 "manufacturer": "Schneider Electric",
 "manufacturer_slug": "schneider-electric",
 "model": "Conext Core XC Series grid-tie PV inverter (0G-XC-BB)",
 "model_slug": "conext-core-xc",
 "short_model": "Conext Core XC",
 "aliases": [
  "0G-XC-BB",
  "XC-AIC15P"
 ],
 "equipment_type": "Solar inverter",
 "applies_to": "Conext Core XC Series grid-tied PV inverters (540/630/680 kW ratings, 0G-XC-BB) with firmware v1.07 and later; some registers need newer firmware as noted.",
 "summary": "The Conext Core XC is a grid-tied three-phase PV inverter with an RS-485 Modbus RTU port. All values are 16-bit integers with a fixed multiplier, read with function 03 and written with function 16. This map covers the read-only monitoring block (0x1700-0x1828), ratings and grid-code settings, the main power-limit and remote enable/disable controls, Modbus port settings and the log-reading registers.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": 247,
  "baud": 19200,
  "parity": "Even",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "hex 0-based",
  "note": "The application note says register addresses are zero based, printed in hex, and go straight into the request's address field. A master that wants register numbers must convert to decimal and add 1."
 },
 "default_word_order": null,
 "firmware": "v1.07 and later (individual registers list a minimum firmware, e.g. v3.01, v5.00)",
 "source": {
  "title": "Conext Core XC Series, 0G-XC-BB Grid-Tied Photovoltaic Inverter: Using Modbus Application Note",
  "doc_number": "AP-XC-095 Revision A",
  "revision_date": "2017-01",
  "url": "https://solar.se.com/eu/wp-content/uploads/sites/4/2021/12/TP20170101_Conext-Core-XC-Using-Modbus-App-NoteAP-XC-095.pdf",
  "pages": "PDF pp. 4-15 (RS-485 settings, functions, scaling, state codes, logs), p. 15 (addressing), pp. 16-17 (Table 17 monitoring), pp. 19-27 (Table 18 writable), pp. 28-30 (read-only configuration)"
 },
 "notes": [
  "Scale: the document gives units as 'unit/xN', meaning divide the raw value by N; this is converted to scale = 1/N.",
  "Left out: the 32-bit items (kWh Energy Produced 0x0802-0x0803, Energy Today 0x0804-0x0805, Operating Hours 0x081E-0x081F and Time 0xFA21-0xFA22) because the note does not state their word order; the text product designation, assembly and serial number blocks (0x1-0x1D, typed uchar8); and the log buffer registers.",
  "Only a selection of the writable registers in Table 18 is included (enable/disable, power and phase-current limits, power reference source, MPPT voltage window, port settings and a few grid-support switches). The many grid-code thresholds and delays are left out.",
  "Registers flagged ** in the note can be written while the inverter is enabled; the rest need the inverter disabled.",
  "Unmapped addresses inside a block read 0xFFFF without an error; writing one returns an illegal address exception.",
  "The note's Table 20/21 for the optional Vigilohm IM400 insulation monitor is a separate device and is not part of this map."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 5888,
   "documented": "0x1700",
   "name": "Operational Mode State",
   "description": "High byte = enable mode, low byte = state.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "PV mode offline",
    "1": "PV mode reconnecting",
    "2": "PV mode online",
    "256": "CP mode offline",
    "257": "CP mode reconnecting",
    "258": "CP mode online",
    "512": "PVCQ mode offline",
    "513": "PVCQ mode reconnecting",
    "514": "PVCQ mode online"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5889,
   "documented": "0x1701",
   "name": "Temperature Power Board",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5890,
   "documented": "0x1702",
   "name": "Temperature Heatsink1",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5891,
   "documented": "0x1703",
   "name": "Temperature Heatsink2",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5892,
   "documented": "0x1704",
   "name": "Temperature Heatsink3",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5893,
   "documented": "0x1705",
   "name": "Grid Current",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "Arms",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6129,
   "documented": "0x17F1",
   "name": "Apparent Power",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "kVA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6132,
   "documented": "0x17F4",
   "name": "Reactive Power",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "kVAr",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6136,
   "documented": "0x17F8",
   "name": "Grid Voltage V12",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "Vrms",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6137,
   "documented": "0x17F9",
   "name": "Grid Voltage V23",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "Vrms",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6138,
   "documented": "0x17FA",
   "name": "Grid Voltage V31",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "Vrms",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6139,
   "documented": "0x17FB",
   "name": "Grid Current Line1",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "Arms",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6140,
   "documented": "0x17FC",
   "name": "Grid Current Line2",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "Arms",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6141,
   "documented": "0x17FD",
   "name": "Grid Current Line3",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "Arms",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6142,
   "documented": "0x17FE",
   "name": "Active Power",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "kW",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6143,
   "documented": "0x17FF",
   "name": "PV Voltage",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "VDC",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6144,
   "documented": "0x1800",
   "name": "PV Current",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "ADC",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6145,
   "documented": "0x1801",
   "name": "PV Power",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "kW",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6146,
   "documented": "0x1802",
   "name": "Grid Frequency",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6147,
   "documented": "0x1803",
   "name": "Grid Frequency (Hi Res)",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6157,
   "documented": "0x180D",
   "name": "DC Voltage",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "VDC",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6158,
   "documented": "0x180E",
   "name": "Thermal Loading",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6168,
   "documented": "0x1818",
   "name": "Phase A Frequency",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6169,
   "documented": "0x1819",
   "name": "Phase B Frequency",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6170,
   "documented": "0x181A",
   "name": "Phase C Frequency",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6171,
   "documented": "0x181B",
   "name": "Phase A Real Power",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "kW",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6172,
   "documented": "0x181C",
   "name": "Phase B Real Power",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "kW",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6173,
   "documented": "0x181D",
   "name": "Phase C Real Power",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "kW",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6174,
   "documented": "0x181E",
   "name": "Phase A Reactive Power",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "kVAr",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6175,
   "documented": "0x181F",
   "name": "Phase B Reactive Power",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "kVAr",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6176,
   "documented": "0x1820",
   "name": "Phase C Reactive Power",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "kVAr",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6177,
   "documented": "0x1821",
   "name": "Phase A Apparent Power",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "kVA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6178,
   "documented": "0x1822",
   "name": "Phase B Apparent Power",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "kVA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6179,
   "documented": "0x1823",
   "name": "Phase C Apparent Power",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "kVA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6182,
   "documented": "0x1826",
   "name": "Event Code",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6183,
   "documented": "0x1827",
   "name": "System State",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Initializing",
    "1": "Disable",
    "2": "Enable",
    "3": "Service"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6184,
   "documented": "0x1828",
   "name": "Alarm Code",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16393,
   "documented": "0x4009",
   "name": "Day Log Rate",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "min",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16394,
   "documented": "0x400A",
   "name": "First Daytime Hour",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16395,
   "documented": "0x400B",
   "name": "Night Log Rate",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "min",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16396,
   "documented": "0x400C",
   "name": "First Nighttime Hour",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16476,
   "documented": "0x405C",
   "name": "Grid Voltage12 Gain Calibration",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.001,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16477,
   "documented": "0x405D",
   "name": "Grid Voltage23 Gain Calibration",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.001,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16478,
   "documented": "0x405E",
   "name": "Grid Voltage31 Gain Calibration",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.001,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16479,
   "documented": "0x405F",
   "name": "Grid Voltage12 Offset Calibration",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16480,
   "documented": "0x4060",
   "name": "Grid Voltage23 Offset Calibration",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16481,
   "documented": "0x4061",
   "name": "Grid Voltage31 Offset Calibration",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16482,
   "documented": "0x4062",
   "name": "Gain kVAr Inductive",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "(V2/kVAr*Hz)",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16483,
   "documented": "0x4063",
   "name": "Gain kVAr Capacitive",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "(V2/kVAr*Hz)",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16526,
   "documented": "0x408E",
   "name": "Disconnect Profile",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16527,
   "documented": "0x408F",
   "name": "P-analog Filter Time",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16528,
   "documented": "0x4090",
   "name": "Q-analog Filter Time",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16529,
   "documented": "0x4091",
   "name": "I1 Gain Cal",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.001,
   "scale_factor_ref": null,
   "units": "s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16530,
   "documented": "0x4092",
   "name": "I2 Gain Cal",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.001,
   "scale_factor_ref": null,
   "units": "s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16531,
   "documented": "0x4093",
   "name": "I3 Gain Cal",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.001,
   "scale_factor_ref": null,
   "units": "s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16532,
   "documented": "0x4094",
   "name": "I1 Offset Cal",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16533,
   "documented": "0x4095",
   "name": "I2 Offset Cal",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16534,
   "documented": "0x4096",
   "name": "I3 Offset Cal",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16535,
   "documented": "0x4097",
   "name": "Analog Error Suppressed",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "Suppress P error",
    "2": "Suppress Q error",
    "3": "Suppress P and Q error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16536,
   "documented": "0x4098",
   "name": "Modbus User P Readout",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "kW",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16537,
   "documented": "0x4099",
   "name": "Modbus User Q Readout",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "kVAr",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16538,
   "documented": "0x409A",
   "name": "Analog P Signal Readout",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "mA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16539,
   "documented": "0x409B",
   "name": "Analog Q Signal Readout",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "mA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16563,
   "documented": "0x40B3",
   "name": "AI Disconn LF Threshold",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16564,
   "documented": "0x40B4",
   "name": "AI Disconn LF Delay",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16565,
   "documented": "0x40B5",
   "name": "AI LF Disconn Function",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 18176,
   "documented": "0x4700",
   "name": "Number of Data Log Records",
   "description": "Up to 1861 records.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 18177,
   "documented": "0x4701",
   "name": "Number of Event Log Records",
   "description": "Up to 8192 records.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 18178,
   "documented": "0x4702",
   "name": "Number of Fault Log Records",
   "description": "Up to 910 records.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 18179,
   "documented": "0x4703",
   "name": "Log Request Index",
   "description": "Record to fetch; 1 = most recent.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 18180,
   "documented": "0x4704",
   "name": "Log Response Index",
   "description": "Equals the request index when the buffer is ready.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 18181,
   "documented": "0x4705",
   "name": "Logger Mode",
   "description": "0 log, 1 data, 2 event, 3 service, 4 oscillography, 5 config.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Log mode",
    "1": "Read data log",
    "2": "Read event log",
    "3": "Read service log",
    "4": "Read oscillography",
    "5": "Config mode"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 18182,
   "documented": "0x4706",
   "name": "Logger State",
   "description": "Logger status flags.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Board not ready",
    "1": "Log mode active",
    "2": "Read mode active",
    "3": "Config mode active",
    "8": "RTC battery low",
    "9": "NVRAM record CRC error",
    "10": "Other RTC error"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 32771,
   "documented": "0x8003",
   "name": "Modbus Unit ID",
   "description": "Modbus unit ID; takes effect after a system reset.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 32784,
   "documented": "0x8010",
   "name": "Baud Rate",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "24": "4800 baud",
    "28": "9600 baud",
    "32": "19200 baud",
    "36": "38400 baud",
    "40": "57600 baud"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 57568,
   "documented": "0xE0E0",
   "name": "Parameter Control Station",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "1": "PANELCONTROL",
    "2": "MODBUS"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 57569,
   "documented": "0xE0E1",
   "name": "Commit Modbus Settings",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "W",
   "values": {
    "1": "COMMIT"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 61438,
   "documented": "0xEFFE",
   "name": "Remote Disable/Enable",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "W",
   "values": {
    "0": "Remote start",
    "1": "Remote shutdown"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 63489,
   "documented": "0xF801",
   "name": "Rated Input (PV) Current",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 63490,
   "documented": "0xF802",
   "name": "Maximum Input (PV) Voltage",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "VDC",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 63491,
   "documented": "0xF803",
   "name": "Max Tracking Volt",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "V",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 63492,
   "documented": "0xF804",
   "name": "Min Tracking Volt",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "V",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 63493,
   "documented": "0xF805",
   "name": "Max PV OC Voltage",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "VDC",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 63494,
   "documented": "0xF806",
   "name": "Max STC PV-SC Current",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "ADC",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 63495,
   "documented": "0xF807",
   "name": "Rated Apparent Power",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "kVA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 63496,
   "documented": "0xF808",
   "name": "Rated Powerat Unity PF",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "kW",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 63497,
   "documented": "0xF809",
   "name": "Min Input (PV) Voltage",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "VDC",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 63498,
   "documented": "0xF80A",
   "name": "Nominal L-to-L Voltage",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "Vrms",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 63499,
   "documented": "0xF80B",
   "name": "Nominal Line Current",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "Arms",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 63500,
   "documented": "0xF80C",
   "name": "Rated Reactive Power",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "kVAr",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 63990,
   "documented": "0xF9F6",
   "name": "P(f) Control Function",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "P(f) type 1",
    "2": "P(f) type 2"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64009,
   "documented": "0xFA09",
   "name": "Grid Reconnection Delay",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64011,
   "documented": "0xFA0B",
   "name": "Disconn HV Threshold",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64012,
   "documented": "0xFA0C",
   "name": "Disconn LV Threshold",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64015,
   "documented": "0xFA0F",
   "name": "Disconn HF Threshold",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64016,
   "documented": "0xFA10",
   "name": "Disconn LF Threshold",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64025,
   "documented": "0xFA19",
   "name": "User Active Power Limit",
   "description": "Can be written while the inverter is enabled.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "kW",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64026,
   "documented": "0xFA1A",
   "name": "Active Anti-Islanding Function",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64027,
   "documented": "0xFA1B",
   "name": "User Reactive Power Reference",
   "description": "Can be written while the inverter is enabled.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "kVAr",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64029,
   "documented": "0xFA1D",
   "name": "User Apparent Power Limit",
   "description": "Can be written while the inverter is enabled.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "kVA",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64030,
   "documented": "0xFA1E",
   "name": "User Phase Current Limit",
   "description": "Can be written while the inverter is enabled.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64031,
   "documented": "0xFA1F",
   "name": "Utility Region",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64032,
   "documented": "0xFA20",
   "name": "Language",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "English",
    "1": "German",
    "2": "Spanish",
    "3": "French",
    "4": "Italian",
    "6": "Custom 1",
    "7": "Custom 2"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64036,
   "documented": "0xFA24",
   "name": "Voltage Support Function",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64053,
   "documented": "0xFA35",
   "name": "Power Ref. Ramp Time",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "ms",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64054,
   "documented": "0xFA36",
   "name": "System L-to-L Voltage",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "Vrms",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64055,
   "documented": "0xFA37",
   "name": "Disconnvery HV Threshold",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64058,
   "documented": "0xFA3A",
   "name": "Disconnvery LV Threshold",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64061,
   "documented": "0xFA3D",
   "name": "Disconnvery LF Threshold",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64064,
   "documented": "0xFA40",
   "name": "Disconnvery HF Threshold",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64070,
   "documented": "0xFA46",
   "name": "Reconn Power Ramp Time",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64072,
   "documented": "0xFA48",
   "name": "Power Reference Selection",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "MODBUS",
    "1": "ANALOGINPUT"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64264,
   "documented": "0xFB08",
   "name": "DC Cap Surge Accum",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "min",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64272,
   "documented": "0xFB10",
   "name": "Voltage Envelope Threshold",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64273,
   "documented": "0xFB11",
   "name": "Voltage Envelope Delay",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "Samples",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64305,
   "documented": "0xFB31",
   "name": "DC Switch Open Count",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64306,
   "documented": "0xFB32",
   "name": "AC Switch Open Count",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64344,
   "documented": "0xFB58",
   "name": "Vac-Regulation",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "Q(V)",
    "2": "Phi(P)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64354,
   "documented": "0xFB62",
   "name": "Power Ramp Rate",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "%/min",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64355,
   "documented": "0xFB63",
   "name": "Min. Power Ramp Step",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "kW",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64413,
   "documented": "0xFB9D",
   "name": "CQ Mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64415,
   "documented": "0xFB9F",
   "name": "Device Active Status",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "AC breaker closed",
    "1": "DC switch closed",
    "2": "Fan in test mode"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64419,
   "documented": "0xFBA3",
   "name": "Countdown",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64466,
   "documented": "0xFBD2",
   "name": "Max Daily Online Cycling",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64474,
   "documented": "0xFBDA",
   "name": "Fan Speed",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Poll 0x1700-0x1828 with function 03 for state, grid voltages and currents, active/reactive power and PV values (all 16-bit, divide by the listed factor). To control power, set Parameter Control Station (0xE0E0) to 2 = Modbus, then write the active power limit at 0xFA19 with function 16.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 5888,
    "why": "Operating mode and state"
   },
   {
    "table": "holding_register",
    "address": 6142,
    "why": "Active power, kW x10"
   },
   {
    "table": "holding_register",
    "address": 6145,
    "why": "PV power"
   },
   {
    "table": "holding_register",
    "address": 6136,
    "why": "Grid voltage V12"
   },
   {
    "table": "holding_register",
    "address": 6146,
    "why": "Grid frequency"
   },
   {
    "table": "holding_register",
    "address": 6184,
    "why": "Active alarm code"
   },
   {
    "table": "holding_register",
    "address": 57568,
    "why": "Hand settings control to Modbus"
   },
   {
    "table": "holding_register",
    "address": 64025,
    "why": "User active power limit"
   }
  ],
  "enable": "On the front panel go to 2 Language, Time, Interface > Comm. Interface > Parameter Control Station and select panel control to set the Modbus address and baud rate, then power-cycle with QF2. For writes, set register 0xE0E0 to 2 (Modbus).",
  "watchdog": null,
  "quirks": [
   "Addresses are hex and zero based; a master that counts from 1 must add one.",
   "Only function codes 03, 16, 08 (sub-function 00) and 43 are supported; there is no FC06 single-register write.",
   "Changing the Modbus unit ID (0xE0E1 commit, 0x8003) needs a system reset before it takes effect."
  ],
  "setup": [
   "Default RS-485 settings: 19200 baud, 8 data bits, even parity, 1 stop bit; all inverters on one bus must use the same settings.",
   "Do not use 57600 baud if the Vigilohm IM400 is installed (it only supports 38400)."
  ],
  "gotchas": [
   "Reading an unmapped address returns 0xFFFF with no exception, so a wrong address can look like a valid value.",
   "Leaving Logger Mode (0x4705) in any read mode stops data logging; set it back to 0."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/schneider-electric/conext-core-xc",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}