 "manufacturer": "Samsung",
 "manufacturer_slug": "samsung",
 "model": "CycloGic CL-MC03 Modbus interface module (Samsung DVM / CAC / RAC)",
 "model_slug": "cyclogic-cl-mc03",
 "short_model": "CL-MC03",
 "aliases": [
  "CL-MC0301C",
  "CL-MC0308C",
  "CL-MC0316C",
  "CL-MC0332C",
  "CL-MC0364C",
  "CycloGic Modbus Interface Module"
 ],
 "equipment_type": "VRF / split AC gateway",
 "applies_to": "CycloGic CL-MC03*** series Modbus interface modules (1 to 64 indoor units) for Samsung DVM, CAC, FJM and RAC units, instruction manual Rev. 2 (Oct. 2017).",
 "summary": "The CL-MC03 series is a CycloGic-made Modbus RTU interface that connects to the F1/F2 network of Samsung DVM, CAC, FJM or RAC indoor units and controls up to 64 of them. Each indoor unit has a 20-register block. This map covers the block for indoor unit 0: on/off, mode, set and room temperature, fan speed, louver swing and the duct-unit supply-air setpoints.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": null,
  "baud": 19200,
  "parity": "Even",
  "data_bits": null,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "Modicon",
  "note": "The manual uses Modicon numbers: 40001-40014 for indoor unit 00, plus 20 per indoor unit (unit 01 = 40021, unit 63 = 41261). Subtract 40001 for the wire address: unit N, register 4000k is address 20*N + k - 1."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "CL-MC03*** Series Modbus Interface Module Instruction Manual",
  "doc_number": "Document Rev. 2",
  "revision_date": "2017-10",
  "url": "https://cdn.komachine.com/media/product-catalog/Manual-CYCLOGIC-Modbus_Interface_Module.pdf",
  "unofficial": true,
  "pages": "DIP switches p. 4; rotary address p. 5; Modbus configuration and functions p. 7; readback data p. 8; control data p. 9"
 },
 "notes": [
  "Source host: an unaltered copy of the CycloGic manual on a product-catalogue site; we did not find a public copy on CycloGic's or Samsung's sites.",
  "Only FC 03 (read) and FC 06 (write single register) are supported; all values are 16-bit.",
  "Writes to 40001 and 40009 carry two one-byte fields (on/off + mode, fan speed + louver swing). The manual does not say which byte holds which field, so those writes are not mapped; the registers are listed for reading.",
  "Temperatures are value / 10; the manual does not state whether they are signed.",
  "Registers 40003-40004 and 40007-40008 are not described in the manual."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 0,
   "documented": "40001",
   "name": "IDU on/off status",
   "description": "Read value. Writes to this register use a packed on/off + mode format (see notes).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1,
   "documented": "40002",
   "name": "IDU operation mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Auto",
    "1": "Cooling",
    "2": "Dry (dehumidification)",
    "3": "Fan",
    "4": "Heat",
    "11": "Auto cool",
    "12": "Auto dry",
    "13": "Auto fan",
    "14": "Auto heat"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4,
   "documented": "40005",
   "name": "Set temperature",
   "description": "Value / 10.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5,
   "documented": "40006",
   "name": "Room temperature",
   "description": "Value / 10.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8,
   "documented": "40009",
   "name": "IDU fan speed",
   "description": "Read value. Writes use a packed fan speed + louver format (see notes).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Automatic",
    "1": "Low",
    "2": "Middle",
    "3": "High",
    "4": "Turbo"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9,
   "documented": "40010",
   "name": "Deco panel louver swing",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Swing off",
    "1": "Swing on: upper and lower louver",
    "2": "Swing on: right and left louver",
    "3": "Swing on: upper/lower and right/left louver"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10,
   "documented": "40011",
   "name": "Supply air (discharge) temperature",
   "description": "Duct units only; value / 10.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11,
   "documented": "40012",
   "name": "Supply air temperature control",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disable",
    "1": "Enable"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 12,
   "documented": "40013",
   "name": "Cooling supply air set temperature",
   "description": "Duct units only; value / 10.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 13,
   "documented": "40014",
   "name": "Heating supply air set temperature",
   "description": "Duct units only; value / 10.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Set DIP SW2 for the Samsung product type, set the Modbus address on the two rotary switches, then poll FC 03 from address 20*N for indoor unit N. Change the set temperature with FC 06 at 20*N + 4.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 0,
    "why": "Unit 0 on/off status"
   },
   {
    "table": "holding_register",
    "address": 1,
    "why": "Unit 0 operation mode"
   },
   {
    "table": "holding_register",
    "address": 4,
    "why": "Unit 0 set temperature"
   },
   {
    "table": "holding_register",
    "address": 5,
    "why": "Unit 0 room temperature"
   },
   {
    "table": "holding_register",
    "address": 8,
    "why": "Unit 0 fan speed"
   }
  ],
  "enable": "DIP SW2 OFF for DVM/CAC (AM/AC models), ON for RAC/FJM (AR/AJ models); DIP SW1 must stay ON (firmware download disabled) in normal use. The slave address is set with RSW1 (tens) and RSW2 (ones).",
  "watchdog": null,
  "quirks": [
   "Modicon numbering, 20 registers per indoor unit.",
   "Temperatures are tenths of a degree."
  ],
  "setup": [
   "19200 bps, even parity, 1 stop bit; Modbus line up to 500 m.",
   "12 V DC supply from the indoor unit V1/V2 terminals; F1/F2 to the Samsung network."
  ],
  "gotchas": [
   "DIP SW2 must match the Samsung product family: OFF for DVM/CAC, ON for RAC/FJM.",
   "The module's dry-contact input forces units on/off and its DO closes on an error."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/samsung/cyclogic-cl-mc03",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}