 "manufacturer": "Samsung",
 "manufacturer_slug": "samsung",
 "model": "MIM-B19N Modbus interface module (DVM / EHS / indoor units)",
 "model_slug": "mim-b19n",
 "short_model": "MIM-B19N",
 "aliases": [
  "MIM-B19N",
  "Samsung Modbus interface module"
 ],
 "equipment_type": "VRF / split AC gateway",
 "applies_to": "Samsung MIM-B19N Modbus interface module on the R1/R2 bus of one outdoor system with up to 48 indoor units (installation manual DB68-07538A-00).",
 "summary": "The MIM-B19N links one Samsung outdoor system (up to 4 modular outdoor units) and up to 48 indoor units, hydro units, AHU kits, ERVs, chillers or FCUs on the R1/R2 bus to a Modbus RTU master. Each indoor unit gets a fixed 50-register block. This map covers the module status registers and the indoor-unit block: on/off, mode, fan speed, setpoints, room and water temperatures, errors, ventilation and hot-water functions. Addresses are given for indoor unit 0.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": null,
  "baud": 9600,
  "parity": "Even",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "0-based",
  "note": "The table prints both a 1-based register number and the Modbus PDU address; the PDU address is used. Indoor unit n (0-47) occupies PDU addresses 50 + n*50 + k. This map lists indoor unit 0 (addresses 50-81); add 50 per unit, e.g. indoor unit 3 on/off = 50 + 150 + 2 = 202."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "Modbus Interface Module MIM-B19N Installation Manual",
  "doc_number": "DB68-07538A-00",
  "revision_date": null,
  "url": "https://midsummerwholesale.co.uk/pdfs/mim-b19n-manual.pdf",
  "unofficial": true,
  "pages": "specifications and communication settings p. 8; communication sequence p. 9; address switches pp. 11-12; register table pp. 13-16"
 },
 "notes": [
  "Source host: the unaltered Samsung manual hosted by a UK distributor; we did not find a public Samsung copy.",
  "All values are single 16-bit registers, big-endian. Temperatures are Celsius x10; the manual's ranges go down to -41 °C, so they are listed as signed.",
  "The manual marks each point R, W or R/W per unit type (indoor, HE/HT/EHS, AHU kit, ERV, ERV+, chiller, FCU, FCU kit). Read-only points are listed as input registers (FC 04) and writable points as holding registers (FC 03/06/16); the module supports both read functions but the manual does not say which table each read-only point lives in, so try FC 03 if FC 04 is refused.",
  "Access shown is the widest across unit types; a point marked '-' for a unit type does not apply to it (e.g. water temperatures only for HE/HT/EHS and chillers, ventilation only for ERV).",
  "Left out: the MCC chiller error-information registers (+26/+27, packed bytes) and the reserved ranges.",
  "Any write to a holding register is always forwarded to the indoor unit as a command, even if the value is unchanged."
 ],
 "registers": [
  {
   "table": "input_register",
   "address": 0,
   "documented": "0",
   "name": "Modbus interface module error status",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Address error",
    "1": "Communication error on R1/R2",
    "2": "Tracking error"
   },
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1,
   "documented": "1",
   "name": "Integrated outdoor unit error code",
   "description": "100-999 = error code.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2,
   "documented": "2",
   "name": "Outdoor defrost operation",
   "description": "0 or 0xFF = defrost off; other values = defrost on.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 50,
   "documented": "(50 + IU*50) + 0",
   "name": "Communication status",
   "description": "Bits 0-2 all set (value 7) = unit tracked and ready for control.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Exist",
    "1": "Type OK",
    "2": "Ready",
    "3": "Communication error"
   },
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 51,
   "documented": "(50 + IU*50) + 1",
   "name": "Unit type",
   "description": "Low byte = model code (e.g. HE 110, ERV 100-102); high byte 10 = FCU.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 56,
   "documented": "(50 + IU*50) + 6",
   "name": "Filter-cleaning reminder",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Filter alarm not present",
    "1": "Filter alarm present"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 59,
   "documented": "(50 + IU*50) + 9",
   "name": "Room temperature",
   "description": "Celsius x10. Range -41 to 100 °C.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 60,
   "documented": "(50 + IU*50) + 10",
   "name": "Discharge temperature",
   "description": "Celsius x10.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 63,
   "documented": "(50 + IU*50) + 13",
   "name": "Integrated indoor unit error code",
   "description": "100-999 = error code.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 65,
   "documented": "(50 + IU*50) + 15",
   "name": "Water-in temperature",
   "description": "Celsius x10.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 66,
   "documented": "(50 + IU*50) + 16",
   "name": "Water-out Temperature",
   "description": "Celsius x10.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 67,
   "documented": "(50 + IU*50) + 17",
   "name": "MCC water-out temperature",
   "description": "Celsius x10.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 75,
   "documented": "(50 + IU*50) + 25",
   "name": "Hot water temperature",
   "description": "Celsius x10.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3,
   "documented": "3",
   "name": "Buzzer on/off",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": {
    "0": "Turns the buzzer on",
    "1": "Turns the buzzer off"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 52,
   "documented": "(50 + IU*50) + 2",
   "name": "Air conditioner on/off",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 53,
   "documented": "(50 + IU*50) + 3",
   "name": "Air conditioner mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Auto",
    "1": "Cool",
    "2": "Dry",
    "3": "Fan",
    "4": "Heat",
    "21": "Cool Storage",
    "24": "Heat Storage"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 54,
   "documented": "(50 + IU*50) + 4",
   "name": "Indoor fan speed",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Auto",
    "1": "Low",
    "2": "Middle",
    "3": "High"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 55,
   "documented": "(50 + IU*50) + 5",
   "name": "Use of vertical air flow direction",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 57,
   "documented": "(50 + IU*50) + 7",
   "name": "Canceling the filter-cleaning reminder",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": {
    "0": "No Clear Filter Alarm",
    "1": "Clear Filter Alarm"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 58,
   "documented": "(50 + IU*50) + 8",
   "name": "Set temperature",
   "description": "Celsius x10.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 61,
   "documented": "(50 + IU*50) + 11",
   "name": "Cooling discharge set temperature",
   "description": "Celsius x10. Range 8 to 18 °C.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 62,
   "documented": "(50 + IU*50) + 12",
   "name": "Heating discharge set temperature",
   "description": "Celsius x10. Range 30 to 43 °C.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64,
   "documented": "(50 + IU*50) + 14",
   "name": "Restrictions on the remote control",
   "description": "Read 0 = none, other = restricted; write 0x0000 to release, 0x6363 to restrict.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 68,
   "documented": "(50 + IU*50) + 18",
   "name": "Water-out set temperature",
   "description": "Celsius x10; allowed range depends on unit type.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 69,
   "documented": "(50 + IU*50) + 19",
   "name": "Ventilation on/off",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 70,
   "documented": "(50 + IU*50) + 20",
   "name": "Ventilation mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Bypass",
    "1": "HeatEx",
    "2": "Auto",
    "6": "Sleep"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 71,
   "documented": "(50 + IU*50) + 21",
   "name": "Ventilation fan speed",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "AUTO",
    "2": "Low",
    "3": "High",
    "4": "Turbo"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 72,
   "documented": "(50 + IU*50) + 22",
   "name": "Hot water operation on/off",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "HotWater Off",
    "1": "HotWater On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 73,
   "documented": "(50 + IU*50) + 23",
   "name": "Hot water mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Eco",
    "1": "Standard",
    "2": "Power",
    "3": "Force (for the EHS only)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 74,
   "documented": "(50 + IU*50) + 24",
   "name": "Hot water set temperature",
   "description": "Celsius x10; allowed range depends on unit type.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 78,
   "documented": "(50 + IU*50) + 28",
   "name": "Quiet control",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Slience Off",
    "1": "Slience On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 79,
   "documented": "(50 + IU*50) + 29",
   "name": "Away function",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Outing Off",
    "1": "Outing On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 80,
   "documented": "(50 + IU*50) + 30",
   "name": "Wind-Free function",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "None",
    "9": "WindFree"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 81,
   "documented": "(50 + IU*50) + 31",
   "name": "360 air flow direction",
   "description": "Other values = individual control.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "106": "Spot",
    "85": "Mid",
    "64": "Wide",
    "15": "Swing"
   },
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Set the module address with the DIP/rotary switches, connect RS-485 at 9600 8E1, wait until bits 0-2 of an indoor unit's communication status (50 + n*50) read 7, then read and write its 50-register block.",
  "minimum_registers": [
   {
    "table": "input_register",
    "address": 50,
    "why": "Indoor unit 0 communication status"
   },
   {
    "table": "holding_register",
    "address": 52,
    "why": "Indoor unit 0 on/off"
   },
   {
    "table": "holding_register",
    "address": 53,
    "why": "Indoor unit 0 mode"
   },
   {
    "table": "holding_register",
    "address": 58,
    "why": "Indoor unit 0 set temperature"
   },
   {
    "table": "input_register",
    "address": 59,
    "why": "Indoor unit 0 room temperature"
   },
   {
    "table": "input_register",
    "address": 63,
    "why": "Indoor unit 0 error code"
   },
   {
    "table": "input_register",
    "address": 0,
    "why": "Module error status"
   }
  ],
  "enable": "Set the Modbus address (1-247) as the sum of the ON DIP switches plus the rotary switch value, connect R1/R2 to the outdoor unit, and give every indoor unit an address 0-47. Reset the module after changing indoor unit addresses or the central-control option.",
  "watchdog": null,
  "quirks": [
   "Per-unit blocks: address = 50 + indoor address x 50 + offset.",
   "Temperatures are x10 integers.",
   "Holding values update only after the indoor unit reports a change."
  ],
  "setup": [
   "Fixed serial format: 9600 bps, 8 data bits, even parity, 1 stop bit.",
   "RS-485 2-wire, up to 1000 m; DC 12 V supply."
  ],
  "gotchas": [
   "Leave at least 10 ms after each response before the next request.",
   "Repeated identical writes are sent to the unit each time; write only when a change is needed.",
   "After power-up all registers read 0 until tracking of the outdoor/indoor units completes."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/samsung/mim-b19n",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}