 2 type selection (CH1)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Not provided",
    "1": "Process high",
    "2": "Process low",
    "3": "Deviation high",
    "4": "Deviation low",
    "5": "Deviation high/low",
    "6": "Band"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4096,
   "documented": "1000",
   "name": "Measured value (PV) (CH2)",
   "description": "Raw integer; decimals follow the input range (0873H for voltage/current inputs).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4097,
   "documented": "1001",
   "name": "Comprehensive event state (CH2)",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Burnout",
    "1": "Event 1",
    "2": "Event 2",
    "3": "Heater break alarm",
    "4": "Control loop break alarm (LBA)"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4098,
   "documented": "1002",
   "name": "Heat-side manipulated output value (CH2)",
   "description": "-5.0 to +105.0 %.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4099,
   "documented": "1003",
   "name": "Set value monitor (CH2)",
   "description": "Raw integer; decimals follow the input range (0873H for voltage/current inputs).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4101,
   "documented": "1005",
   "name": "Cool-side manipulated output value (CH2)",
   "description": "-5.0 to +105.0 %.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4102,
   "documented": "1006",
   "name": "Current transformer input measured value (CH2)",
   "description": "0.0 to 30.0 A or 0.0 to 100.0 A depending on CT.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4104,
   "documented": "1008",
   "name": "Burnout state (CH2)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4105,
   "documented": "1009",
   "name": "Event 1 state (CH2)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4106,
   "documented": "100A",
   "name": "Event 2 state (CH2)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4107,
   "documented": "100B",
   "name": "Heater break alarm (HBA) state (CH2)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "OFF",
    "1": "Heater break",
    "2": "Relay welding"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4108,
   "documented": "100C",
   "name": "Control loop break alarm (LBA) state (CH2)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4109,
   "documented": "100D",
   "name": "Temperature rise completion state (CH2)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Not complete",
    "1": "Temperature rise complete"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4111,
   "documented": "100F",
   "name": "Operation mode (CH2)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Unused",
    "1": "Monitor 1",
    "2": "Monitor 2",
    "3": "Control"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4112,
   "documented": "1010",
   "name": "Set value (SV) (CH2)",
   "description": "Raw integer; decimals follow the input range (0873H for voltage/current inputs).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4113,
   "documented": "1011",
   "name": "Heat-side proportional band (CH2)",
   "description": "0 = ON/OFF action. Decimal places follow the input range; V/I inputs are in % of span.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4114,
   "documented": "1012",
   "name": "Integral time (CH2)",
   "description": "1 to 3600 s.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4115,
   "documented": "1013",
   "name": "Derivative time (CH2)",
   "description": "0 to 3600 s; 0 = PI action.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4116,
   "documented": "1014",
   "name": "Control response parameters (CH2)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Slow",
    "1": "Medium",
    "2": "Fast"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4117,
   "documented": "1015",
   "name": "PV bias (CH2)",
   "description": "Raw integer; decimals follow the input range (0873H for voltage/current inputs).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4118,
   "documented": "1016",
   "name": "Event 1 set value (CH2)",
   "description": "Raw integer; decimals follow the input range (0873H for voltage/current inputs).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4119,
   "documented": "1017",
   "name": "Event 2 set value (CH2)",
   "description": "Raw integer; decimals follow the input range (0873H for voltage/current inputs).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4124,
   "documented": "101C",
   "name": "Cool-side proportional band (CH2)",
   "description": "Decimal places follow the input range; V/I inputs are in % of span.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4126,
   "documented": "101E",
   "name": "Overlap/Deadband (CH2)",
   "description": "Raw integer; decimals follow the input range (0873H for voltage/current inputs).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4127,
   "documented": "101F",
   "name": "Setting change rate limiter (CH2)",
   "description": "Input span per minute, 0 = off; decimal places follow the input range.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4128,
   "documented": "1020",
   "name": "PID/AT transfer (CH2)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "PID control",
    "1": "Autotuning (AT)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4129,
   "documented": "1021",
   "name": "Auto/Manual transfer (CH2)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Auto",
    "1": "Manual"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4130,
   "documented": "1022",
   "name": "Manual output value (CH2)",
   "description": "-5.0 to +105.0 %.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4131,
   "documented": "1023",
   "name": "Output limiter (high) (CH2)",
   "description": "Output limiter (low) to 105.0 %.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4132,
   "documented": "1024",
   "name": "Output limiter (low) (CH2)",
   "description": "-5.0 % to output limiter (high).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4133,
   "documented": "1025",
   "name": "Heat-side proportional cycle time (CH2)",
   "description": "1 to 100 s.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4134,
   "documented": "1026",
   "name": "Cool-side proportional cycle time (CH2)",
   "description": "1 to 100 s.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4135,
   "documented": "1027",
   "name": "Digital filter (CH2)",
   "description": "0 to 100 s; 0 = off.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4136,
   "documented": "1028",
   "name": "Heater break alarm (HBA) set value (CH2)",
   "description": "0.0 to 30.0 A or 0.0 to 100.0 A.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "A",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4149,
   "documented": "1035",
   "name": "Manipulated output value at input error (CH2)",
   "description": "-105.0 to +105.0 %.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4163,
   "documented": "1043",
   "name": "Temperature rise completion zone (CH2)",
   "description": "0 = unused. Raw integer; decimals follow the input range (0873H for voltage/current inputs).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4164,
   "documented": "1044",
   "name": "Temperature rise completion soak time (CH2)",
   "description": "0 to 360 min.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6233,
   "documented": "1859",
   "name": "Control loop break alarm (LBA) use selection (CH2)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Unused",
    "1": "Used"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6234,
   "documented": "185A",
   "name": "Control loop break alarm (LBA) time (CH2)",
   "description": "1 to 7200 s.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6256,
   "documented": "1870",
   "name": "Input range number (CH2)",
   "description": "Input type code 0-37, e.g. 0 = type K, 23 = Pt100, 37 = 4-20 mA.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6257,
   "documented": "1871",
   "name": "Input scale high limit (CH2)",
   "description": "Voltage/current input only. Raw integer; decimals follow the input range (0873H for voltage/current inputs).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6258,
   "documented": "1872",
   "name": "Input scale low limit (CH2)",
   "description": "Voltage/current input only. Raw integer; decimals follow the input range (0873H for voltage/current inputs).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6259,
   "documented": "1873",
   "name": "Input range decimal point position (CH2)",
   "description": "Voltage/current input only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No decimal place",
    "1": "One decimal place",
    "2": "Two decimal places",
    "3": "Three decimal places"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6260,
   "documented": "1874",
   "name": "Temperature unit selection (CH2)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "°C",
    "1": "°F"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6261,
   "documented": "1875",
   "name": "Control type selection (CH2)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Heat control, direct action",
    "1": "Heat control, reverse action",
    "2": "Heat/cool control, water cooling",
    "3": "Heat/cool control, air cooling"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6266,
   "documented": "187A",
   "name": "Event 1 type selection (CH2)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Not provided",
    "1": "Process high",
    "2": "Process low",
    "3": "Deviation high",
    "4": "Deviation low",
    "5": "Deviation high/low",
    "6": "Band"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6267,
   "documented": "187B",
   "name": "Event 2 type selection (CH2)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Not provided",
    "1": "Process high",
    "2": "Process low",
    "3": "Deviation high",
    "4": "Deviation low",
    "5": "Deviation high/low",
    "6": "Band"
   },
   "bits": null,
   "offset": 0
  }
 ],
 "page": "https://easymodbus.com/modbus-register-maps/rkc-instrument/srv-tio",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}