 "manufacturer": "Schneider Electric",
 "manufacturer_slug": "schneider-electric",
 "model": "Altivar Machine ATV340 (embedded Modbus serial / Modbus TCP)",
 "model_slug": "atv340",
 "short_model": "ATV340",
 "aliases": [
  "ATV340",
  "Altivar 340",
  "Altivar Machine ATV340",
  "ATV340U",
  "ATV340D",
  "ATV340...N4E"
 ],
 "equipment_type": "Variable frequency drive",
 "applies_to": "ATV340 drives on the built-in Modbus serial port; Ethernet versions (ATV340...N4E) expose the same addresses on embedded Modbus TCP. Per Communication Parameters file NVE61728 V4.6.",
 "summary": "Schneider Electric's high-performance machine drive with Modbus RTU on the built-in serial port, plus embedded Ethernet on the N4E versions. Each parameter has a fixed decimal logical address sent as the holding-register address. This map covers the CiA402 command and status words, frequency and speed references, the main monitors, energy counters, fault and warning codes, I/O states and the Modbus and channel settings needed for network control.",
 "transport": [
  "RTU",
  "TCP"
 ],
 "defaults": {
  "unit_id": null,
  "baud": 19200,
  "parity": "Even",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "0-based",
  "note": "The parameter file gives each logical address in hex and decimal (16#0C81 = 3201); the decimal value goes into the request unchanged. The Modbus serial manual's example reads W3102-W3105 by sending start address 0C1E hex (= 3102) and writes W9001 at 2329 hex, so there is no 40001 offset and no minus 1."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "ATV340 - Communication Parameters (Excel)",
  "doc_number": "NVE61728 V4.6",
  "revision_date": null,
  "url": "https://download.schneider-electric.com/files?p_Doc_Ref=NVE61728",
  "pages": "Sheet 'Parameters' (code, logic address, access, type, unit, factory, range), sheet 'Enumerations' (HMIS, LFT, ALR, PSA, CDX, TBR, FOR, ECFG, INR, STT, IPM), sheet 'Registers' (CMI, ETI, CRC, CCC, IL1R, OL1R bits). Modbus manual NVE61654 (06/2016): pp. 31-33 Add/tbr/tFO/ttO, pp. 45-47 CMD and ETA bits and state table, p. 71 M1EC/M1CT."
 },
 "notes": [
  "Second source: Altivar Machine ATV340 Modbus Serial Line Manual NVE61654 (06/2016), https://download.schneider-electric.com/files?p_Doc_Ref=NVE61654 - addressing examples, function codes, settings, the CiA402 sequence and the CMD/ETA bit layout (the parameter file does not break these two words out bit by bit).",
  "Every register in this map is a single 16-bit word. 32-bit values (RTH motor run time 3244, PTH power-on time 3246, both UINT32 in seconds) are left out because neither document states their word order.",
  "LFR (8502) and RFR (3202) are 0.1 Hz only while CMI bit 9 = 0; with bit 9 = 1 they become a signed value where 32767 = tFr. The parameter file states this in the CMI bit 9 description.",
  "LCR (3204) is left unscaled: the parameter file says 'refer to programming manual' and the programming manual (NVE61643) only says the unit follows the drive rating.",
  "ACC/DEC (9001/9002) are raw values; their resolution follows INR (9020): 0 = 0.01 s, 1 = 0.1 s (factory), 2 = 1 s.",
  "Energy is split into 0-999 registers per decade: motor energy = OC4 TWh + OC3 GWh + OC2 MWh + OC1 kWh + OC0 Wh; input energy likewise with IC0-IC4.",
  "Value lists for HMIS, LFT/DP0-DP3, LALR, FR1 (PSA list), CD1, TBR and the stop/fault reactions are copied from the Enumerations sheet.",
  "Registers shown as RW that the file lists as R/WS can only be written while the drive is not running.",
  "Left out: NCR, ITH, AI physical values, PID feedback/reference and SPD because their unit is 'refer to programming manual'; option-card, safety and function-block parameters.",
  "ETHL, IM00 and TTOB only apply to the Ethernet versions (ATV340...N4E). Neither source states the Modbus TCP port, so tcp_port is left null.",
  "Ethernet manual NVE61653 (12/2018, https://download.schneider-electric.com/files?p_Doc_Ref=NVE61653): on Modbus TCP, Unit ID 0 or 248 reaches the drive parameters at the same logical addresses; Unit ID 255 is the I/O scanner."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 3102,
   "documented": "3102",
   "name": "SFR - Switching frequency",
   "description": "Range 2.0 kHz to 16.0 kHz.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "kHz",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3103,
   "documented": "3103",
   "name": "TFR - Max frequency",
   "description": "Range 10.0 Hz to 599.0 Hz. Write only when stopped.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "Hz",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3104,
   "documented": "3104",
   "name": "HSP - High speed",
   "description": "Range 0.0 Hz to 599.0 Hz.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "Hz",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3105,
   "documented": "3105",
   "name": "LSP - Low speed",
   "description": "Range 0.0 Hz to 599.0 Hz.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "Hz",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3201,
   "documented": "3201",
   "name": "ETA - Status Register",
   "description": "CiA402 status word.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Ready to switch on",
    "1": "Switched on",
    "2": "Operation enabled (running)",
    "3": "Fault",
    "4": "Voltage enabled (power stage supplied)",
    "5": "Quick stop (0 = quick stop active)",
    "6": "Switch on disabled",
    "7": "Warning active",
    "9": "Remote: command or reference via network",
    "10": "Target reference reached",
    "11": "Reference outside LSP/HSP limits",
    "14": "Stop via STOP key",
    "15": "Reverse rotation at output"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3202,
   "documented": "3202",
   "name": "RFR - Motor frequency",
   "description": "Signed; 0.1 Hz while CMI bit 9 = 0.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3203,
   "documented": "3203",
   "name": "FRH - Reference frequency before ramp",
   "description": "Range -599.0 Hz to 599.0 Hz.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3204,
   "documented": "3204",
   "name": "LCR - Motor current",
   "description": "Raw; resolution depends on drive rating (see notes).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3205,
   "documented": "3205",
   "name": "OTR - Motor torque",
   "description": "Range -3276.7 % to 3276.7 %.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3206,
   "documented": "3206",
   "name": "ETI - Internal State register",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Access to the EEPROM non-volatile memory in progress"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3207,
   "documented": "3207",
   "name": "ULN - Mains voltage",
   "description": "Range 0.0 V to 6553.5 V.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3208,
   "documented": "3208",
   "name": "UOP - Motor voltage",
   "description": "Range 0 V to 65535 V.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3209,
   "documented": "3209",
   "name": "THD - Drive thermal state",
   "description": "Range 0 % to 200 %.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3211,
   "documented": "3211",
   "name": "OPR - Motor power in %",
   "description": "Range -32767 % to 32767 %.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3240,
   "documented": "3240",
   "name": "HMIS - Device state",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Drive automatic tuning (TUN)",
    "1": "DC injection (DCB)",
    "2": "Ready (RDY)",
    "3": "Freewheel stop (NST)",
    "4": "Running (RUN)",
    "5": "Accelerating (ACC)",
    "6": "Decelerating (DEC)",
    "7": "In current limitation (CLI)",
    "8": "Fast stop (FST)",
    "9": "Motor fluxing (FLU)",
    "11": "No mains voltage (NLP)",
    "13": "Control stopping (CTL)",
    "14": "Dec ramp adaptation (OBR)",
    "15": "Output cut (SOC)",
    "17": "Undervoltage warning (USA)",
    "18": "TC mode active (TC)",
    "19": "In autotest (ST)",
    "20": "Autotest error (FA)",
    "21": "Autotest OK (OK)",
    "22": "EEprom test (EP)",
    "23": "Operating state \"Fault\" (FLT)",
    "25": "DCP Flashing mode (DCP)",
    "28": "SS1 active (SS1)",
    "29": "SLS active (SLS)",
    "30": "STO active (STO)",
    "36": "Firmware Update (FWUP)",
    "38": "Angle test (ASA)",
    "40": "SOS active (SOS)",
    "41": "SS2 active (SS2)",
    "42": "SMS active (SMS)",
    "43": "Safety configuration test (SCTP)",
    "44": "Safety function (SFTY)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3243,
   "documented": "3243",
   "name": "VBUS - DC bus voltage",
   "description": "Range 0.0 V to 6553.5 V.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3263,
   "documented": "3263",
   "name": "FSPD - Fan speed",
   "description": "Range 0 rpm to 65535 rpm.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "rpm",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3297,
   "documented": "3297",
   "name": "EPR - Active Electrical output power in %",
   "description": "Range -300 % to 300 %.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5202,
   "documented": "5202",
   "name": "IL1R - Logic inputs states",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "LI1 input state",
    "1": "LI2 input state",
    "2": "LI3 input state",
    "3": "LI4 input state",
    "4": "LI5 input state",
    "5": "LI6 input state",
    "6": "LI7 input state",
    "7": "LI8 input state",
    "10": "LI11 input state",
    "11": "LI12 input state",
    "12": "LI13 input state",
    "13": "LI14 input state",
    "14": "LI15 input state",
    "15": "LI16 input state"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5212,
   "documented": "5212",
   "name": "OL1R - Logic outputs states",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "R1 relay state",
    "1": "R2 relay state",
    "2": "R3 relay state",
    "3": "R4 relay state",
    "4": "R5 relay state",
    "5": "R6 relay state",
    "8": "DO1 output state",
    "9": "DO2 output state",
    "12": "DO11 output state",
    "13": "DO12 output state"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6001,
   "documented": "6001",
   "name": "ADD - Device modbus address",
   "description": "Range 0 to 247. Factory 0. Write only when stopped.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6003,
   "documented": "6003",
   "name": "TBR - Modbus baud rate",
   "description": "Factory [19200 bps]. Write only when stopped.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "4": "Automatic (AUTO)",
    "8": "300 bps (300)",
    "12": "600 bps (600)",
    "16": "1.2 Kbps (1200)",
    "20": "2.4 Kbps (2400)",
    "24": "4800 bps (4800)",
    "28": "9600 bps (9600)",
    "30": "10 Kbps (10000)",
    "32": "19200 bps (19200)",
    "34": "20 Kbps (20000)",
    "35": "28.8 Kbps (28800)",
    "36": "38.4 Kbps (38400)",
    "37": "45.45 Kbps (45450)",
    "38": "50 Kbps (50000)",
    "40": "57.6 Kbps (57600)",
    "41": "76.8 Kbps (76800)",
    "42": "93.75 Kbps (93750)",
    "44": "100 Kbps (100K)",
    "48": "115.2 Kbps (115K2)",
    "52": "125 Kbps (125K)",
    "53": "156 Kbps (156K)",
    "54": "187.5 Kbps (187K5)",
    "56": "230.4 Kbps (230K4)",
    "60": "250 Kbps (250K)",
    "64": "460.8 Kbps (460K8)",
    "68": "500 Kbps (500K)",
    "69": "625 Kbps (625K)",
    "70": "800 Kbps (800K)",
    "72": "921.6 Kbps (921K6)",
    "76": "1 Mbps (1M)",
    "80": "1.5 Mbps (1M5)",
    "81": "2.5 Mbps (2M5)",
    "82": "3 Mbps (3M)",
    "83": "6 Mbps (6M)",
    "84": "10 Mbps (10M)",
    "86": "5 Mbps (5M)",
    "88": "12 Mbps (12M)",
    "92": "100 Mbps (100M)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6004,
   "documented": "6004",
   "name": "TFO - Modbus format",
   "description": "Factory [8 bits even parity 1 stop bit]. Write only when stopped.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "2": "8bit odd parity 1stop bit (8O1)",
    "3": "8 bits even parity 1 stop bit (8E1)",
    "4": "8bit no parity 1stop bit (8N1)",
    "5": "8bit no parity 2stop bits (8N2)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6005,
   "documented": "6005",
   "name": "TTO - Modbus timeout",
   "description": "Range 0.1 s to 30.0 s. Factory 10.0 s. Write only when stopped.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6010,
   "documented": "6010",
   "name": "M1EC - Mdb CRC errors",
   "description": "Range 0 to 65535.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6011,
   "documented": "6011",
   "name": "M1CT - Mdb frame number",
   "description": "Range 0 to 65535.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 7010,
   "documented": "7010",
   "name": "SLL - Response to Modbus interruption",
   "description": "Factory [Freewheel stop]. Write only when stopped.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Ignore (NO)",
    "1": "Freewheel stop (YES)",
    "2": "Configured stop [STT] parameter (STT)",
    "4": "Fallback speed (LFF)",
    "5": "Speed maintained (RLS)",
    "6": "Ramp stop (RMP)",
    "7": "Fast stop (FST)",
    "8": "DC injection (DCI)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 7021,
   "documented": "7021",
   "name": "ETHL - Ethernet error response",
   "description": "Factory [Freewheel stop]. Write only when stopped.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Ignore (NO)",
    "1": "Freewheel stop (YES)",
    "2": "Configured stop [STT] parameter (STT)",
    "4": "Fallback speed (LFF)",
    "5": "Speed maintained (RLS)",
    "6": "Ramp stop (RMP)",
    "7": "Fast stop (FST)",
    "8": "DC injection (DCI)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 7080,
   "documented": "7080",
   "name": "LFF - Fall back speed",
   "description": "Range 0.0 Hz to 599.0 Hz. Factory 0.0 Hz. Write only when stopped.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "Hz",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 7121,
   "documented": "7121",
   "name": "LFT - Last error occurred",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No error detected (NOF)",
    "2": "Control memory error (EEF1)",
    "3": "Incorrect configuration (CFF)",
    "4": "Invalid configuration (CFI)",
    "5": "Modbus communication interruption (SLF1)",
    "6": "Internal communication interruption with option module (ILF)",
    "7": "Fieldbus communication interruption (CNF)",
    "8": "External detected error (EPF1)",
    "9": "Overcurrent (OCF)",
    "10": "Precharge capacitor (CRF1)",
    "11": "Encoder feedback loss (SPF)",
    "12": "Load slipping (ANF)",
    "15": "Input Overheating (IHF)",
    "16": "Device overheating (OHF)",
    "17": "Motor overload (OLF)",
    "18": "DC bus overvoltage (OBF)",
    "19": "Supply mains overvoltage (OSF)",
    "20": "Single output phase loss (OPF1)",
    "21": "Input phase loss (PHF)",
    "22": "Supply mains undervoltage (USF)",
    "23": "Motor short circuit (SCF1)",
    "24": "Motor overspeed (SOF)",
    "25": "Autotuning detected error (TNF)",
    "26": "Internal error 1 (Rating) (INF1)",
    "27": "Internal error 2 (Soft) (INF2)",
    "28": "Internal error 3 (Intern Comm) (INF3)",
    "29": "Internal error 4 (Manufacturing) (INF4)",
    "30": "Power memory error (EEF2)",
    "32": "Ground short circuit (SCF3)",
    "33": "Output phase loss (OPF2)",
    "34": "CANopen communication interruption (COF)",
    "35": "Brake control (BLF)",
    "37": "Internal error 7 (Init) (INF7)",
    "38": "External error detected by Fieldbus (EPF2)",
    "40": "Internal error 8 (Switching Supply) (INF8)",
    "41": "Brake feedback (BRF)",
    "42": "PC communication interruption (SLF2)",
    "43": "Encoder coupling (ECF)",
    "44": "Torque limitation error (SSF)",
    "45": "HMI communication interruption (SLF3)",
    "51": "Internal error 9 (Measure) (INF9)",
    "52": "Internal error 10 (Mains) (INFA)",
    "53": "Internal error 11 (Temperature) (INFB)",
    "54": "Device overheating (TJF)",
    "55": "IGBT short circuit (SCF4)",
    "56": "Motor short circuit (SCF5)",
    "57": "Torque timeout (SRF)",
    "58": "Output contactor closed error (FCF1)",
    "59": "Output contactor opened error (FCF2)",
    "60": "Internal error 12 (Internal current supply) (INFC)",
    "62": "Encoder (ENF)",
    "64": "input contactor (LCF)",
    "65": "DB unit sh. circuit (BUF)",
    "68": "Internal error 6 (Option) (INF6)",
    "69": "Internal error 14 (CPU) (INFE)",
    "70": "Braking resistor overload (BOF)",
    "71": "AI3 4-20mA loss (LFF3)",
    "72": "AI4 4-20mA loss (LFF4)",
    "73": "Boards compatibility (HCF)",
    "76": "Dynamic load detected error (DLF)",
    "77": "Configuration transfer error (CFI2)",
    "79": "AI5 4-20 mA loss (LFF5)",
    "82": "ON lock error (LKON)",
    "99": "Channel switching detected error (CSF)",
    "100": "Process underload (ULF)",
    "101": "Process overload (OLC)",
    "105": "Angle error (ASF)",
    "106": "AI1 4-20 mA loss (LFF1)",
    "107": "Safety function detected error (SAFF)",
    "112": "AI3 thermal level error (TH3F)",
    "113": "Thermal sensor error on AI3 (T3CF)",
    "120": "AI4 thermal level error (TH4F)",
    "121": "Thermal sensor error on AI4 (T4CF)",
    "122": "AI5 thermal level error (TH5F)",
    "123": "Thermal sensor error on AI5 (T5CF)",
    "128": "Program loading detected error (PGLF)",
    "129": "Program running detected error (PGRF)",
    "133": "Safety violation (SAVF)",
    "134": "Safety configuration error (SCFF)",
    "135": "Safety IO error (SIOF)",
    "142": "Internal error 16 (IO module - relay) (INFG)",
    "143": "Internal error 17 (IO module - Standard) (INFH)",
    "144": "Internal error 0 (IPC) (INF0)",
    "146": "Internal error 13 (Diff current) (INFD)",
    "147": "Internal error 18 (Safety function module) (INFI)",
    "148": "Motor stall detected error (STF)",
    "149": "Internal error 21 (RTC) (INFL)",
    "150": "Embedded Ethernet communication interruption (ETHF)",
    "151": "Internal error 15 (Flash) (INFF)",
    "152": "Firmware Update error (FWER)",
    "153": "Internal error 22 (Embedded Ethernet) (INFM)",
    "154": "Internal error 25 (Incompatibility CB & SW) (INFP)",
    "155": "Internal error 20 (option interface PCBA) (INFK)",
    "156": "Internal error 19 (Encoder module) (INFJ)",
    "157": "Internal error 27 (Diagnostics CPLD) (INFR)",
    "158": "Internal error 23 (Module link) (INFN)",
    "159": "AFE ShortCircuit error (SCF6)",
    "160": "AFE Bus unbalancing (OBF2)",
    "161": "Internal error 28 (AFE) (INFS)",
    "162": "Monitoring circuit A error (IFA)",
    "163": "Monitoring circuit B error (IFB)",
    "164": "Monitoring circuit C error (IFC)",
    "165": "Monitoring circuit D error (IFD)",
    "173": "Cabinet overheat error (CHF)",
    "175": "Internal error 31 (Missing brick) (INFV)",
    "176": "Internal error 29 (Inverter) (INFT)",
    "177": "Internal error 30 (Rectifier) (INFU)",
    "179": "AFE IGBT over-heat error (TJF2)",
    "180": "AFE contactor feedback error (CRF3)",
    "181": "Pre-settings transfer error (CFI3)",
    "182": "Circuit breaker error (CBF)",
    "184": "DB unit open circuit (BUFO)",
    "185": "Drive overload (TLOF)",
    "186": "MultiDrive Link error (MDLF)",
    "187": "AI1 thermal level error (TH1F)",
    "188": "Thermal sensor error on AI1 (T1CF)",
    "189": "Backlash error (BSQF)",
    "190": "M/S device error (MSDF)",
    "194": "Encoder module thermal level error (THEF)",
    "195": "Thermal sensor error on encoder module (TECF)",
    "196": "Empty configuration (CFI4)",
    "200": "FDR Eth embedded error (FDR1)",
    "201": "FDR Eth module error (FDR2)",
    "206": "DC Bus ripple error (DCRE)",
    "208": "Idle mode exit error (IDLF)",
    "209": "Load movement error (MDCF)",
    "211": "Security files corrupt (SPFC)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 7200,
   "documented": "7200",
   "name": "DP0 - Fault code on last fault",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No error detected (NOF)",
    "2": "Control memory error (EEF1)",
    "3": "Incorrect configuration (CFF)",
    "4": "Invalid configuration (CFI)",
    "5": "Modbus communication interruption (SLF1)",
    "6": "Internal communication interruption with option module (ILF)",
    "7": "Fieldbus communication interruption (CNF)",
    "8": "External detected error (EPF1)",
    "9": "Overcurrent (OCF)",
    "10": "Precharge capacitor (CRF1)",
    "11": "Encoder feedback loss (SPF)",
    "12": "Load slipping (ANF)",
    "15": "Input Overheating (IHF)",
    "16": "Device overheating (OHF)",
    "17": "Motor overload (OLF)",
    "18": "DC bus overvoltage (OBF)",
    "19": "Supply mains overvoltage (OSF)",
    "20": "Single output phase loss (OPF1)",
    "21": "Input phase loss (PHF)",
    "22": "Supply mains undervoltage (USF)",
    "23": "Motor short circuit (SCF1)",
    "24": "Motor overspeed (SOF)",
    "25": "Autotuning detected error (TNF)",
    "26": "Internal error 1 (Rating) (INF1)",
    "27": "Internal error 2 (Soft) (INF2)",
    "28": "Internal error 3 (Intern Comm) (INF3)",
    "29": "Internal error 4 (Manufacturing) (INF4)",
    "30": "Power memory error (EEF2)",
    "32": "Ground short circuit (SCF3)",
    "33": "Output phase loss (OPF2)",
    "34": "CANopen communication interruption (COF)",
    "35": "Brake control (BLF)",
    "37": "Internal error 7 (Init) (INF7)",
    "38": "External error detected by Fieldbus (EPF2)",
    "40": "Internal error 8 (Switching Supply) (INF8)",
    "41": "Brake feedback (BRF)",
    "42": "PC communication interruption (SLF2)",
    "43": "Encoder coupling (ECF)",
    "44": "Torque limitation error (SSF)",
    "45": "HMI communication interruption (SLF3)",
    "51": "Internal error 9 (Measure) (INF9)",
    "52": "Internal error 10 (Mains) (INFA)",
    "53": "Internal error 11 (Temperature) (INFB)",
    "54": "Device overheating (TJF)",
    "55": "IGBT short circuit (SCF4)",
    "56": "Motor short circuit (SCF5)",
    "57": "Torque timeout (SRF)",
    "58": "Output contactor closed error (FCF1)",
    "59": "Output contactor opened error (FCF2)",
    "60": "Internal error 12 (Internal current supply) (INFC)",
    "62": "Encoder (ENF)",
    "64": "input contactor (LCF)",
    "65": "DB unit sh. circuit (BUF)",
    "68": "Internal error 6 (Option) (INF6)",
    "69": "Internal error 14 (CPU) (INFE)",
    "70": "Braking resistor overload (BOF)",
    "71": "AI3 4-20mA loss (LFF3)",
    "72": "AI4 4-20mA loss (LFF4)",
    "73": "Boards compatibility (HCF)",
    "76": "Dynamic load detected error (DLF)",
    "77": "Configuration transfer error (CFI2)",
    "79": "AI5 4-20 mA loss (LFF5)",
    "82": "ON lock error (LKON)",
    "99": "Channel switching detected error (CSF)",
    "100": "Process underload (ULF)",
    "101": "Process overload (OLC)",
    "105": "Angle error (ASF)",
    "106": "AI1 4-20 mA loss (LFF1)",
    "107": "Safety function detected error (SAFF)",
    "112": "AI3 thermal level error (TH3F)",
    "113": "Thermal sensor error on AI3 (T3CF)",
    "120": "AI4 thermal level error (TH4F)",
    "121": "Thermal sensor error on AI4 (T4CF)",
    "122": "AI5 thermal level error (TH5F)",
    "123": "Thermal sensor error on AI5 (T5CF)",
    "128": "Program loading detected error (PGLF)",
    "129": "Program running detected error (PGRF)",
    "133": "Safety violation (SAVF)",
    "134": "Safety configuration error (SCFF)",
    "135": "Safety IO error (SIOF)",
    "142": "Internal error 16 (IO module - relay) (INFG)",
    "143": "Internal error 17 (IO module - Standard) (INFH)",
    "144": "Internal error 0 (IPC) (INF0)",
    "146": "Internal error 13 (Diff current) (INFD)",
    "147": "Internal error 18 (Safety function module) (INFI)",
    "148": "Motor stall detected error (STF)",
    "149": "Internal error 21 (RTC) (INFL)",
    "150": "Embedded Ethernet communication interruption (ETHF)",
    "151": "Internal error 15 (Flash) (INFF)",
    "152": "Firmware Update error (FWER)",
    "153": "Internal error 22 (Embedded Ethernet) (INFM)",
    "154": "Internal error 25 (Incompatibility CB & SW) (INFP)",
    "155": "Internal error 20 (option interface PCBA) (INFK)",
    "156": "Internal error 19 (Encoder module) (INFJ)",
    "157": "Internal error 27 (Diagnostics CPLD) (INFR)",
    "158": "Internal error 23 (Module link) (INFN)",
    "159": "AFE ShortCircuit error (SCF6)",
    "160": "AFE Bus unbalancing (OBF2)",
    "161": "Internal error 28 (AFE) (INFS)",
    "162": "Monitoring circuit A error (IFA)",
    "163": "Monitoring circuit B error (IFB)",
    "164": "Monitoring circuit C error (IFC)",
    "165": "Monitoring circuit D error (IFD)",
    "173": "Cabinet overheat error (CHF)",
    "175": "Internal error 31 (Missing brick) (INFV)",
    "176": "Internal error 29 (Inverter) (INFT)",
    "177": "Internal error 30 (Rectifier) (INFU)",
    "179": "AFE IGBT over-heat error (TJF2)",
    "180": "AFE contactor feedback error (CRF3)",
    "181": "Pre-settings transfer error (CFI3)",
    "182": "Circuit breaker error (CBF)",
    "184": "DB unit open circuit (BUFO)",
    "185": "Drive overload (TLOF)",
    "186": "MultiDrive Link error (MDLF)",
    "187": "AI1 thermal level error (TH1F)",
    "188": "Thermal sensor error on AI1 (T1CF)",
    "189": "Backlash error (BSQF)",
    "190": "M/S device error (MSDF)",
    "194": "Encoder module thermal level error (THEF)",
    "195": "Thermal sensor error on encoder module (TECF)",
    "196": "Empty configuration (CFI4)",
    "200": "FDR Eth embedded error (FDR1)",
    "201": "FDR Eth module error (FDR2)",
    "206": "DC Bus ripple error (DCRE)",
    "208": "Idle mode exit error (IDLF)",
    "209": "Load movement error (MDCF)",
    "211": "Security files corrupt (SPFC)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 7201,
   "documented": "7201",
   "name": "DP1 - Fault code on fault n-1",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No error detected (NOF)",
    "2": "Control memory error (EEF1)",
    "3": "Incorrect configuration (CFF)",
    "4": "Invalid configuration (CFI)",
    "5": "Modbus communication interruption (SLF1)",
    "6": "Internal communication interruption with option module (ILF)",
    "7": "Fieldbus communication interruption (CNF)",
    "8": "External detected error (EPF1)",
    "9": "Overcurrent (OCF)",
    "10": "Precharge capacitor (CRF1)",
    "11": "Encoder feedback loss (SPF)",
    "12": "Load slipping (ANF)",
    "15": "Input Overheating (IHF)",
    "16": "Device overheating (OHF)",
    "17": "Motor overload (OLF)",
    "18": "DC bus overvoltage (OBF)",
    "19": "Supply mains overvoltage (OSF)",
    "20": "Single output phase loss (OPF1)",
    "21": "Input phase loss (PHF)",
    "22": "Supply mains undervoltage (USF)",
    "23": "Motor short circuit (SCF1)",
    "24": "Motor overspeed (SOF)",
    "25": "Autotuning detected error (TNF)",
    "26": "Internal error 1 (Rating) (INF1)",
    "27": "Internal error 2 (Soft) (INF2)",
    "28": "Internal error 3 (Intern Comm) (INF3)",
    "29": "Internal error 4 (Manufacturing) (INF4)",
    "30": "Power memory error (EEF2)",
    "32": "Ground short circuit (SCF3)",
    "33": "Output phase loss (OPF2)",
    "34": "CANopen communication interruption (COF)",
    "35": "Brake control (BLF)",
    "37": "Internal error 7 (Init) (INF7)",
    "38": "External error detected by Fieldbus (EPF2)",
    "40": "Internal error 8 (Switching Supply) (INF8)",
    "41": "Brake feedback (BRF)",
    "42": "PC communication interruption (SLF2)",
    "43": "Encoder coupling (ECF)",
    "44": "Torque limitation error (SSF)",
    "45": "HMI communication interruption (SLF3)",
    "51": "Internal error 9 (Measure) (INF9)",
    "52": "Internal error 10 (Mains) (INFA)",
    "53": "Internal error 11 (Temperature) (INFB)",
    "54": "Device overheating (TJF)",
    "55": "IGBT short circuit (SCF4)",
    "56": "Motor short circuit (SCF5)",
    "57": "Torque timeout (SRF)",
    "58": "Output contactor closed error (FCF1)",
    "59": "Output contactor opened error (FCF2)",
    "60": "Internal error 12 (Internal current supply) (INFC)",
    "62": "Encoder (ENF)",
    "64": "input contactor (LCF)",
    "65": "DB unit sh. circuit (BUF)",
    "68": "Internal error 6 (Option) (INF6)",
    "69": "Internal error 14 (CPU) (INFE)",
    "70": "Braking resistor overload (BOF)",
    "71": "AI3 4-20mA loss (LFF3)",
    "72": "AI4 4-20mA loss (LFF4)",
    "73": "Boards compatibility (HCF)",
    "76": "Dynamic load detected error (DLF)",
    "77": "Configuration transfer error (CFI2)",
    "79": "AI5 4-20 mA loss (LFF5)",
    "82": "ON lock error (LKON)",
    "99": "Channel switching detected error (CSF)",
    "100": "Process underload (ULF)",
    "101": "Process overload (OLC)",
    "105": "Angle error (ASF)",
    "106": "AI1 4-20 mA loss (LFF1)",
    "107": "Safety function detected error (SAFF)",
    "112": "AI3 thermal level error (TH3F)",
    "113": "Thermal sensor error on AI3 (T3CF)",
    "120": "AI4 thermal level error (TH4F)",
    "121": "Thermal sensor error on AI4 (T4CF)",
    "122": "AI5 thermal level error (TH5F)",
    "123": "Thermal sensor error on AI5 (T5CF)",
    "128": "Program loading detected error (PGLF)",
    "129": "Program running detected error (PGRF)",
    "133": "Safety violation (SAVF)",
    "134": "Safety configuration error (SCFF)",
    "135": "Safety IO error (SIOF)",
    "142": "Internal error 16 (IO module - relay) (INFG)",
    "143": "Internal error 17 (IO module - Standard) (INFH)",
    "144": "Internal error 0 (IPC) (INF0)",
    "146": "Internal error 13 (Diff current) (INFD)",
    "147": "Internal error 18 (Safety function module) (INFI)",
    "148": "Motor stall detected error (STF)",
    "149": "Internal error 21 (RTC) (INFL)",
    "150": "Embedded Ethernet communication interruption (ETHF)",
    "151": "Internal error 15 (Flash) (INFF)",
    "152": "Firmware Update error (FWER)",
    "153": "Internal error 22 (Embedded Ethernet) (INFM)",
    "154": "Internal error 25 (Incompatibility CB & SW) (INFP)",
    "155": "Internal error 20 (option interface PCBA) (INFK)",
    "156": "Internal error 19 (Encoder module) (INFJ)",
    "157": "Internal error 27 (Diagnostics CPLD) (INFR)",
    "158": "Internal error 23 (Module link) (INFN)",
    "159": "AFE ShortCircuit error (SCF6)",
    "160": "AFE Bus unbalancing (OBF2)",
    "161": "Internal error 28 (AFE) (INFS)",
    "162": "Monitoring circuit A error (IFA)",
    "163": "Monitoring circuit B error (IFB)",
    "164": "Monitoring circuit C error (IFC)",
    "165": "Monitoring circuit D error (IFD)",
    "173": "Cabinet overheat error (CHF)",
    "175": "Internal error 31 (Missing brick) (INFV)",
    "176": "Internal error 29 (Inverter) (INFT)",
    "177": "Internal error 30 (Rectifier) (INFU)",
    "179": "AFE IGBT over-heat error (TJF2)",
    "180": "AFE contactor feedback error (CRF3)",
    "181": "Pre-settings transfer error (CFI3)",
    "182": "Circuit breaker error (CBF)",
    "184": "DB unit open circuit (BUFO)",
    "185": "Drive overload (TLOF)",
    "186": "MultiDrive Link error (MDLF)",
    "187": "AI1 thermal level error (TH1F)",
    "188": "Thermal sensor error on AI1 (T1CF)",
    "189": "Backlash error (BSQF)",
    "190": "M/S device error (MSDF)",
    "194": "Encoder module thermal level error (THEF)",
    "195": "Thermal sensor error on encoder module (TECF)",
    "196": "Empty configuration (CFI4)",
    "200": "FDR Eth embedded error (FDR1)",
    "201": "FDR Eth module error (FDR2)",
    "206": "DC Bus ripple error (DCRE)",
    "208": "Idle mode exit error (IDLF)",
    "209": "Load movement error (MDCF)",
    "211": "Security files corrupt (SPFC)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 7202,
   "documented": "7202",
   "name": "DP2 - Fault code on fault n-2",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No error detected (NOF)",
    "2": "Control memory error (EEF1)",
    "3": "Incorrect configuration (CFF)",
    "4": "Invalid configuration (CFI)",
    "5": "Modbus communication interruption (SLF1)",
    "6": "Internal communication interruption with option module (ILF)",
    "7": "Fieldbus communication interruption (CNF)",
    "8": "External detected error (EPF1)",
    "9": "Overcurrent (OCF)",
    "10": "Precharge capacitor (CRF1)",
    "11": "Encoder feedback loss (SPF)",
    "12": "Load slipping (ANF)",
    "15": "Input Overheating (IHF)",
    "16": "Device overheating (OHF)",
    "17": "Motor overload (OLF)",
    "18": "DC bus overvoltage (OBF)",
    "19": "Supply mains overvoltage (OSF)",
    "20": "Single output phase loss (OPF1)",
    "21": "Input phase loss (PHF)",
    "22": "Supply mains undervoltage (USF)",
    "23": "Motor short circuit (SCF1)",
    "24": "Motor overspeed (SOF)",
    "25": "Autotuning detected error (TNF)",
    "26": "Internal error 1 (Rating) (INF1)",
    "27": "Internal error 2 (Soft) (INF2)",
    "28": "Internal error 3 (Intern Comm) (INF3)",
    "29": "Internal error 4 (Manufacturing) (INF4)",
    "30": "Power memory error (EEF2)",
    "32": "Ground short circuit (SCF3)",
    "33": "Output phase loss (OPF2)",
    "34": "CANopen communication interruption (COF)",
    "35": "Brake control (BLF)",
    "37": "Internal error 7 (Init) (INF7)",
    "38": "External error detected by Fieldbus (EPF2)",
    "40": "Internal error 8 (Switching Supply) (INF8)",
    "41": "Brake feedback (BRF)",
    "42": "PC communication interruption (SLF2)",
    "43": "Encoder coupling (ECF)",
    "44": "Torque limitation error (SSF)",
    "45": "HMI communication interruption (SLF3)",
    "51": "Internal error 9 (Measure) (INF9)",
    "52": "Internal error 10 (Mains) (INFA)",
    "53": "Internal error 11 (Temperature) (INFB)",
    "54": "Device overheating (TJF)",
    "55": "IGBT short circuit (SCF4)",
    "56": "Motor short circuit (SCF5)",
    "57": "Torque timeout (SRF)",
    "58": "Output contactor closed error (FCF1)",
    "59": "Output contactor opened error (FCF2)",
    "60": "Internal error 12 (Internal current supply) (INFC)",
    "62": "Encoder (ENF)",
    "64": "input contactor (LCF)",
    "65": "DB unit sh. circuit (BUF)",
    "68": "Internal error 6 (Option) (INF6)",
    "69": "Internal error 14 (CPU) (INFE)",
    "70": "Braking resistor overload (BOF)",
    "71": "AI3 4-20mA loss (LFF3)",
    "72": "AI4 4-20mA loss (LFF4)",
    "73": "Boards compatibility (HCF)",
    "76": "Dynamic load detected error (DLF)",
    "77": "Configuration transfer error (CFI2)",
    "79": "AI5 4-20 mA loss (LFF5)",
    "82": "ON lock error (LKON)",
    "99": "Channel switching detected error (CSF)",
    "100": "Process underload (ULF)",
    "101": "Process overload (OLC)",
    "105": "Angle error (ASF)",
    "106": "AI1 4-20 mA loss (LFF1)",
    "107": "Safety function detected error (SAFF)",
    "112": "AI3 thermal level error (TH3F)",
    "113": "Thermal sensor error on AI3 (T3CF)",
    "120": "AI4 thermal level error (TH4F)",
    "121": "Thermal sensor error on AI4 (T4CF)",
    "122": "AI5 thermal level error (TH5F)",
    "123": "Thermal sensor error on AI5 (T5CF)",
    "128": "Program loading detected error (PGLF)",
    "129": "Program running detected error (PGRF)",
    "133": "Safety violation (SAVF)",
    "134": "Safety configuration error (SCFF)",
    "135": "Safety IO error (SIOF)",
    "142": "Internal error 16 (IO module - relay) (INFG)",
    "143": "Internal error 17 (IO module - Standard) (INFH)",
    "144": "Internal error 0 (IPC) (INF0)",
    "146": "Internal error 13 (Diff current) (INFD)",
    "147": "Internal error 18 (Safety function module) (INFI)",
    "148": "Motor stall detected error (STF)",
    "149": "Internal error 21 (RTC) (INFL)",
    "150": "Embedded Ethernet communication interruption (ETHF)",
    "151": "Internal error 15 (Flash) (INFF)",
    "152": "Firmware Update error (FWER)",
    "153": "Internal error 22 (Embedded Ethernet) (INFM)",
    "154": "Internal error 25 (Incompatibility CB & SW) (INFP)",
    "155": "Internal error 20 (option interface PCBA) (INFK)",
    "156": "Internal error 19 (Encoder module) (INFJ)",
    "157": "Internal error 27 (Diagnostics CPLD) (INFR)",
    "158": "Internal error 23 (Module link) (INFN)",
    "159": "AFE ShortCircuit error (SCF6)",
    "160": "AFE Bus unbalancing (OBF2)",
    "161": "Internal error 28 (AFE) (INFS)",
    "162": "Monitoring circuit A error (IFA)",
    "163": "Monitoring circuit B error (IFB)",
    "164": "Monitoring circuit C error (IFC)",
    "165": "Monitoring circuit D error (IFD)",
    "173": "Cabinet overheat error (CHF)",
    "175": "Internal error 31 (Missing brick) (INFV)",
    "176": "Internal error 29 (Inverter) (INFT)",
    "177": "Internal error 30 (Rectifier) (INFU)",
    "179": "AFE IGBT over-heat error (TJF2)",
    "180": "AFE contactor feedback error (CRF3)",
    "181": "Pre-settings transfer error (CFI3)",
    "182": "Circuit breaker error (CBF)",
    "184": "DB unit open circuit (BUFO)",
    "185": "Drive overload (TLOF)",
    "186": "MultiDrive Link error (MDLF)",
    "187": "AI1 thermal level error (TH1F)",
    "188": "Thermal sensor error on AI1 (T1CF)",
    "189": "Backlash error (BSQF)",
    "190": "M/S device error (MSDF)",
    "194": "Encoder module thermal level error (THEF)",
    "195": "Thermal sensor error on encoder module (TECF)",
    "196": "Empty configuration (CFI4)",
    "200": "FDR Eth embedded error (FDR1)",
    "201": "FDR Eth module error (FDR2)",
    "206": "DC Bus ripple error (DCRE)",
    "208": "Idle mode exit error (IDLF)",
    "209": "Load movement error (MDCF)",
    "211": "Security files corrupt (SPFC)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 7203,
   "documented": "7203",
   "name": "DP3 - Fault code on fault n-3",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No error detected (NOF)",
    "2": "Control memory error (EEF1)",
    "3": "Incorrect configuration (CFF)",
    "4": "Invalid configuration (CFI)",
    "5": "Modbus communication interruption (SLF1)",
    "6": "Internal communication interruption with option module (ILF)",
    "7": "Fieldbus communication interruption (CNF)",
    "8": "External detected error (EPF1)",
    "9": "Overcurrent (OCF)",
    "10": "Precharge capacitor (CRF1)",
    "11": "Encoder feedback loss (SPF)",
    "12": "Load slipping (ANF)",
    "15": "Input Overheating (IHF)",
    "16": "Device overheating (OHF)",
    "17": "Motor overload (OLF)",
    "18": "DC bus overvoltage (OBF)",
    "19": "Supply mains overvoltage (OSF)",
    "20": "Single output phase loss (OPF1)",
    "21": "Input phase loss (PHF)",
    "22": "Supply mains undervoltage (USF)",
    "23": "Motor short circuit (SCF1)",
    "24": "Motor overspeed (SOF)",
    "25": "Autotuning detected error (TNF)",
    "26": "Internal error 1 (Rating) (INF1)",
    "27": "Internal error 2 (Soft) (INF2)",
    "28": "Internal error 3 (Intern Comm) (INF3)",
    "29": "Internal error 4 (Manufacturing) (INF4)",
    "30": "Power memory error (EEF2)",
    "32": "Ground short circuit (SCF3)",
    "33": "Output phase loss (OPF2)",
    "34": "CANopen communication interruption (COF)",
    "35": "Brake control (BLF)",
    "37": "Internal error 7 (Init) (INF7)",
    "38": "External error detected by Fieldbus (EPF2)",
    "40": "Internal error 8 (Switching Supply) (INF8)",
    "41": "Brake feedback (BRF)",
    "42": "PC communication interruption (SLF2)",
    "43": "Encoder coupling (ECF)",
    "44": "Torque limitation error (SSF)",
    "45": "HMI communication interruption (SLF3)",
    "51": "Internal error 9 (Measure) (INF9)",
    "52": "Internal error 10 (Mains) (INFA)",
    "53": "Internal error 11 (Temperature) (INFB)",
    "54": "Device overheating (TJF)",
    "55": "IGBT short circuit (SCF4)",
    "56": "Motor short circuit (SCF5)",
    "57": "Torque timeout (SRF)",
    "58": "Output contactor closed error (FCF1)",
    "59": "Output contactor opened error (FCF2)",
    "60": "Internal error 12 (Internal current supply) (INFC)",
    "62": "Encoder (ENF)",
    "64": "input contactor (LCF)",
    "65": "DB unit sh. circuit (BUF)",
    "68": "Internal error 6 (Option) (INF6)",
    "69": "Internal error 14 (CPU) (INFE)",
    "70": "Braking resistor overload (BOF)",
    "71": "AI3 4-20mA loss (LFF3)",
    "72": "AI4 4-20mA loss (LFF4)",
    "73": "Boards compatibility (HCF)",
    "76": "Dynamic load detected error (DLF)",
    "77": "Configuration transfer error (CFI2)",
    "79": "AI5 4-20 mA loss (LFF5)",
    "82": "ON lock error (LKON)",
    "99": "Channel switching detected error (CSF)",
    "100": "Process underload (ULF)",
    "101": "Process overload (OLC)",
    "105": "Angle error (ASF)",
    "106": "AI1 4-20 mA loss (LFF1)",
    "107": "Safety function detected error (SAFF)",
    "112": "AI3 thermal level error (TH3F)",
    "113": "Thermal sensor error on AI3 (T3CF)",
    "120": "AI4 thermal level error (TH4F)",
    "121": "Thermal sensor error on AI4 (T4CF)",
    "122": "AI5 thermal level error (TH5F)",
    "123": "Thermal sensor error on AI5 (T5CF)",
    "128": "Program loading detected error (PGLF)",
    "129": "Program running detected error (PGRF)",
    "133": "Safety violation (SAVF)",
    "134": "Safety configuration error (SCFF)",
    "135": "Safety IO error (SIOF)",
    "142": "Internal error 16 (IO module - relay) (INFG)",
    "143": "Internal error 17 (IO module - Standard) (INFH)",
    "144": "Internal error 0 (IPC) (INF0)",
    "146": "Internal error 13 (Diff current) (INFD)",
    "147": "Internal error 18 (Safety function module) (INFI)",
    "148": "Motor stall detected error (STF)",
    "149": "Internal error 21 (RTC) (INFL)",
    "150": "Embedded Ethernet communication interruption (ETHF)",
    "151": "Internal error 15 (Flash) (INFF)",
    "152": "Firmware Update error (FWER)",
    "153": "Internal error 22 (Embedded Ethernet) (INFM)",
    "154": "Internal error 25 (Incompatibility CB & SW) (INFP)",
    "155": "Internal error 20 (option interface PCBA) (INFK)",
    "156": "Internal error 19 (Encoder module) (INFJ)",
    "157": "Internal error 27 (Diagnostics CPLD) (INFR)",
    "158": "Internal error 23 (Module link) (INFN)",
    "159": "AFE ShortCircuit error (SCF6)",
    "160": "AFE Bus unbalancing (OBF2)",
    "161": "Internal error 28 (AFE) (INFS)",
    "162": "Monitoring circuit A error (IFA)",
    "163": "Monitoring circuit B error (IFB)",
    "164": "Monitoring circuit C error (IFC)",
    "165": "Monitoring circuit D error (IFD)",
    "173": "Cabinet overheat error (CHF)",
    "175": "Internal error 31 (Missing brick) (INFV)",
    "176": "Internal error 29 (Inverter) (INFT)",
    "177": "Internal error 30 (Rectifier) (INFU)",
    "179": "AFE IGBT over-heat error (TJF2)",
    "180": "AFE contactor feedback error (CRF3)",
    "181": "Pre-settings transfer error (CFI3)",
    "182": "Circuit breaker error (CBF)",
    "184": "DB unit open circuit (BUFO)",
    "185": "Drive overload (TLOF)",
    "186": "MultiDrive Link error (MDLF)",
    "187": "AI1 thermal level error (TH1F)",
    "188": "Thermal sensor error on AI1 (T1CF)",
    "189": "Backlash error (BSQF)",
    "190": "M/S device error (MSDF)",
    "194": "Encoder module thermal level error (THEF)",
    "195": "Thermal sensor error on encoder module (TECF)",
    "196": "Empty configuration (CFI4)",
    "200": "FDR Eth embedded error (FDR1)",
    "201": "FDR Eth module error (FDR2)",
    "206": "DC Bus ripple error (DCRE)",
    "208": "Idle mode exit error (IDLF)",
    "209": "Load movement error (MDCF)",
    "211": "Security files corrupt (SPFC)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 7393,
   "documented": "7393",
   "name": "FNB - Fault counter",
   "description": "Range 0 to 65535.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8401,
   "documented": "8401",
   "name": "CHCF - Control mode configuration",
   "description": "Factory [Combined channel mode]. Write only when stopped.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Combined channel mode (SIM)",
    "2": "Separated channel mode (SEP)",
    "3": "I/O mode (IO)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8413,
   "documented": "8413",
   "name": "FR1 - Configuration reference frequency 1",
   "description": "Write only when stopped.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Not configured (NO)",
    "1": "AI1 Analog input (AI1)",
    "2": "AI2 Analog input (AI2)",
    "3": "AI3 Analog input (AI3)",
    "4": "AI4 Analog input (AI4)",
    "5": "AI5 Analog input (AI5)",
    "129": "Motor current (OCR)",
    "130": "Motor frequency (OFR)",
    "131": "Ramp output (ORP)",
    "132": "Motor torque (TRQ)",
    "133": "Signed torque (STQ)",
    "134": "Signed ramp (ORS)",
    "135": "PID reference (OPS)",
    "136": "PID feedback (OPF)",
    "137": "PID error (OPE)",
    "138": "PID output (OPI)",
    "139": "Motor power in % (OPR)",
    "140": "Motor thermal state (THR)",
    "141": "Drive thermal state (THD)",
    "142": "Torque 4Q (TR4Q)",
    "143": "Measured motor frequency (OFRR)",
    "145": "Motor frequency without filter (OFR1)",
    "160": "Reference frequency via DI (UPDT)",
    "163": "Local HMI (LCC)",
    "164": "Reference frequency via Modbus (MDB)",
    "167": "Reference frequency via CANopen (CAN)",
    "169": "Reference frequency via Com module (NET)",
    "171": "Embedded Ethernet (ETH)",
    "173": "Signed output frequency (OFS)",
    "174": "Motor thermal 2 state (THR2)",
    "175": "Motor thermal 3 state (THR3)",
    "176": "Motor thermal 4 state (THR4)",
    "177": "Unsigned torque reference (UTR)",
    "178": "Signed torque reference (STR)",
    "179": "Torque limit (TQL)",
    "180": "Motor voltage (UOP)",
    "183": "AI Virtual 1 (AIV1)",
    "184": "Digital output 1 (DO1)",
    "188": "DI7 pulseInput (PI7)",
    "189": "DI8 pulseInput (PI8)",
    "181": "Pulse input (PI)",
    "182": "Encoder reference (PG)",
    "344": "M/S output speed reference (MSSO)",
    "345": "M/S output torque reference (MSTO)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8423,
   "documented": "8423",
   "name": "CD1 - Command channel 1 assign",
   "description": "Factory [Terminal block]. Write only when stopped.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Terminal block (TER)",
    "3": "Local HMI (LCC)",
    "10": "Modbus communication (MDB)",
    "20": "CANopen communication (CAN)",
    "30": "Ext. communication module (NET)",
    "40": "Ethernet Embedded (ETH)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8441,
   "documented": "8441",
   "name": "CRC - Channel for reference frequency",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Terminals",
    "1": "Local keypad",
    "2": "Remote keypad",
    "3": "Modbus",
    "6": "CANopen",
    "7": "Terminal up-Down speed",
    "8": "Remote keypad up-down speed",
    "9": "COM option board",
    "11": "Embedded Ethernet",
    "14": "Indus",
    "15": "PowerSuite"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8442,
   "documented": "8442",
   "name": "CCC - Active command channel",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Terminals",
    "1": "Local keypad",
    "2": "Remote keypad",
    "3": "Modbus",
    "6": "CANopen",
    "7": "Terminal up-Down speed",
    "8": "Remote keypad up-down speed",
    "9": "COM option board",
    "11": "Embedded Ethernet",
    "14": "Indus",
    "15": "PowerSuite"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8501,
   "documented": "8501",
   "name": "CMD - Command register",
   "description": "CiA402 control word (I/O-profile bits when CHCF = IO).",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "CiA402: Switch on",
    "1": "CiA402: Enable voltage",
    "2": "CiA402: Quick stop (0 = quick stop active)",
    "3": "CiA402: Enable operation (run)",
    "7": "CiA402: Fault reset on 0->1 edge",
    "8": "CiA402: Halt (stop per Stt, stays in Operation enabled)",
    "11": "CiA402: assignable, default reverse direction (rrS = C111)",
    "12": "Assignable (C112)",
    "13": "Assignable (C113)",
    "14": "Assignable (C114)",
    "15": "Assignable (C115)"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8502,
   "documented": "8502",
   "name": "LFR - Reference frequency",
   "description": "Signed; 0.1 Hz while CMI bit 9 = 0.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "Hz",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8503,
   "documented": "8503",
   "name": "PISP - PIDSet point",
   "description": "Range 0 to 1000.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8504,
   "documented": "8504",
   "name": "CMI - Extended control word",
   "description": "Save to EEPROM, factory reset, LFR unit select.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Restore factory settings (drive stopped)",
    "1": "Save configuration to EEPROM (drive stopped)",
    "9": "LFR/RFR unit: 0 = 0.1 Hz, 1 = signed value where 32767 = tFr",
    "15": "1 = parameter consistency check off (drive locked in stop)"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8602,
   "documented": "8602",
   "name": "LFRD - Speed setpoint",
   "description": "Signed speed reference in rpm.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "rpm",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8604,
   "documented": "8604",
   "name": "RFRD - Output velocity",
   "description": "Range -32767 rpm to 32767 rpm.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "rpm",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8605,
   "documented": "8605",
   "name": "FRHD - Speed reference before ramp",
   "description": "Range -32767 rpm to 32767 rpm.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "rpm",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9001,
   "documented": "9001",
   "name": "ACC - Acceleration ramp time",
   "description": "Raw; resolution set by INR (factory 0.1 s).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9002,
   "documented": "9002",
   "name": "DEC - Deceleration ramp time",
   "description": "Raw; resolution set by INR (factory 0.1 s).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9020,
   "documented": "9020",
   "name": "INR - Ramp increment",
   "description": "Factory [Tenths of seconds].",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "hundredths of seconds (001)",
    "1": "Tenths of seconds (01)",
    "2": "seconds (1)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9601,
   "documented": "9601",
   "name": "UNS - Nominal motor voltage",
   "description": "Range 100 V to 690 V. Write only when stopped.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "V",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9602,
   "documented": "9602",
   "name": "FRS - Nominal motor frequency",
   "description": "Range 10.0 Hz to 599.0 Hz. Write only when stopped.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "Hz",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9604,
   "documented": "9604",
   "name": "NSP - Nominal motor speed",
   "description": "Range 0 rpm to 65535 rpm. Write only when stopped.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "rpm",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9630,
   "documented": "9630",
   "name": "THR - Motor thermal state",
   "description": "Range 0 % to 200 %.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10606,
   "documented": "10606",
   "name": "OC0 - Electrical energy consumed by the motor (Wh)",
   "description": "Range 0 Wh to 999 Wh. Write only when stopped.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "Wh",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10607,
   "documented": "10607",
   "name": "OC1 - Electrical energy consumed by the motor (KWh)",
   "description": "Range 0 kWh to 999 kWh. Write only when stopped.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "kWh",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10608,
   "documented": "10608",
   "name": "OC2 - Electrical energy consumed by the motor (MWh)",
   "description": "Range 0 MWh to 999 MWh. Write only when stopped.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "MWh",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10609,
   "documented": "10609",
   "name": "OC3 - Electrical energy consumed by the motor (GWh)",
   "description": "Range 0 GWh to 999 GWh. Write only when stopped.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "GWh",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10610,
   "documented": "10610",
   "name": "OC4 - Electrical energy consumed by the motor (TWh)",
   "description": "Range 0 TWh to 999 TWh. Write only when stopped.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "TWh",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10626,
   "documented": "10626",
   "name": "IC0 - Input Energy (Wh)",
   "description": "Range 0 Wh to 999 Wh. Write only when stopped.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "Wh",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10627,
   "documented": "10627",
   "name": "IC1 - Input Energy (kWh)",
   "description": "Range 0 kWh to 999 kWh. Write only when stopped.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "kWh",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10628,
   "documented": "10628",
   "name": "IC2 - Input Energy (MWh)",
   "description": "Range 0 MWh to 999 MWh. Write only when stopped.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "MWh",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10629,
   "documented": "10629",
   "name": "IC3 - Input Energy (GWh)",
   "description": "Range 0 GWh to 999 GWh. Write only when stopped.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "GWh",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10630,
   "documented": "10630",
   "name": "IC4 - Input Energy (TWh)",
   "description": "Range 0 TWh to 999 TWh. Write only when stopped.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "TWh",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11201,
   "documented": "11201",
   "name": "STT - Type of stop",
   "description": "Write only when stopped.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "On ramp (RMP)",
    "1": "Fast stop (FST)",
    "2": "Freewheel stop (NST)",
    "3": "DC injection (DCI)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11983,
   "documented": "11983",
   "name": "RPO - PID output",
   "description": "Range -3276.7 Hz to 3276.7 Hz.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 12701,
   "documented": "12701",
   "name": "NMA1 - Scan input 1 address",
   "description": "Range 0 to 65535. Factory 3201. Write only when stopped.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 12721,
   "documented": "12721",
   "name": "NCA1 - Scan output 1 address",
   "description": "Range 0 to 65535. Factory 8501. Write only when stopped.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 12741,
   "documented": "12741",
   "name": "NM1 - Com scan input 1 value",
   "description": "Range 0 to 65535.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 12761,
   "documented": "12761",
   "name": "NC1 - Com scan output 1 value",
   "description": "Range 0 to 65535.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 12890,
   "documented": "12890",
   "name": "LALR - Last warning",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No warning stored (NOA)",
    "1": "Fallback frequency reaction (FRF)",
    "2": "Speed maintained (RLS)",
    "3": "Type of stop (STT)",
    "4": "Reference frequency warning (SRA)",
    "18": "PID error warning (PEE)",
    "19": "PID feedback warning (PFA)",
    "20": "PID high feedback warning (PFAH)",
    "21": "PID low feedback warning (PFAL)",
    "22": "Regulation warning (PISH)",
    "23": "Limit switch reached (LSA)",
    "24": "Slack rope warning (RSDA)",
    "25": "Dynamic load warning (DLDA)",
    "27": "AI3 thermal sensor warning (TP3A)",
    "28": "AI4 thermal sensor warning (TP4A)",
    "29": "AI5 thermal sensor warning (TP5A)",
    "30": "AI1 4-20 loss warning (AP1)",
    "32": "AI3 4-20 loss warning (AP3)",
    "33": "AI4 4-20 loss warning (AP4)",
    "34": "AI5 4-20 loss warning (AP5)",
    "35": "Device thermal state warning (THA)",
    "36": "Thermal junction warning (TJA)",
    "37": "Fan counter warning (FCTA)",
    "39": "Braking resistor thermal warning (BOA)",
    "40": "External error warning (EFA)",
    "41": "Undervoltage warning (USA)",
    "42": "Preventive undervoltage active (UPA)",
    "44": "Motor frequency high threshold reached (FTA)",
    "45": "Motor frequency low threshold reached (FTAL)",
    "46": "Pulse warning threshold reached (FQLA)",
    "47": "Motor frequency low threshold 2 reached (F2AL)",
    "48": "High speed reached (FLA)",
    "49": "Reference frequency high threshold reached (RTAH)",
    "50": "Reference frequency low threshold reached (RTAL)",
    "51": "2nd frequency threshold reached (F2A)",
    "52": "Current threshold reached (CTA)",
    "53": "Low current threshold reached (CTAL)",
    "54": "High torque warning (TTHA)",
    "55": "Low torque warning (TTLA)",
    "56": "Process underload warning (ULA)",
    "57": "Process overload warning (OLA)",
    "58": "Torque limit reached (SSA)",
    "59": "Torque control warning (RTA)",
    "60": "Device thermal threshold reached (TAD)",
    "61": "Motor thermal threshold reached (TSA)",
    "62": "Motor 2 thermal threshold reached (TS2)",
    "63": "Motor 3 thermal threshold reached (TS3)",
    "64": "Motor 4 thermal threshold reached (TS4)",
    "65": "Power high threshold reached (PTHA)",
    "66": "Power low threshold reached (PTHL)",
    "67": "Customer warning 1 (CAS1)",
    "68": "Customer warning 2 (CAS2)",
    "69": "Customer warning 3 (CAS3)",
    "70": "Customer warning 4 (CAS4)",
    "71": "Customer warning 5 (CAS5)",
    "73": "Power Consumption warning (POWD)",
    "83": "Slipping warning (ANA)",
    "85": "Load movement warning (BSA)",
    "86": "Brake contact warning (BCA)",
    "87": "AI1 thermal sensor warning (TP1A)",
    "89": "Current reduction warning (TLOW)",
    "97": "Monitoring circuit A warning (IWA)",
    "98": "Monitoring circuit B warning (IWB)",
    "99": "Monitoring circuit C warning (IWC)",
    "100": "Monitoring circuit D warning (IWD)",
    "110": "Fieldbus communication loss fallback channel is active (AFFL)",
    "124": "M/S device warning (MSDA)",
    "125": "Backlash warning (BSQA)",
    "126": "Encoder module thermal warning (TPEA)",
    "133": "Temperature sensor AI1 warning (TS1A)",
    "135": "Temperature sensor AI3 warning (TS3A)",
    "136": "Temperature sensor AI4 warning (TS4A)",
    "137": "Temperature sensor AI5 warning (TS5A)",
    "138": "DC bus ripple warning (DCRW)",
    "143": "ON lock warning (LKON)",
    "144": "Power backup mode warning (RFTA)",
    "145": "Internal error 22 (Embedded Ethernet) (INFM)",
    "146": "Modbus communication interruption warning (SLF1)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64400,
   "documented": "64400",
   "name": "IM00 - IP mode Ethernet Embd",
   "description": "Factory [DHCP].",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Fixed address (MANU)",
    "1": "BOOTP (BOOTP)",
    "2": "DHCP (DHCP)",
    "3": "DCP (DCP)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64415,
   "documented": "64415",
   "name": "TTOB - Ethernet embedded : time-out",
   "description": "Range 0.1 s to 30.0 s. Factory 10.0 s. Write only when stopped.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Set Add (6001) to 1-247 and power-cycle, keep CHCF = SIM and set FR1 to Modbus (164), then write CMD (8501) = 0006h followed by 000Fh with a non-zero LFR (8502, 0.1 Hz) or LFRD (8602, rpm). Poll ETA (3201), RFR (3202), HMIS (3240) and LFT (7121).",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 8501,
    "why": "CMD: CiA402 run/stop/reset"
   },
   {
    "table": "holding_register",
    "address": 8502,
    "why": "LFR: frequency reference, 0.1 Hz"
   },
   {
    "table": "holding_register",
    "address": 3201,
    "why": "ETA: CiA402 status word"
   },
   {
    "table": "holding_register",
    "address": 3202,
    "why": "RFR: output frequency, 0.1 Hz"
   },
   {
    "table": "holding_register",
    "address": 3204,
    "why": "LCR: motor current (raw)"
   },
   {
    "table": "holding_register",
    "address": 3240,
    "why": "HMIS: drive state code"
   },
   {
    "table": "holding_register",
    "address": 7121,
    "why": "LFT: last fault code"
   },
   {
    "table": "holding_register",
    "address": 3209,
    "why": "THD: drive thermal state"
   }
  ],
  "enable": "Set [Modbus Address] Add (logical 6001) to 1-247; the factory value 0 (OFF) means the drive does not answer. Speed and format default to 19200 baud, 8-E-1 (tbr 6003, tFO 6004). Communication changes take effect after a power cycle. For combined CiA402 control keep [Control Mode] CHCF = [Not separ.] SIM and set [Ref Freq 1 Config] FR1 = Modbus (164); for separate mode use CHCF = SEP with Cd1 = Modbus.",
  "watchdog": "[ModbusTimeout] ttO (6005), 0.1-30 s, factory 10 s. If no valid Modbus frame arrives within ttO on a monitored channel, the drive raises [Modbus Com Interruption] SLF1 and reacts per SLL (7010): factory freewheel stop, or ignore, configured stop, fallback speed LFF (7080), speed maintained, ramp stop, fast stop or DC injection.",
  "quirks": [
   "Addresses are decimal logical numbers sent as-is (3201 = 0x0C81); do not subtract 1 or add 40001.",
   "CiA402 sequence: 0006h (shutdown) -> Ready to switch on, then 000Fh (enable operation) to run; 0007h disables operation, 0000h disables voltage, 0002h quick stop, 0080h rising edge resets a fault.",
   "Mask ETA with 006Fh to read the state: 0040h switch on disabled, 0021h ready to switch on, 0023h switched on, 0027h operation enabled, 0007h quick stop active, 0008h/0028h fault.",
   "CMD bit 11 is reverse direction by default ([Reverse Assign] rrS = C111); bits 12-15 can be assigned to functions (C112-C115)."
  ],
  "setup": [
   "Set Add, tbr and tFO in the [Communication] COM- / [Modbus SL] menu, then power-cycle the drive.",
   "RS-485 trunk: shielded twisted pair plus a common conductor; each line terminator is 120 ohm in series with 1 nF; the master supplies bus polarization.",
   "Write CMD and the reference at least once so the Modbus channel becomes active and monitored."
  ],
  "gotchas": [
   "Factory Add = OFF: a brand-new drive is silent on the bus.",
   "Configuration parameters (R/WS) are refused while the motor is running.",
   "CMI bit 1 (save to EEPROM) clears itself, but if CMI is written cyclically the master must write it back to 0; EEPROM life is about 100,000 writes."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/schneider-electric/atv340",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}