 "manufacturer": "Schneider Electric",
 "manufacturer_slug": "schneider-electric",
 "model": "Acti 9 Smartlink Modbus (A9XMSB11) 11-channel I/O and pulse concentrator",
 "model_slug": "acti9-smartlink-modbus",
 "short_model": "Acti 9 Smartlink",
 "aliases": [
  "Acti 9 Smartlink",
  "Smartlink Modbus",
  "A9XMSB11",
  "Acti9 Smartlink"
 ],
 "equipment_type": "Energy meter (pulse and status concentrator)",
 "applies_to": "Acti 9 Smartlink Modbus RS-485 module A9XMSB11, per user manual DOCA0004EN-06 (04/2016).",
 "summary": "The Acti 9 Smartlink gathers status, commands and pulse counts from up to 11 Ti24 channels (iOF+SD24 auxiliaries, iACT24/iATL24, Reflex iC60, RCA iC60, pulse meters such as iEM2000T) and serves them on one Modbus RTU address. Summary blocks give all channels in one read; each channel also has a 40-register detail block. 32-bit counters are big-endian.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": null,
  "baud": 19200,
  "parity": "Even",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "0-based",
  "note": "The manual prints Modbus protocol addresses, which start at 0, and says a master that uses data-model numbering must add 1. Its frame example reads address 14050 as 0x36E2."
 },
 "default_word_order": "ABCD",
 "firmware": null,
 "source": {
  "title": "Acti 9 Smartlink Modbus Communication System - User Manual",
  "doc_number": "DOCA0004EN-06",
  "revision_date": "2016-04",
  "url": "https://download.se.com/files?p_Doc_Ref=DOCA0004EN",
  "pages": "Comms settings pp. 63-64; data types and big-endian rule pp. 74-75; frame example p. 76; address overview p. 77; system and summary registers pp. 79-83; channel detail pp. 84-89; configuration registers p. 90"
 },
 "notes": [
  "The manual states 32-bit values are big-endian: most significant word first.",
  "Channel n detail registers = channel 1 register + 40 x (n-1) (14200, 14240 ... 14600). Only channel 1's detail block is listed here; the summary blocks 14000-14165 cover all channels.",
  "Power/flow and consumption units depend on the meter on that input (Wh, m3, L ...), set by its pulse weight. The flow value drops to 0 when pulses stop.",
  "Left out: identification strings (100, 109), date/time (115) and counter setting dates (DATE type), and the embedded configuration blocks beyond the channel 1 product type.",
  "The Smartlink adapts to the master's baud and parity after up to 25 frames at power-up; with no parity it needs 2 stop bits."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 112,
   "documented": "112",
   "name": "Smartlink status and diagnostics",
   "description": "Bits 0-3 are mutually exclusive modes.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Start-up phase",
    "1": "Operating phase",
    "2": "Downgraded mode (24 V low or I/O overcurrent)",
    "3": "Failure mode",
    "6": "Invalid data",
    "7": "Invalid 24 V I/O",
    "13": "EEPROM error",
    "14": "RAM error",
    "15": "FLASH error"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 120,
   "documented": "120",
   "name": "Input 1 state, all channels",
   "description": "Bit n-1 = channel n input I1; 1 = current flowing.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Channel 1",
    "1": "Channel 2",
    "2": "Channel 3",
    "3": "Channel 4",
    "4": "Channel 5",
    "5": "Channel 6",
    "6": "Channel 7",
    "7": "Channel 8",
    "8": "Channel 9",
    "9": "Channel 10",
    "10": "Channel 11"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 121,
   "documented": "121",
   "name": "Input 2 state, all channels",
   "description": "Bit n-1 = channel n input I2; 1 = current flowing.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Channel 1",
    "1": "Channel 2",
    "2": "Channel 3",
    "3": "Channel 4",
    "4": "Channel 5",
    "5": "Channel 6",
    "6": "Channel 7",
    "7": "Channel 8",
    "8": "Channel 9",
    "9": "Channel 10",
    "10": "Channel 11"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 130,
   "documented": "130",
   "name": "Open order, Acti 9 products",
   "description": "Set bit n-1 to open channel n; the Smartlink clears it when done.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Channel 1",
    "1": "Channel 2",
    "2": "Channel 3",
    "3": "Channel 4",
    "4": "Channel 5",
    "5": "Channel 6",
    "6": "Channel 7",
    "7": "Channel 8",
    "8": "Channel 9",
    "9": "Channel 10",
    "10": "Channel 11"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 131,
   "documented": "131",
   "name": "Close order, Acti 9 products",
   "description": "Set bit n-1 to close channel n; cleared when taken into account.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Channel 1",
    "1": "Channel 2",
    "2": "Channel 3",
    "3": "Channel 4",
    "4": "Channel 5",
    "5": "Channel 6",
    "6": "Channel 7",
    "7": "Channel 8",
    "8": "Channel 9",
    "9": "Channel 10",
    "10": "Channel 11"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 132,
   "documented": "132",
   "name": "Deactivation order, non-Acti 9 products",
   "description": "Bit n-1 = channel n.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Channel 1",
    "1": "Channel 2",
    "2": "Channel 3",
    "3": "Channel 4",
    "4": "Channel 5",
    "5": "Channel 6",
    "6": "Channel 7",
    "7": "Channel 8",
    "8": "Channel 9",
    "9": "Channel 10",
    "10": "Channel 11"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 133,
   "documented": "133",
   "name": "Activation order, non-Acti 9 products",
   "description": "Bit n-1 = channel n.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Channel 1",
    "1": "Channel 2",
    "2": "Channel 3",
    "3": "Channel 4",
    "4": "Channel 5",
    "5": "Channel 6",
    "6": "Channel 7",
    "7": "Channel 8",
    "8": "Channel 9",
    "9": "Channel 10",
    "10": "Channel 11"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14000,
   "documented": "14000",
   "name": "Ch 1 I1 power or flow indicator",
   "description": "Rate from the last two pulses, per hour; unit set by the connected meter.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14002,
   "documented": "14002",
   "name": "Ch 2 I1 power or flow indicator",
   "description": "Rate from the last two pulses, per hour; unit set by the connected meter.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14004,
   "documented": "14004",
   "name": "Ch 3 I1 power or flow indicator",
   "description": "Rate from the last two pulses, per hour; unit set by the connected meter.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14006,
   "documented": "14006",
   "name": "Ch 4 I1 power or flow indicator",
   "description": "Rate from the last two pulses, per hour; unit set by the connected meter.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14008,
   "documented": "14008",
   "name": "Ch 5 I1 power or flow indicator",
   "description": "Rate from the last two pulses, per hour; unit set by the connected meter.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14010,
   "documented": "14010",
   "name": "Ch 6 I1 power or flow indicator",
   "description": "Rate from the last two pulses, per hour; unit set by the connected meter.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14012,
   "documented": "14012",
   "name": "Ch 7 I1 power or flow indicator",
   "description": "Rate from the last two pulses, per hour; unit set by the connected meter.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14014,
   "documented": "14014",
   "name": "Ch 8 I1 power or flow indicator",
   "description": "Rate from the last two pulses, per hour; unit set by the connected meter.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14016,
   "documented": "14016",
   "name": "Ch 9 I1 power or flow indicator",
   "description": "Rate from the last two pulses, per hour; unit set by the connected meter.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14018,
   "documented": "14018",
   "name": "Ch 10 I1 power or flow indicator",
   "description": "Rate from the last two pulses, per hour; unit set by the connected meter.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14020,
   "documented": "14020",
   "name": "Ch 11 I1 power or flow indicator",
   "description": "Rate from the last two pulses, per hour; unit set by the connected meter.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14022,
   "documented": "14022",
   "name": "Ch 1 I2 power or flow indicator",
   "description": "Rate from the last two pulses, per hour; unit set by the connected meter.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14024,
   "documented": "14024",
   "name": "Ch 2 I2 power or flow indicator",
   "description": "Rate from the last two pulses, per hour; unit set by the connected meter.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14026,
   "documented": "14026",
   "name": "Ch 3 I2 power or flow indicator",
   "description": "Rate from the last two pulses, per hour; unit set by the connected meter.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14028,
   "documented": "14028",
   "name": "Ch 4 I2 power or flow indicator",
   "description": "Rate from the last two pulses, per hour; unit set by the connected meter.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14030,
   "documented": "14030",
   "name": "Ch 5 I2 power or flow indicator",
   "description": "Rate from the last two pulses, per hour; unit set by the connected meter.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14032,
   "documented": "14032",
   "name": "Ch 6 I2 power or flow indicator",
   "description": "Rate from the last two pulses, per hour; unit set by the connected meter.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14034,
   "documented": "14034",
   "name": "Ch 7 I2 power or flow indicator",
   "description": "Rate from the last two pulses, per hour; unit set by the connected meter.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14036,
   "documented": "14036",
   "name": "Ch 8 I2 power or flow indicator",
   "description": "Rate from the last two pulses, per hour; unit set by the connected meter.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14038,
   "documented": "14038",
   "name": "Ch 9 I2 power or flow indicator",
   "description": "Rate from the last two pulses, per hour; unit set by the connected meter.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14040,
   "documented": "14040",
   "name": "Ch 10 I2 power or flow indicator",
   "description": "Rate from the last two pulses, per hour; unit set by the connected meter.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14042,
   "documented": "14042",
   "name": "Ch 11 I2 power or flow indicator",
   "description": "Rate from the last two pulses, per hour; unit set by the connected meter.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14050,
   "documented": "14050",
   "name": "Ch 1 I1 consumption meter",
   "description": "Pulse total times pulse weight.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14052,
   "documented": "14052",
   "name": "Ch 2 I1 consumption meter",
   "description": "Pulse total times pulse weight.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14054,
   "documented": "14054",
   "name": "Ch 3 I1 consumption meter",
   "description": "Pulse total times pulse weight.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14056,
   "documented": "14056",
   "name": "Ch 4 I1 consumption meter",
   "description": "Pulse total times pulse weight.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14058,
   "documented": "14058",
   "name": "Ch 5 I1 consumption meter",
   "description": "Pulse total times pulse weight.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14060,
   "documented": "14060",
   "name": "Ch 6 I1 consumption meter",
   "description": "Pulse total times pulse weight.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14062,
   "documented": "14062",
   "name": "Ch 7 I1 consumption meter",
   "description": "Pulse total times pulse weight.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14064,
   "documented": "14064",
   "name": "Ch 8 I1 consumption meter",
   "description": "Pulse total times pulse weight.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14066,
   "documented": "14066",
   "name": "Ch 9 I1 consumption meter",
   "description": "Pulse total times pulse weight.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14068,
   "documented": "14068",
   "name": "Ch 10 I1 consumption meter",
   "description": "Pulse total times pulse weight.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14070,
   "documented": "14070",
   "name": "Ch 11 I1 consumption meter",
   "description": "Pulse total times pulse weight.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14072,
   "documented": "14072",
   "name": "Ch 1 I2 consumption meter",
   "description": "Pulse total times pulse weight.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14074,
   "documented": "14074",
   "name": "Ch 2 I2 consumption meter",
   "description": "Pulse total times pulse weight.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14076,
   "documented": "14076",
   "name": "Ch 3 I2 consumption meter",
   "description": "Pulse total times pulse weight.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14078,
   "documented": "14078",
   "name": "Ch 4 I2 consumption meter",
   "description": "Pulse total times pulse weight.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14080,
   "documented": "14080",
   "name": "Ch 5 I2 consumption meter",
   "description": "Pulse total times pulse weight.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14082,
   "documented": "14082",
   "name": "Ch 6 I2 consumption meter",
   "description": "Pulse total times pulse weight.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14084,
   "documented": "14084",
   "name": "Ch 7 I2 consumption meter",
   "description": "Pulse total times pulse weight.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14086,
   "documented": "14086",
   "name": "Ch 8 I2 consumption meter",
   "description": "Pulse total times pulse weight.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14088,
   "documented": "14088",
   "name": "Ch 9 I2 consumption meter",
   "description": "Pulse total times pulse weight.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14090,
   "documented": "14090",
   "name": "Ch 10 I2 consumption meter",
   "description": "Pulse total times pulse weight.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14092,
   "documented": "14092",
   "name": "Ch 11 I2 consumption meter",
   "description": "Pulse total times pulse weight.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14100,
   "documented": "14100",
   "name": "Ch 1 I1 operation counter",
   "description": "Counts input changes from 1 to 0; writable to preset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14102,
   "documented": "14102",
   "name": "Ch 2 I1 operation counter",
   "description": "Counts input changes from 1 to 0; writable to preset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14104,
   "documented": "14104",
   "name": "Ch 3 I1 operation counter",
   "description": "Counts input changes from 1 to 0; writable to preset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14106,
   "documented": "14106",
   "name": "Ch 4 I1 operation counter",
   "description": "Counts input changes from 1 to 0; writable to preset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14108,
   "documented": "14108",
   "name": "Ch 5 I1 operation counter",
   "description": "Counts input changes from 1 to 0; writable to preset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14110,
   "documented": "14110",
   "name": "Ch 6 I1 operation counter",
   "description": "Counts input changes from 1 to 0; writable to preset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14112,
   "documented": "14112",
   "name": "Ch 7 I1 operation counter",
   "description": "Counts input changes from 1 to 0; writable to preset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14114,
   "documented": "14114",
   "name": "Ch 8 I1 operation counter",
   "description": "Counts input changes from 1 to 0; writable to preset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14116,
   "documented": "14116",
   "name": "Ch 9 I1 operation counter",
   "description": "Counts input changes from 1 to 0; writable to preset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14118,
   "documented": "14118",
   "name": "Ch 10 I1 operation counter",
   "description": "Counts input changes from 1 to 0; writable to preset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14120,
   "documented": "14120",
   "name": "Ch 11 I1 operation counter",
   "description": "Counts input changes from 1 to 0; writable to preset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14144,
   "documented": "14144",
   "name": "Ch 1 I1 running hours",
   "description": "Hours with input I1 active; writable to preset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "h",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14146,
   "documented": "14146",
   "name": "Ch 2 I1 running hours",
   "description": "Hours with input I1 active; writable to preset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "h",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14148,
   "documented": "14148",
   "name": "Ch 3 I1 running hours",
   "description": "Hours with input I1 active; writable to preset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "h",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14150,
   "documented": "14150",
   "name": "Ch 4 I1 running hours",
   "description": "Hours with input I1 active; writable to preset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "h",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14152,
   "documented": "14152",
   "name": "Ch 5 I1 running hours",
   "description": "Hours with input I1 active; writable to preset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "h",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14154,
   "documented": "14154",
   "name": "Ch 6 I1 running hours",
   "description": "Hours with input I1 active; writable to preset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "h",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14156,
   "documented": "14156",
   "name": "Ch 7 I1 running hours",
   "description": "Hours with input I1 active; writable to preset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "h",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14158,
   "documented": "14158",
   "name": "Ch 8 I1 running hours",
   "description": "Hours with input I1 active; writable to preset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "h",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14160,
   "documented": "14160",
   "name": "Ch 9 I1 running hours",
   "description": "Hours with input I1 active; writable to preset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "h",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14162,
   "documented": "14162",
   "name": "Ch 10 I1 running hours",
   "description": "Hours with input I1 active; writable to preset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "h",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14164,
   "documented": "14164",
   "name": "Ch 11 I1 running hours",
   "description": "Hours with input I1 active; writable to preset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "h",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14200,
   "documented": "14200",
   "name": "Ch 1 input status",
   "description": "Add 40 x (n-1) for channel n.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Input I1 level (1 = current)",
    "1": "Input I2 level (1 = current)"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14201,
   "documented": "14201",
   "name": "Ch 1 order, Acti 9 product",
   "description": "Add 40 x (n-1) for channel n.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Close order",
    "1": "Open order"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14202,
   "documented": "14202",
   "name": "Ch 1 order, non-Acti 9 product",
   "description": "Add 40 x (n-1) for channel n.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Deactivation order",
    "1": "Activation order"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14214,
   "documented": "14214",
   "name": "Ch 1 I2 operation counter",
   "description": "Add 40 x (n-1) for channel n.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14230,
   "documented": "14230",
   "name": "Ch 1 I1 pulse weight",
   "description": "Default 10; add 40 x (n-1) for channel n.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14231,
   "documented": "14231",
   "name": "Ch 1 I2 pulse weight",
   "description": "Default 10; add 40 x (n-1) for channel n.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 20035,
   "documented": "20035",
   "name": "Ch 1 I1 product type",
   "description": "Configured device on channel 1 input 1.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "None",
    "1": "Standard IO",
    "2": "Standard pulse counter",
    "3": "OF+SD24",
    "4": "iOF+SD24",
    "5": "Reflex iC60",
    "6": "RCA iC60",
    "7": "iACT24",
    "8": "iATL24",
    "10": "PM3210",
    "12": "PM3255",
    "13": "iEM3110",
    "15": "iEM3155",
    "16": "iEM3210",
    "18": "iEM3255",
    "19": "iEM2000T",
    "25": "Breaker IO",
    "27": "iEM3355"
   },
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Read 120-121 for all input states, 14050-14093 for every channel's energy/pulse totals and 14000-14043 for rates; write bits in 130/131 to open or close Acti 9 devices.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 112,
    "why": "Module health"
   },
   {
    "table": "holding_register",
    "address": 120,
    "why": "Input 1 state of all channels"
   },
   {
    "table": "holding_register",
    "address": 121,
    "why": "Input 2 state of all channels"
   },
   {
    "table": "holding_register",
    "address": 130,
    "why": "Open orders"
   },
   {
    "table": "holding_register",
    "address": 131,
    "why": "Close orders"
   },
   {
    "table": "holding_register",
    "address": 14050,
    "why": "Channel 1 meter total"
   }
  ],
  "enable": "Set the Modbus address (01-99) on the two thumbwheels. Speed, parity and stop bits are picked up from the master automatically at power-up.",
  "watchdog": null,
  "quirks": [
   "Addresses are protocol (0-based) addresses.",
   "Order bits are cleared by the Smartlink once executed.",
   "In a channel order register (14201 / 14202), setting bit 0 and bit 1 together has no effect."
  ],
  "setup": [
   "Thumbwheels: left = tens, right = units (01-99).",
   "Default 19200 baud, even parity, 1 stop bit; 4800 and 9600 also supported.",
   "Factory reset: power off, set address 00, power on."
  ],
  "gotchas": [
   "Auto-adaptation only happens at power-up.",
   "Pulse weights default to 10; set 14230/14231 per channel to match the meter."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/schneider-electric/acti9-smartlink-modbus",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}