 "manufacturer": "RLE Technologies",
 "manufacturer_slug": "rle-technologies",
 "model": "LD5200 leak detection controller (Modbus RTU / Modbus TCP slave)",
 "model_slug": "ld5200",
 "short_model": "LD5200",
 "aliases": [
  "LD5200"
 ],
 "equipment_type": "Sensor (leak detection controller)",
 "applies_to": "RLE LD5200 distance-read leak detection controller, user guide version 04.22 (firmware 2.3.1).",
 "summary": "The LD5200 monitors a water-sensing cable and reports where along the cable a leak is. As a Modbus slave on its EIA-485 ports (or Modbus over Ethernet) it gives leak, cable-break and contamination status, leak distance and current, cable resistances, virtual-zone alarms and the status of the slave panels it polls as a Modbus master. Thresholds and alarm delays are writable holding registers.",
 "transport": [
  "RTU",
  "TCP"
 ],
 "defaults": {
  "unit_id": null,
  "baud": 9600,
  "parity": "None",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "Modicon",
  "note": "RLE says the start register is numbered from zero: 40001 = 0, 30001 = 0. So input register 30002 (leak distance) is wire address 1 with FC4, holding register 40016 is address 15 with FC3/FC6/FC16."
 },
 "default_word_order": "ABCD",
 "firmware": "Documented with firmware 2.3.1",
 "source": {
  "title": "LD5200 User Guide",
  "doc_number": "Version 04.22",
  "revision_date": "2022-04",
  "url": "https://WWW.RLETECH.COM/wp-content/uploads/2022/04/LD5200_UserGuide-04-22.pdf",
  "pages": "pp. 87-101 (ch. 5 Modbus communication: tables 5.3, 5.5, 5.6, 5.7); p. 78 (table 4.12 port options)"
 },
 "notes": [
  "Float word order: the guide labels 38001 as the float MSW and 38002 as the LSW, so the leak-location float is ABCD.",
  "Only the first block of Modbus slave zones (2-16, registers 30012-30042) is listed. Later blocks cover 16 zones each: 30043 flags zones 17-32 with status/distance pairs from 30044, 30076 flags zones 33-48, and so on up to zone 128 at 30272/30273.",
  "Holding registers 40003-40015 are spare.",
  "Distance registers are in feet or meters depending on register 30003.",
  "The guide calls the Ethernet option 'Modbus/TCP/UDP' with its own slave unit identifier (1-254); it does not list a separate map, so the same registers are assumed to apply over Ethernet. The TCP port is not given.",
  "The leak trip range differs inside the guide: the Modbus table shows 25-295 uA, the LCD settings page says 25-175 uA.",
  "Bit 15 of 30012 is labeled zone 16 although bit 0 is zone 2, so the bits of 30012 are not listed."
 ],
 "integration": {
  "summary": "Read input registers 30001-30011 with FC4: status bits for leak / cable break / contamination, leak distance and unit, leak current and cable data. Read 38001-38002 for the leak position as a float in meters.",
  "minimum_registers": [
   {
    "table": "input_register",
    "address": 0,
    "why": "Leak / cable break / contamination status"
   },
   {
    "table": "input_register",
    "address": 1,
    "why": "Leak distance"
   },
   {
    "table": "input_register",
    "address": 2,
    "why": "Distance unit"
   },
   {
    "table": "input_register",
    "address": 3,
    "why": "Leak current"
   },
   {
    "table": "input_register",
    "address": 8000,
    "why": "Leak location in meters (float)"
   },
   {
    "table": "input_register",
    "address": 9,
    "why": "Virtual zone alarms 1-16"
   }
  ],
  "enable": "Set an EIA-485 port function to Modbus-Slave and give it a slave address (1-254, 0 = disabled) and baud rate in the Comm Port Settings menu (LCD) or the Modbus/EIA-485 web page. For Ethernet, set the Modbus/TCP/UDP slave unit identifier on the same page.",
  "watchdog": null,
  "quirks": [
   "RTU only on the serial ports, fixed 8 data bits, no parity, 1 stop bit; baud 9600 (default), 19200 or 38400.",
   "As a slave the LD5200 accepts only one master."
  ],
  "setup": [
   "Three EIA-485 ports (TB5/TB6); port 2 can also be BACnet MS/TP or N2.",
   "When the LD5200 is a master for distance-read panels, the first slave must use address 2, the next 3, and so on."
  ],
  "gotchas": [
   "A missing end-of-line terminator on the sensing cable shows as a cable fault."
  ]
 },
 "registers": [
  {
   "table": "input_register",
   "address": 0,
   "documented": "30001",
   "name": "Status",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Leak detected",
    "1": "Cable break alarm",
    "2": "Contamination detected"
   },
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1,
   "documented": "30002",
   "name": "Leak distance",
   "description": "Location of the leak; unit per register 30003.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "ft or m",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2,
   "documented": "30003",
   "name": "Distance units",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Meters",
    "1": "Feet"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3,
   "documented": "30004",
   "name": "Leak current",
   "description": "Leakage current on the sensing cable.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "uA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 4,
   "documented": "30005",
   "name": "Cable length",
   "description": "Installed sensing-cable length.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "ft or m",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 5,
   "documented": "30006",
   "name": "Loop 1 resistance",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "ohm",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 6,
   "documented": "30007",
   "name": "Loop 2 resistance",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "ohm",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 7,
   "documented": "30008",
   "name": "Resistance per foot",
   "description": "Published as ohms x 1000.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.001,
   "scale_factor_ref": null,
   "units": "ohm",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 8,
   "documented": "30009",
   "name": "Firmware version",
   "description": "xx.xx x 100.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 9,
   "documented": "30010",
   "name": "Virtual zone alarm status, zones 1-16",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Zone 1 in alarm",
    "1": "Zone 2 in alarm",
    "2": "Zone 3 in alarm",
    "3": "Zone 4 in alarm",
    "4": "Zone 5 in alarm",
    "5": "Zone 6 in alarm",
    "6": "Zone 7 in alarm",
    "7": "Zone 8 in alarm",
    "8": "Zone 9 in alarm",
    "9": "Zone 10 in alarm",
    "10": "Zone 11 in alarm",
    "11": "Zone 12 in alarm",
    "12": "Zone 13 in alarm",
    "13": "Zone 14 in alarm",
    "14": "Zone 15 in alarm",
    "15": "Zone 16 in alarm"
   },
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 10,
   "documented": "30011",
   "name": "Virtual zone alarm status, zones 17-32",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Zone 17 in alarm",
    "1": "Zone 18 in alarm",
    "2": "Zone 19 in alarm",
    "3": "Zone 20 in alarm",
    "4": "Zone 21 in alarm",
    "5": "Zone 22 in alarm",
    "6": "Zone 23 in alarm",
    "7": "Zone 24 in alarm",
    "8": "Zone 25 in alarm",
    "9": "Zone 26 in alarm",
    "10": "Zone 27 in alarm",
    "11": "Zone 28 in alarm",
    "12": "Zone 29 in alarm",
    "13": "Zone 30 in alarm",
    "14": "Zone 31 in alarm",
    "15": "Zone 32 in alarm"
   },
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 11,
   "documented": "30012",
   "name": "Modbus zone enabled flags, zones 2-16",
   "description": "One bit per zone 2-16; the guide's bit labels (0 = zone 2, 15 = zone 16) do not add up.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 12,
   "documented": "30013",
   "name": "Modbus zone 2 status",
   "description": "Slave leak-detection panel on the LD5200's master port.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Leak detected",
    "1": "Cable break",
    "2": "Contamination",
    "7": "Communication loss"
   },
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 13,
   "documented": "30014",
   "name": "Modbus zone 2 distance",
   "description": "Leak location reported by that slave.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "ft or m",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 14,
   "documented": "30015",
   "name": "Modbus zone 3 status",
   "description": "Slave leak-detection panel on the LD5200's master port.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Leak detected",
    "1": "Cable break",
    "2": "Contamination",
    "7": "Communication loss"
   },
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 15,
   "documented": "30016",
   "name": "Modbus zone 3 distance",
   "description": "Leak location reported by that slave.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "ft or m",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 16,
   "documented": "30017",
   "name": "Modbus zone 4 status",
   "description": "Slave leak-detection panel on the LD5200's master port.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Leak detected",
    "1": "Cable break",
    "2": "Contamination",
    "7": "Communication loss"
   },
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 17,
   "documented": "30018",
   "name": "Modbus zone 4 distance",
   "description": "Leak location reported by that slave.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "ft or m",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 18,
   "documented": "30019",
   "name": "Modbus zone 5 status",
   "description": "Slave leak-detection panel on the LD5200's master port.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Leak detected",
    "1": "Cable break",
    "2": "Contamination",
    "7": "Communication loss"
   },
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 19,
   "documented": "30020",
   "name": "Modbus zone 5 distance",
   "description": "Leak location reported by that slave.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "ft or m",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 20,
   "documented": "30021",
   "name": "Modbus zone 6 status",
   "description": "Slave leak-detection panel on the LD5200's master port.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Leak detected",
    "1": "Cable break",
    "2": "Contamination",
    "7": "Communication loss"
   },
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 21,
   "documented": "30022",
   "name": "Modbus zone 6 distance",
   "description": "Leak location reported by that slave.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "ft or m",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 22,
   "documented": "30023",
   "name": "Modbus zone 7 status",
   "description": "Slave leak-detection panel on the LD5200's master port.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Leak detected",
    "1": "Cable break",
    "2": "Contamination",
    "7": "Communication loss"
   },
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 23,
   "documented": "30024",
   "name": "Modbus zone 7 distance",
   "description": "Leak location reported by that slave.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "ft or m",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 24,
   "documented": "30025",
   "name": "Modbus zone 8 status",
   "description": "Slave leak-detection panel on the LD5200's master port.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Leak detected",
    "1": "Cable break",
    "2": "Contamination",
    "7": "Communication loss"
   },
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 25,
   "documented": "30026",
   "name": "Modbus zone 8 distance",
   "description": "Leak location reported by that slave.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "ft or m",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 26,
   "documented": "30027",
   "name": "Modbus zone 9 status",
   "description": "Slave leak-detection panel on the LD5200's master port.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Leak detected",
    "1": "Cable break",
    "2": "Contamination",
    "7": "Communication loss"
   },
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 27,
   "documented": "30028",
   "name": "Modbus zone 9 distance",
   "description": "Leak location reported by that slave.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "ft or m",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 28,
   "documented": "30029",
   "name": "Modbus zone 10 status",
   "description": "Slave leak-detection panel on the LD5200's master port.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Leak detected",
    "1": "Cable break",
    "2": "Contamination",
    "7": "Communication loss"
   },
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 29,
   "documented": "30030",
   "name": "Modbus zone 10 distance",
   "description": "Leak location reported by that slave.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "ft or m",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 30,
   "documented": "30031",
   "name": "Modbus zone 11 status",
   "description": "Slave leak-detection panel on the LD5200's master port.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Leak detected",
    "1": "Cable break",
    "2": "Contamination",
    "7": "Communication loss"
   },
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 31,
   "documented": "30032",
   "name": "Modbus zone 11 distance",
   "description": "Leak location reported by that slave.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "ft or m",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 32,
   "documented": "30033",
   "name": "Modbus zone 12 status",
   "description": "Slave leak-detection panel on the LD5200's master port.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Leak detected",
    "1": "Cable break",
    "2": "Contamination",
    "7": "Communication loss"
   },
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 33,
   "documented": "30034",
   "name": "Modbus zone 12 distance",
   "description": "Leak location reported by that slave.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "ft or m",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 34,
   "documented": "30035",
   "name": "Modbus zone 13 status",
   "description": "Slave leak-detection panel on the LD5200's master port.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Leak detected",
    "1": "Cable break",
    "2": "Contamination",
    "7": "Communication loss"
   },
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 35,
   "documented": "30036",
   "name": "Modbus zone 13 distance",
   "description": "Leak location reported by that slave.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "ft or m",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 36,
   "documented": "30037",
   "name": "Modbus zone 14 status",
   "description": "Slave leak-detection panel on the LD5200's master port.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Leak detected",
    "1": "Cable break",
    "2": "Contamination",
    "7": "Communication loss"
   },
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 37,
   "documented": "30038",
   "name": "Modbus zone 14 distance",
   "description": "Leak location reported by that slave.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "ft or m",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 38,
   "documented": "30039",
   "name": "Modbus zone 15 status",
   "description": "Slave leak-detection panel on the LD5200's master port.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Leak detected",
    "1": "Cable break",
    "2": "Contamination",
    "7": "Communication loss"
   },
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 39,
   "documented": "30040",
   "name": "Modbus zone 15 distance",
   "description": "Leak location reported by that slave.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "ft or m",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 40,
   "documented": "30041",
   "name": "Modbus zone 16 status",
   "description": "Slave leak-detection panel on the LD5200's master port.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Leak detected",
    "1": "Cable break",
    "2": "Contamination",
    "7": "Communication loss"
   },
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 41,
   "documented": "30042",
   "name": "Modbus zone 16 distance",
   "description": "Leak location reported by that slave.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "ft or m",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 8000,
   "documented": "38001",
   "name": "Leak location (float)",
   "description": "Location of leak in meters; MSW at 38001, LSW at 38002.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "scale_factor_ref": null,
   "units": "m",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 0,
   "documented": "40001",
   "name": "Leak threshold",
   "description": "Trip current for a leak alarm.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "uA",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1,
   "documented": "40002",
   "name": "Contamination threshold",
   "description": "Trip current for a contamination alarm, 20-295.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "uA",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 15,
   "documented": "40016",
   "name": "Leak alarm delay",
   "description": "5-995 s.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16,
   "documented": "40017",
   "name": "Contamination alarm delay",
   "description": "5-995 s.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "page": "https://easymodbus.com/modbus-register-maps/rle-technologies/ld5200",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}