 "manufacturer": "Saia Burgess Controls",
 "manufacturer_slug": "saia-burgess-controls",
 "model": "ALE3 three-phase 65 A energy meter (Modbus RTU)",
 "model_slug": "ale3-modbus",
 "short_model": "ALE3",
 "aliases": [
  "ALE3D5FD10C3A00",
  "ALE3B5FD00C3A00",
  "ALE3D5FD10",
  "ALE3B5FD00",
  "SBC ALE3 Modbus"
 ],
 "equipment_type": "Energy meter",
 "applies_to": "ALE3 unidirectional (ALE3D5FD10C3A00) and bidirectional (ALE3B5FD00C3A00) Modbus types, assembly and operating instructions 431951130.",
 "summary": "The ALE3 is a Saia Burgess Controls DIN-rail three-phase active energy meter for direct connection up to 65 A, with an RS-485 Modbus RTU interface. Baud rate and parity are detected automatically. This map covers identification, status and error registers, the two total and two resettable partial energy counters, and per-phase voltage and current.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": null,
  "baud": null,
  "parity": null,
  "data_bits": 8,
  "stop_bits": null,
  "tcp_port": null
 },
 "addressing": {
  "convention": "1-based",
  "note": "The register list numbers registers from 1, and the manual states that register R is sent as R - 1: register 28 (energy total) is wire address 27."
 },
 "default_word_order": "ABCD",
 "firmware": null,
 "source": {
  "title": "ALE3 Modbus - Assembly and operating instructions (unidirectional ALE3D5FD10, bidirectional ALE3B5FD00)",
  "doc_number": "4 319 5113 0 H (file MI-UG ALE3 Modbus UniBiDi 02)",
  "revision_date": "2022-02-25",
  "url": "https://community.viessmann.de/viessmann/attachments/viessmann/customers-heatpump-hybrid/52600/1/431951130s_MI-UG_ALE3_Modbus-UniBiDi_02.pdf",
  "unofficial": true,
  "pages": "English register list and Modbus technical data, PDF page 2"
 },
 "notes": [
  "This is an unaltered copy of the SBC instruction sheet posted on the Viessmann community forum; an official public SBC URL for this revision was not found in the time available.",
  "The sheet lists the double registers sent high register first (big-endian, ABCD) as 4-5, 16-17, 28-29, 30-31 and 32-33. Example from the sheet: high 13, low 60383 = 912351 = 9123.51 kWh.",
  "Energy counters are 0.01 kWh per count. Voltage is 1 V per count, current 0.1 A per count.",
  "On the unidirectional type registers 28-35 are tariff 1 and tariff 2 counters. On the bidirectional type the sheet's display section describes the second counter set as feed-back (delivered) energy; the tariff register's arrows mark direction.",
  "Left out: active and reactive power and cos phi per phase and total (registers 38-40, 43-45, 48-52), because the sheet does not say whether these 16-bit values are signed, which matters on the bidirectional type; the serial number (16-18), whose word layout is printed inconsistently; type/ASN text registers 7-14.",
  "Left out: partial energy WT2 (registers 34-35). The sheet names it a resettable partial counter but leaves it off its list of high-register-first pairs, so its word order is not stated.",
  "Only functions 03 and 16 are accepted, and at most 20 registers per request.",
  "Serial format: baud rate (4800-115200) and parity are auto-detected; even or odd parity use 1 stop bit, no parity uses 2 stop bits."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 0,
   "documented": "1",
   "name": "Firmware version",
   "description": "e.g. 11 = FW 1.1.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1,
   "documented": "2",
   "name": "Number of supported registers",
   "description": "Reads 52.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3,
   "documented": "4-5",
   "name": "Baud rate",
   "description": "Detected baud rate, e.g. 115200.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "bps",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14,
   "documented": "15",
   "name": "Hardware version",
   "description": "e.g. 11 = HW 1.1.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 21,
   "documented": "22",
   "name": "Status / protect",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No problem",
    "1": "Problem with last communication request"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 22,
   "documented": "23",
   "name": "Response timeout",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "ms",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 23,
   "documented": "24",
   "name": "Modbus address",
   "description": "1-247; cannot be written by broadcast.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 24,
   "documented": "25",
   "name": "Error register",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No error",
    "1": "Error phase 1",
    "2": "Error phase 2",
    "3": "Error phase 1 + 2",
    "4": "Error phase 3",
    "5": "Error phase 1 + 3",
    "6": "Error phase 2 + 3",
    "7": "Error phase 1, 2 + 3"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 26,
   "documented": "27",
   "name": "Tariff register",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Tariff 1 (bidirectional: forward)",
    "4": "Tariff 2 (bidirectional: reverse)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 27,
   "documented": "28-29",
   "name": "Counter total energy WT1",
   "description": "Tariff 1 total; see notes for the bidirectional type.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 29,
   "documented": "30-31",
   "name": "Counter partial energy WT1",
   "description": "Resettable: write 0 to both registers in one FC16 message.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "units": "kWh",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 31,
   "documented": "32-33",
   "name": "Counter total energy WT2",
   "description": "Tariff 2 total; see notes for the bidirectional type.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 35,
   "documented": "36",
   "name": "Voltage phase 1 (URMS)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 36,
   "documented": "37",
   "name": "Current phase 1 (IRMS)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 40,
   "documented": "41",
   "name": "Voltage phase 2 (URMS)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 41,
   "documented": "42",
   "name": "Current phase 2 (IRMS)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 45,
   "documented": "46",
   "name": "Voltage phase 3 (URMS)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 46,
   "documented": "47",
   "name": "Current phase 3 (IRMS)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Read holding registers 28-33 (wire 27-32) for the energy counters as 32-bit high-word-first values in 0.01 kWh, and 36-47 for voltages and currents; keep each request at 20 registers or fewer.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 27,
    "why": "Total energy WT1, 0.01 kWh"
   },
   {
    "table": "holding_register",
    "address": 31,
    "why": "Total energy WT2, 0.01 kWh"
   },
   {
    "table": "holding_register",
    "address": 35,
    "why": "Voltage L1"
   },
   {
    "table": "holding_register",
    "address": 36,
    "why": "Current L1, 0.1 A"
   },
   {
    "table": "holding_register",
    "address": 24,
    "why": "Error register"
   }
  ],
  "enable": "Set the Modbus address on the meter (press the touch key for 3 s, then step the address) or write register 24; baud rate and parity are detected automatically.",
  "watchdog": null,
  "quirks": [
   "Register R is wire address R - 1.",
   "Max 20 registers per read; only FC03 and FC16.",
   "Address register cannot be written by broadcast."
  ],
  "setup": [
   "The interface has no built-in terminating resistor; fit one externally.",
   "Up to 247 meters per bus; use a repeater beyond 128."
  ],
  "gotchas": [
   "Reset partial counter WT1 by writing 0 to both of its registers (30-31) in one FC16 message.",
   "Data refreshes every 10 s; the sheet advises not polling one meter faster than that.",
   "The interface works only with phase 1 connected and answers 30 s after power-up."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/saia-burgess-controls/ale3-modbus",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}