 "manufacturer": "RKC Instrument",
 "manufacturer_slug": "rkc-instrument",
 "model": "SRX module type controller, TIO temperature control module (Modbus RTU)",
 "model_slug": "srx-tio",
 "short_model": "SRX TIO",
 "aliases": [
  "SRX",
  "X-TIO-A",
  "X-TIO-B",
  "SRX TIO module",
  "RKC SRX"
 ],
 "equipment_type": "Sensor (modular temperature controller)",
 "applies_to": "RKC SRX two-channel temperature control (TIO) modules, basic type X-TIO-A and extension type X-TIO-B, with Modbus selected; DI and DO module maps are not included.",
 "summary": "The SRX is a DIN-rail modular controller: each TIO module runs two PID loops, and extension, DI and DO modules share the bus of a basic TIO module. With DIP switch 6 set to Modbus, each TIO module answers Modbus RTU on RS-485 with channel 1 data at 0000H and channel 2 data at 1000H. This map covers measured values, events, setpoints, PID, manual output, program run control and the key input setup items.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": 1,
  "baud": 9600,
  "parity": "None",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "hex 0-based",
  "note": "The data map prints each register in hex and decimal; the value is the address sent on the wire. The manual's read example asks for 0000H-0002H and gets back PV, event state and output, so 0000H is a real register (CH1 measured value)."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "SRX Communication Instruction Manual (Module Type Controller)",
  "doc_number": "IMS01N01-E5",
  "revision_date": null,
  "url": "https://www.flw.com/rkc/pdf/ims01n01e5.pdf",
  "pages": "Settings pp. 15-16; Modbus frames pp. 70-73; decimal handling pp. 74-77; TIO data map pp. 78-89",
  "unofficial": true
 },
 "notes": [
  "RKC's own download center does not offer this manual publicly; the linked copy is the unaltered RKC manual hosted by a US distributor (a distributor stamp on the cover only).",
  "All registers are 16-bit; FFFFH is -1. Values are sent without a decimal point: PV/SV-type items follow the input range decimal point (0873H), integral/derivative time follows 085CH, others have the fixed decimals shown (scale).",
  "Items marked (module) exist once per module (channel 1 address only); all others repeat for channel 2 at +1000H.",
  "The decimal-handling list prints Manual output value twice and does not name the manipulated output (0002H); its scale 0.1 rests on its printed -5.0 to +105.0 % range.",
  "Level PID tables, program pattern/segment tables, digital input assignments and the DI/DO module maps are left out.",
  "Writing input range, scale, decimal point, unit or event type can take up to 200 ms to answer; stop control (0030H) before changing initial-setting items."
 ],
 "integration": {
  "summary": "Set DIP switch 6 ON (Modbus) and the rotary address, then read 0000H-0003H for CH1 PV, event state, output and SV monitor (1000H-1003H for CH2). Write the setpoint to 0010H/1010H and start control with 0030H = 1.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 0,
    "why": "CH1 measured value"
   },
   {
    "table": "holding_register",
    "address": 1,
    "why": "CH1 event state"
   },
   {
    "table": "holding_register",
    "address": 2,
    "why": "CH1 output"
   },
   {
    "table": "holding_register",
    "address": 16,
    "why": "CH1 set value"
   },
   {
    "table": "holding_register",
    "address": 48,
    "why": "Control RUN/STOP"
   },
   {
    "table": "holding_register",
    "address": 4096,
    "why": "CH2 measured value"
   },
   {
    "table": "holding_register",
    "address": 4112,
    "why": "CH2 set value"
   }
  ],
  "enable": "Modbus is chosen with DIP switch 6 (ON = Modbus; factory setting is RKC protocol). Speed is set by DIP switches 1-2, data/parity by 3-5. Power off before changing switches.",
  "watchdog": null,
  "quirks": [
   "The Modbus slave address is the rotary switch setting plus 1 (switch 00 = slave 1).",
   "Each module (slave address) carries at most two channels.",
   "Writes to undefined addresses are not allowed; with a data error part-way through a multi-write, the values before the error still take effect."
  ],
  "setup": [
   "Factory DIP settings: 9600 bps, 8 data bits, no parity, 1 stop bit (fixed). Speeds 2400-38400 bps.",
   "Give the basic TIO module the lowest address when extension modules share its bus; terminate the internal data bus at both ends (DIP 8)."
  ],
  "gotchas": [
   "Wait 30 bit times after a response before the next request; the response takes up to 5 ms (200 ms after initial-setting writes).",
   "Some items read 0 when the matching function is not fitted or not in use (no error is returned)."
  ]
 },
 "registers": [
  {
   "table": "holding_register",
   "address": 0,
   "documented": "0000",
   "name": "Measured value (PV) (CH1)",
   "description": "Raw integer; decimal places follow the input range decimal point setting (0873H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1,
   "documented": "0001",
   "name": "Comprehensive event state (CH1)",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Burnout",
    "1": "Event 1",
    "2": "Event 2",
    "3": "Heater break alarm",
    "4": "Control loop break alarm (LBA)"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "0002",
   "name": "Manipulated output value (CH1)",
   "description": "-5.0 to +105.0 %.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3,
   "documented": "0003",
   "name": "Set value monitor (CH1)",
   "description": "Raw integer; decimal places follow the input range decimal point setting (0873H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4,
   "documented": "0004",
   "name": "Error code (module)",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Memory backup error",
    "2": "Internal communication error",
    "3": "Adjustment data error",
    "4": "Input error",
    "5": "Current transformer input error",
    "6": "Temperature compensation error"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6,
   "documented": "0006",
   "name": "Current transformer input measured value (CH1)",
   "description": "0.0 to 30.0 A or 0.0 to 100.0 A depending on CT.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8,
   "documented": "0008",
   "name": "Burnout state (CH1)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9,
   "documented": "0009",
   "name": "Event 1 state (CH1)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10,
   "documented": "000A",
   "name": "Event 2 state (CH1)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11,
   "documented": "000B",
   "name": "Heater break alarm (HBA) state (CH1)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "OFF",
    "1": "Heater break",
    "2": "Relay welding"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 12,
   "documented": "000C",
   "name": "Control loop break alarm (LBA) state (CH1)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 15,
   "documented": "000F",
   "name": "Operation mode (CH1)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Unused",
    "1": "Monitor 1",
    "2": "Monitor 2",
    "3": "Control"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16,
   "documented": "0010",
   "name": "Set value (SV) (CH1)",
   "description": "Raw integer; decimal places follow the input range decimal point setting (0873H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 17,
   "documented": "0011",
   "name": "Proportional band (CH1)",
   "description": "0 = ON/OFF. Decimals follow the input range (0873H); V/I in % of span.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 18,
   "documented": "0012",
   "name": "Integral time (CH1)",
   "description": "Raw integer; one or two decimal places in seconds per 085CH.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 19,
   "documented": "0013",
   "name": "Derivative time (CH1)",
   "description": "Raw integer; one or two decimal places in seconds per 085CH. 0 = off.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 20,
   "documented": "0014",
   "name": "Control response parameters (CH1)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Slow",
    "1": "Medium",
    "2": "Fast"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 21,
   "documented": "0015",
   "name": "PV bias (CH1)",
   "description": "Raw integer; decimal places follow the input range decimal point setting (0873H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 22,
   "documented": "0016",
   "name": "Event 1 set value (CH1)",
   "description": "Raw integer; decimal places follow the input range decimal point setting (0873H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 23,
   "documented": "0017",
   "name": "Event 2 set value (CH1)",
   "description": "Raw integer; decimal places follow the input range decimal point setting (0873H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 32,
   "documented": "0020",
   "name": "PID/AT transfer (CH1)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "PID control",
    "1": "Autotuning (AT)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 33,
   "documented": "0021",
   "name": "Auto/Manual transfer (CH1)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Auto",
    "1": "Manual"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 34,
   "documented": "0022",
   "name": "Manual output value (CH1)",
   "description": "-5.0 to +105.0 %.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 35,
   "documented": "0023",
   "name": "Output limiter (high) (CH1)",
   "description": "Output limiter (low) to 105.0 %.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 36,
   "documented": "0024",
   "name": "Output limiter (low) (CH1)",
   "description": "-5.0 % to output limiter (high).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 37,
   "documented": "0025",
   "name": "Proportional cycle time (CH1)",
   "description": "0.2 to 50.0 s.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 39,
   "documented": "0027",
   "name": "Digital filter (CH1)",
   "description": "0.00 to 10.00 s.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 40,
   "documented": "0028",
   "name": "Heater break alarm (HBA) set value (CH1)",
   "description": "0.0 to 30.0 A or 0.0 to 100.0 A.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "A",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 48,
   "documented": "0030",
   "name": "Control RUN/STOP transfer (module)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Control STOP",
    "1": "Control RUN"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 53,
   "documented": "0035",
   "name": "Manipulated output value at input error (CH1)",
   "description": "-5.0 to +105.0 %.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 59,
   "documented": "003B",
   "name": "Remote/Local transfer (module)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Local",
    "1": "Remote"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 208,
   "documented": "00D0",
   "name": "Program operation mode selection (CH1)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "RESET",
    "1": "RUN (program control)",
    "2": "FIX (fixed set point control)",
    "3": "MAN (manual control)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 209,
   "documented": "00D1",
   "name": "Execution pattern (CH1)",
   "description": "1 to 16.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 210,
   "documented": "00D2",
   "name": "Execution segment (CH1)",
   "description": "1 to 16.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 212,
   "documented": "00D4",
   "name": "Number of program execution times (CH1)",
   "description": "0 to 9999.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 214,
   "documented": "00D6",
   "name": "Pattern end output state (CH1)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 215,
   "documented": "00D7",
   "name": "End state (CH1)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 216,
   "documented": "00D8",
   "name": "Wait state (CH1)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 217,
   "documented": "00D9",
   "name": "Hold state (CH1)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 218,
   "documented": "00DA",
   "name": "Step action (CH1)",
   "description": "Write 1 to step to the next segment.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No step action",
    "1": "Step action execution"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2137,
   "documented": "0859",
   "name": "Control loop break alarm (LBA) use selection (CH1)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Unused",
    "1": "Used"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2138,
   "documented": "085A",
   "name": "Control loop break alarm (LBA) time (CH1)",
   "description": "1 to 7200 s.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2140,
   "documented": "085C",
   "name": "Integral/derivative time decimal point position (CH1)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Two decimal places",
    "1": "One decimal place"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2160,
   "documented": "0870",
   "name": "Input range number (CH1)",
   "description": "Input type code 0-21, e.g. 0 = K thermocouple, 12 = Pt100, 15 = 4-20 mA.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2161,
   "documented": "0871",
   "name": "Input scale high limit (CH1)",
   "description": "Raw integer; decimal places follow the input range decimal point setting (0873H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2162,
   "documented": "0872",
   "name": "Input scale low limit (CH1)",
   "description": "Raw integer; decimal places follow the input range decimal point setting (0873H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2163,
   "documented": "0873",
   "name": "Input range decimal point position (CH1)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No decimal place",
    "1": "One decimal place",
    "2": "Two decimal places",
    "3": "Three decimal places",
    "4": "Four decimal places"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2164,
   "documented": "0874",
   "name": "Temperature unit selection (CH1)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "°C",
    "1": "°F"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2165,
   "documented": "0875",
   "name": "Control type selection (CH1)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Direct action",
    "1": "Reverse action"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2170,
   "documented": "087A",
   "name": "Event 1 type selection (CH1)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Not provided",
    "1": "Process high",
    "2": "Process low",
    "3": "Deviation high",
    "4": "Deviation low",
    "5": "Deviation high/low",
    "6": "Band"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2171,
   "documented": "087B",
   "name": "Event 2 type selection (CH1)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Not provided",
    "1": "Process high",
    "2": "Process low",
    "3": "Deviation high",
    "4": "Deviation low",
    "5": "Deviation high/low",
    "6": "Band"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4096,
   "documented": "1000",
   "name": "Measured value (PV) (CH2)",
   "description": "Raw integer; decimal places follow the input range decimal point setting (0873H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4097,
   "documented": "1001",
   "name": "Comprehensive event state (CH2)",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Burnout",
    "1": "Event 1",
    "2": "Event 2",
    "3": "Heater break alarm",
    "4": "Control loop break alarm (LBA)"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4098,
   "documented": "1002",
   "name": "Manipulated output value (CH2)",
   "description": "-5.0 to +105.0 %.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4099,
   "documented": "1003",
   "name": "Set value monitor (CH2)",
   "description": "Raw integer; decimal places follow the input range decimal point setting (0873H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4102,
   "documented": "1006",
   "name": "Current transformer input measured value (CH2)",
   "description": "0.0 to 30.0 A or 0.0 to 100.0 A depending on CT.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4104,
   "documented": "1008",
   "name": "Burnout state (CH2)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4105,
   "documented": "1009",
   "name": "Event 1 state (CH2)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4106,
   "documented": "100A",
   "name": "Event 2 state (CH2)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4107,
   "documented": "100B",
   "name": "Heater break alarm (HBA) state (CH2)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "OFF",
    "1": "Heater break",
    "2": "Relay welding"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4108,
   "documented": "100C",
   "name": "Control loop break alarm (LBA) state (CH2)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4111,
   "documented": "100F",
   "name": "Operation mode (CH2)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Unused",
    "1": "Monitor 1",
    "2": "Monitor 2",
    "3": "Control"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4112,
   "documented": "1010",
   "name": "Set value (SV) (CH2)",
   "description": "Raw integer; decimal places follow the input range decimal point setting (0873H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4113,
   "documented": "1011",
   "name": "Proportional band (CH2)",
   "description": "0 = ON/OFF. Decimals follow the input range (0873H); V/I in % of span.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4114,
   "documented": "1012",
   "name": "Integral time (CH2)",
   "description": "Raw integer; one or two decimal places in seconds per 085CH.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4115,
   "documented": "1013",
   "name": "Derivative time (CH2)",
   "description": "Raw integer; one or two decimal places in seconds per 085CH. 0 = off.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4116,
   "documented": "1014",
   "name": "Control response parameters (CH2)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Slow",
    "1": "Medium",
    "2": "Fast"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4117,
   "documented": "1015",
   "name": "PV bias (CH2)",
   "description": "Raw integer; decimal places follow the input range decimal point setting (0873H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4118,
   "documented": "1016",
   "name": "Event 1 set value (CH2)",
   "description": "Raw integer; decimal places follow the input range decimal point setting (0873H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4119,
   "documented": "1017",
   "name": "Event 2 set value (CH2)",
   "description": "Raw integer; decimal places follow the input range decimal point setting (0873H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4128,
   "documented": "1020",
   "name": "PID/AT transfer (CH2)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "PID control",
    "1": "Autotuning (AT)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4129,
   "documented": "1021",
   "name": "Auto/Manual transfer (CH2)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Auto",
    "1": "Manual"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4130,
   "documented": "1022",
   "name": "Manual output value (CH2)",
   "description": "-5.0 to +105.0 %.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4131,
   "documented": "1023",
   "name": "Output limiter (high) (CH2)",
   "description": "Output limiter (low) to 105.0 %.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4132,
   "documented": "1024",
   "name": "Output limiter (low) (CH2)",
   "description": "-5.0 % to output limiter (high).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4133,
   "documented": "1025",
   "name": "Proportional cycle time (CH2)",
   "description": "0.2 to 50.0 s.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4135,
   "documented": "1027",
   "name": "Digital filter (CH2)",
   "description": "0.00 to 10.00 s.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4136,
   "documented": "1028",
   "name": "Heater break alarm (HBA) set value (CH2)",
   "description": "0.0 to 30.0 A or 0.0 to 100.0 A.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "A",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4149,
   "documented": "1035",
   "name": "Manipulated output value at input error (CH2)",
   "description": "-5.0 to +105.0 %.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4304,
   "documented": "10D0",
   "name": "Program operation mode selection (CH2)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "RESET",
    "1": "RUN (program control)",
    "2": "FIX (fixed set point control)",
    "3": "MAN (manual control)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4305,
   "documented": "10D1",
   "name": "Execution pattern (CH2)",
   "description": "1 to 16.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4306,
   "documented": "10D2",
   "name": "Execution segment (CH2)",
   "description": "1 to 16.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4308,
   "documented": "10D4",
   "name": "Number of program execution times (CH2)",
   "description": "0 to 9999.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4310,
   "documented": "10D6",
   "name": "Pattern end output state (CH2)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4311,
   "documented": "10D7",
   "name": "End state (CH2)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4312,
   "documented": "10D8",
   "name": "Wait state (CH2)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4313,
   "documented": "10D9",
   "name": "Hold state (CH2)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4314,
   "documented": "10DA",
   "name": "Step action (CH2)",
   "description": "Write 1 to step to the next segment.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No step action",
    "1": "Step action execution"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6233,
   "documented": "1859",
   "name": "Control loop break alarm (LBA) use selection (CH2)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Unused",
    "1": "Used"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6234,
   "documented": "185A",
   "name": "Control loop break alarm (LBA) time (CH2)",
   "description": "1 to 7200 s.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6236,
   "documented": "185C",
   "name": "Integral/derivative time decimal point position (CH2)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Two decimal places",
    "1": "One decimal place"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6256,
   "documented": "1870",
   "name": "Input range number (CH2)",
   "description": "Input type code 0-21, e.g. 0 = K thermocouple, 12 = Pt100, 15 = 4-20 mA.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6257,
   "documented": "1871",
   "name": "Input scale high limit (CH2)",
   "description": "Raw integer; decimal places follow the input range decimal point setting (0873H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6258,
   "documented": "1872",
   "name": "Input scale low limit (CH2)",
   "description": "Raw integer; decimal places follow the input range decimal point setting (0873H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6259,
   "documented": "1873",
   "name": "Input range decimal point position (CH2)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No decimal place",
    "1": "One decimal place",
    "2": "Two decimal places",
    "3": "Three decimal places",
    "4": "Four decimal places"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6260,
   "documented": "1874",
   "name": "Temperature unit selection (CH2)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "°C",
    "1": "°F"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6261,
   "documented": "1875",
   "name": "Control type selection (CH2)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Direct action",
    "1": "Reverse action"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6266,
   "documented": "187A",
   "name": "Event 1 type selection (CH2)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Not provided",
    "1": "Process high",
    "2": "Process low",
    "3": "Deviation high",
    "4": "Deviation low",
    "5": "Deviation high/low",
    "6": "Band"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6267,
   "documented": "187B",
   "name": "Event 2 type selection (CH2)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Not provided",
    "1": "Process high",
    "2": "Process low",
    "3": "Deviation high",
    "4": "Deviation low",
    "5": "Deviation high/low",
    "6": "Band"
   },
   "bits": null,
   "offset": 0
  }
 ],
 "page": "https://easymodbus.com/modbus-register-maps/rkc-instrument/srx-tio",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}