 "manufacturer": "Schneider Electric",
 "manufacturer_slug": "schneider-electric",
 "model": "PowerTag Energy wireless sensors via PowerTag Link gateway (Modbus TCP)",
 "model_slug": "powertag-energy-powertag-link",
 "short_model": "PowerTag Link",
 "aliases": [
  "PowerTag Link",
  "PowerTag Link HD",
  "A9XMWD20",
  "A9XMWD100",
  "PowerTag Energy 63",
  "A9MEM1520",
  "A9MEM1540",
  "A9MEM1560",
  "A9MEM1570",
  "PowerTag M250",
  "PowerTag M630",
  "LV434020",
  "PowerTag F160",
  "A9MEM1580",
  "PowerTag Rope",
  "A9MEM1590"
 ],
 "equipment_type": "Energy meter (wireless sensors through an Ethernet gateway)",
 "applies_to": "PowerTag Energy 63, M250/M630, F160 and Rope sensors read through a PowerTag Link or PowerTag Link HD gateway, per DOCA0157EN-09 (10/2025).",
 "summary": "PowerTag Energy sensors clip onto breakers and report over radio to a PowerTag Link gateway, which serves each sensor as its own Modbus TCP server address (1-247). Every sensor exposes the same register block: currents, voltages, power and power factor as big-endian floats, and energy counters as 64-bit integers in Wh. Which registers a sensor fills depends on its type (63 A, M250/M630, F160/Rope).",
 "transport": [
  "TCP"
 ],
 "defaults": {
  "unit_id": null,
  "baud": null,
  "parity": null,
  "data_bits": null,
  "stop_bits": null,
  "tcp_port": 502
 },
 "addressing": {
  "convention": "1-based",
  "note": "The guide prints register numbers in decimal and addresses in hex, with address = register - 1 (register 3000 is address 0x0BB7). Two hex cells in the table are misprinted (register 3228 shown as 0x09CB, register 5193 as 0x1488); wire addresses here follow the register-minus-one rule."
 },
 "default_word_order": "ABCD",
 "firmware": null,
 "source": {
  "title": "PowerTag Link Gateway User Guide",
  "doc_number": "DOCA0157EN-09",
  "revision_date": "2025-10",
  "url": "https://download.se.com/files?p_Doc_Ref=DOCA0157EN",
  "pages": "Data types and big-endian rule p. 93; frame example and addressing pp. 94-95; gateway registers pp. 96-97; PowerTag Energy sensor registers pp. 98-105"
 },
 "notes": [
  "The guide says 32-bit and 64-bit values are big-endian: most significant word first.",
  "Read a sensor by using its Modbus server address (set per wireless device on the gateway web pages, 1-247). The gateway's own identification registers answer on server address 255.",
  "Invalid or unavailable values read 0xFFC00000 (floats) or 0x8000000000000000 (64-bit energy).",
  "Each register's description says which sensor types fill it: PowerTag 63 = A9MEM152x/154x/156x/157x, M250/M630 = LV43402x, F160/Rope = A9MEM1580/A9MEM159x.",
  "Left out: the 'set partial counter' write registers (3260, 3268, 3276, 3284, 3292), demand timestamps (DATETIME), the PowerTag control-module, HeatTag, load-monitoring, configuration, diagnostic and synthesis-table registers.",
  "Schneider's function code 100-4 (read scattered registers) is also accepted for most float registers; this map uses plain function 03."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 2999,
   "documented": "3000 (0x0BB7)",
   "name": "RMS current on phase A",
   "description": "Sensors: PowerTag 63, M250, M630, F160, Rope",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3001,
   "documented": "3002 (0x0BB9)",
   "name": "RMS current on phase B",
   "description": "Sensors: PowerTag 63, M250, M630, F160, Rope",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3003,
   "documented": "3004 (0x0BBB)",
   "name": "RMS current on phase C",
   "description": "Sensors: PowerTag 63, M250, M630, F160, Rope",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3005,
   "documented": "3006 (0x0BBD)",
   "name": "RMS current on neutral",
   "description": "Sensors: F160, Rope",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3019,
   "documented": "3020 (0x0BCB)",
   "name": "RMS phase-to-phase voltage A-B",
   "description": "Sensors: PowerTag 63, M250, M630, F160, Rope",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3021,
   "documented": "3022 (0x0BCD)",
   "name": "RMS phase-to-phase voltage B-C",
   "description": "Sensors: PowerTag 63, M250, M630, F160, Rope",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3023,
   "documented": "3024 (0x0BCF)",
   "name": "RMS phase-to-phase voltage C-A",
   "description": "Sensors: PowerTag 63, M250, M630, F160, Rope",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3027,
   "documented": "3028 (0x0BD3)",
   "name": "RMS phase-to-neutral voltage A-N",
   "description": "Sensors: PowerTag 63, M250, M630, F160, Rope",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3029,
   "documented": "3030 (0x0BD5)",
   "name": "RMS phase-to-neutral voltage B-N",
   "description": "Sensors: PowerTag 63, M250, M630, F160, Rope",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3031,
   "documented": "3032 (0x0BD7)",
   "name": "RMS phase-to-neutral voltage C-N",
   "description": "Sensors: PowerTag 63, M250, M630, F160, Rope",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3053,
   "documented": "3054 (0x0BED)",
   "name": "Active power on phase A",
   "description": "Sensors: PowerTag 63, M250, M630, F160, Rope",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3055,
   "documented": "3056 (0x0BEF)",
   "name": "Active power on phase B",
   "description": "Sensors: PowerTag 63, M250, M630, F160, Rope",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3057,
   "documented": "3058 (0x0BF1)",
   "name": "Active power on phase C",
   "description": "Sensors: PowerTag 63, M250, M630, F160, Rope",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3059,
   "documented": "3060 (0x0BF3)",
   "name": "Total active power",
   "description": "Sensors: PowerTag 63, M250, M630, F160, Rope",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3061,
   "documented": "3062 (0x0BF5)",
   "name": "Reactive power on phase A",
   "description": "Sensors: F160, Rope",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VAR",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3063,
   "documented": "3064 (0x0BF7)",
   "name": "Reactive power on phase B",
   "description": "Sensors: F160, Rope",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VAR",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3065,
   "documented": "3066 (0x0BF9)",
   "name": "Reactive power on phase C",
   "description": "Sensors: F160, Rope",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VAR",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3067,
   "documented": "3068 (0x0BFB)",
   "name": "Total reactive power",
   "description": "Sensors: M250, M630, F160, Rope",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VAR",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3069,
   "documented": "3070 (0x0BFD)",
   "name": "Apparent power on phase A",
   "description": "Sensors: F160, Rope",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3071,
   "documented": "3072 (0x0BFF)",
   "name": "Apparent power on phase B",
   "description": "Sensors: F160, Rope",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3073,
   "documented": "3074 (0x0C01)",
   "name": "Apparent power on phase C",
   "description": "Sensors: F160, Rope",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3075,
   "documented": "3076 (0x0C03)",
   "name": "Total apparent power (arithmetic)",
   "description": "Sensors: PowerTag 63, M250, M630, F160, Rope",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3077,
   "documented": "3078 (0x0C05)",
   "name": "Power factor on phase A",
   "description": "Sensors: F160, Rope",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3079,
   "documented": "3080 (0x0C07)",
   "name": "Power factor on phase B",
   "description": "Sensors: F160, Rope",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3081,
   "documented": "3082 (0x0C09)",
   "name": "Power factor on phase C",
   "description": "Sensors: F160, Rope",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3083,
   "documented": "3084 (0x0C0B)",
   "name": "Total power factor",
   "description": "Sensors: PowerTag 63, M250, M630, F160, Rope",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3085,
   "documented": "3086 (0x0C0D)",
   "name": "Power factor sign convention",
   "description": "Sensors: F160, Rope",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "IEC",
    "1": "IEEE"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3109,
   "documented": "3110 (0x0C25)",
   "name": "AC frequency",
   "description": "Sensors: M250, M630, F160, Rope",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3131,
   "documented": "3132 (0x0C3B)",
   "name": "Device internal temperature",
   "description": "Sensors: M250, M630, F160, Rope",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3203,
   "documented": "3204 (0x0C83)",
   "name": "Total active energy delivered + received (non-resettable)",
   "description": "Sensors: PowerTag 63, M250, M630, F160, Rope",
   "data_type": "INT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "Wh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3207,
   "documented": "3208 (0x0C87)",
   "name": "Total active energy delivered count positively (non-resettable)",
   "description": "Sensors: PowerTag 63, M250, M630, F160, Rope",
   "data_type": "INT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "Wh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3211,
   "documented": "3212 (0x0C8B)",
   "name": "Total active energy received (non-resettable)",
   "description": "Sensors: PowerTag 63, M250, M630, F160, Rope",
   "data_type": "INT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "Wh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3215,
   "documented": "3216 (0x0C8F)",
   "name": "Phase A active energy delivered - received (non-resettable)",
   "description": "Sensors: M250, M630",
   "data_type": "INT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "Wh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3219,
   "documented": "3220 (0x0C93)",
   "name": "Phase B active energy delivered - received (non-resettable)",
   "description": "Sensors: M250, M630",
   "data_type": "INT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "Wh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3223,
   "documented": "3224 (0x0C97)",
   "name": "Phase C active energy delivered - received (non-resettable)",
   "description": "Sensors: M250, M630",
   "data_type": "INT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "Wh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3255,
   "documented": "3256 (0x0CB7)",
   "name": "Partial active energy delivered + received (resettable)",
   "description": "Sensors: PowerTag 63, M250, M630, F160, Rope",
   "data_type": "INT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "Wh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3263,
   "documented": "3264 (0x0CBF)",
   "name": "Partial active energy delivered (resettable)",
   "description": "Sensors: PowerTag 63, M250, M630, F160, Rope",
   "data_type": "INT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "Wh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3271,
   "documented": "3272 (0x0CC7)",
   "name": "Partial active energy received (resettable)",
   "description": "Sensors: PowerTag 63, M250, M630, F160, Rope",
   "data_type": "INT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "Wh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3279,
   "documented": "3280 (0x0CCF)",
   "name": "Partial reactive energy delivered (resettable)",
   "description": "Sensors: M250, M630, F160, Rope",
   "data_type": "INT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VARh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3287,
   "documented": "3288 (0x0CD7)",
   "name": "Partial reactive energy received (resettable)",
   "description": "Sensors: M250, M630, F160, Rope",
   "data_type": "INT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VARh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3765,
   "documented": "3766 (0x0EB5)",
   "name": "Demand total active power",
   "description": "Sensors: PowerTag 63, F160, Rope",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3769,
   "documented": "3770 (0x0EB9)",
   "name": "Maximum Demand total active power",
   "description": "Sensors: PowerTag 63, F160, Rope",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5008,
   "documented": "5009 (0x1390)",
   "name": "Active energy delivered (resettable)",
   "description": "Sensors: PowerTag 63, F160, Rope",
   "data_type": "INT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "Wh",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5012,
   "documented": "5013 (0x1394)",
   "name": "Active energy delivered count positively (non-resettable)",
   "description": "Sensors: PowerTag 63, F160, Rope",
   "data_type": "INT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "Wh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5016,
   "documented": "5017 (0x1398)",
   "name": "Active energy received (resettable)",
   "description": "Sensors: PowerTag 63, F160, Rope",
   "data_type": "INT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "Wh",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5020,
   "documented": "5021 (0x139C)",
   "name": "Active energy received count negatively (non-resettable)",
   "description": "Sensors: PowerTag 63, F160, Rope",
   "data_type": "INT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "Wh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5048,
   "documented": "5049 (0x13B8)",
   "name": "Phase A active energy delivered (resettable)",
   "description": "Sensors: F160, Rope",
   "data_type": "INT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "Wh",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5052,
   "documented": "5053 (0x13BC)",
   "name": "Phase A active energy delivered (non-resettable)",
   "description": "Sensors: F160, Rope",
   "data_type": "INT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "Wh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5056,
   "documented": "5057 (0x13C0)",
   "name": "Phase A active energy received (resettable)",
   "description": "Sensors: F160, Rope",
   "data_type": "INT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "Wh",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5060,
   "documented": "5061 (0x13C4)",
   "name": "Phase A active energy received (non-resettable)",
   "description": "Sensors: F160, Rope",
   "data_type": "INT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "Wh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5076,
   "documented": "5077 (0x13D4)",
   "name": "Phase A active energy delivered + received (non-resettable)",
   "description": "Sensors: F160, Rope",
   "data_type": "INT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "Wh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5088,
   "documented": "5089 (0x13E0)",
   "name": "Phase B active energy delivered (resettable)",
   "description": "Sensors: F160, Rope",
   "data_type": "INT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "Wh",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5092,
   "documented": "5093 (0x13E4)",
   "name": "Phase B active energy delivered (non-resettable)",
   "description": "Sensors: F160, Rope",
   "data_type": "INT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "Wh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5096,
   "documented": "5097 (0x13E8)",
   "name": "Phase B active energy received (resettable)",
   "description": "Sensors: F160, Rope",
   "data_type": "INT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "Wh",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5100,
   "documented": "5101 (0x13EC)",
   "name": "Phase B active energy received (non-resettable)",
   "description": "Sensors: F160, Rope",
   "data_type": "INT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "Wh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5128,
   "documented": "5129 (0x1408)",
   "name": "Phase C active energy delivered (resettable)",
   "description": "Sensors: F160, Rope",
   "data_type": "INT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "Wh",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5132,
   "documented": "5133 (0x140C)",
   "name": "Phase C active energy delivered (non-resettable)",
   "description": "Sensors: F160, Rope",
   "data_type": "INT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "Wh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5136,
   "documented": "5137 (0x1410)",
   "name": "Phase C active energy received (resettable)",
   "description": "Sensors: F160, Rope",
   "data_type": "INT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "Wh",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5140,
   "documented": "5141 (0x1414)",
   "name": "Phase C active energy received (non-resettable)",
   "description": "Sensors: F160, Rope",
   "data_type": "INT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "Wh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5176,
   "documented": "5177 (0x1438)",
   "name": "Reactive energy delivered (resettable)",
   "description": "Sensors: F160, Rope",
   "data_type": "INT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VARh",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5180,
   "documented": "5181 (0x143C)",
   "name": "Reactive energy delivered count positively (non-resettable)",
   "description": "Sensors: F160, Rope",
   "data_type": "INT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VARh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5192,
   "documented": "5193 (0x1488)",
   "name": "Reactive energy received (resettable)",
   "description": "Sensors: F160, Rope",
   "data_type": "INT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VARh",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5196,
   "documented": "5197 (0x144C)",
   "name": "Reactive energy received count negatively (non-resettable)",
   "description": "Sensors: F160, Rope",
   "data_type": "INT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VARh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5232,
   "documented": "5233 (0x1470)",
   "name": "Phase A reactive energy delivered (resettable)",
   "description": "Sensors: F160, Rope",
   "data_type": "INT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VARh",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5236,
   "documented": "5237 (0x1474)",
   "name": "Phase A reactive energy delivered (non-resettable)",
   "description": "Sensors: F160, Rope",
   "data_type": "INT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VARh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5240,
   "documented": "5241 (0x1478)",
   "name": "Phase A reactive energy received (resettable)",
   "description": "Sensors: F160, Rope",
   "data_type": "INT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VARh",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5244,
   "documented": "5245 (0x147C)",
   "name": "Phase A reactive energy received (non-resettable)",
   "description": "Sensors: F160, Rope",
   "data_type": "INT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VARh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5272,
   "documented": "5273 (0x1498)",
   "name": "Phase B reactive energy delivered (resettable)",
   "description": "Sensors: F160, Rope",
   "data_type": "INT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VARh",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5276,
   "documented": "5277 (0x149C)",
   "name": "Phase B reactive energy delivered (non-resettable)",
   "description": "Sensors: F160, Rope",
   "data_type": "INT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VARh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5280,
   "documented": "5281 (0x14A0)",
   "name": "Phase B reactive energy received (resettable)",
   "description": "Sensors: F160, Rope",
   "data_type": "INT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VARh",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5284,
   "documented": "5285 (0x14A4)",
   "name": "Phase B reactive energy received (non-resettable)",
   "description": "Sensors: F160, Rope",
   "data_type": "INT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VARh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5312,
   "documented": "5313 (0x14C0)",
   "name": "Phase C reactive energy delivered (resettable)",
   "description": "Sensors: F160, Rope",
   "data_type": "INT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VARh",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5316,
   "documented": "5317 (0x14C4)",
   "name": "Phase C reactive energy delivered (non-resettable)",
   "description": "Sensors: F160, Rope",
   "data_type": "INT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VARh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5320,
   "documented": "5321 (0x14C8)",
   "name": "Phase C reactive energy received (resettable)",
   "description": "Sensors: F160, Rope",
   "data_type": "INT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VARh",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5324,
   "documented": "5325 (0x14CC)",
   "name": "Phase C reactive energy received (non-resettable)",
   "description": "Sensors: F160, Rope",
   "data_type": "INT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VARh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5364,
   "documented": "5365 (0x14F4)",
   "name": "Apparent energy delivered + received (resettable)",
   "description": "Sensors: F160, Rope",
   "data_type": "INT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VAh",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5368,
   "documented": "5369 (0x14F8)",
   "name": "Apparent energy delivered + received (non-resettable)",
   "description": "Sensors: F160, Rope",
   "data_type": "INT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VAh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5388,
   "documented": "5389 (0x150C)",
   "name": "Phase A apparent energy (resettable)",
   "description": "Sensors: F160, Rope",
   "data_type": "INT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VAh",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5392,
   "documented": "5393 (0x1510)",
   "name": "Phase A apparent energy (non-resettable)",
   "description": "Sensors: F160, Rope",
   "data_type": "INT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VAh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5428,
   "documented": "5429 (0x1534)",
   "name": "Phase B apparent energy (resettable)",
   "description": "Sensors: F160, Rope",
   "data_type": "INT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VAh",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5432,
   "documented": "5433 (0x1538)",
   "name": "Phase B apparent energy (non-resettable)",
   "description": "Sensors: F160, Rope",
   "data_type": "INT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VAh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5468,
   "documented": "5469 (0x155C)",
   "name": "Phase C apparent energy (resettable)",
   "description": "Sensors: F160, Rope",
   "data_type": "INT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VAh",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5472,
   "documented": "5473 (0x1560)",
   "name": "Phase C apparent energy (non-resettable)",
   "description": "Sensors: F160, Rope",
   "data_type": "INT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VAh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Connect to the gateway on TCP port 502, use each sensor's Modbus address as the unit ID, and read 3000-3110 (floats) plus the 64-bit energy registers 3204-3212.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 2999,
    "why": "Phase A current"
   },
   {
    "table": "holding_register",
    "address": 3027,
    "why": "Phase A-N voltage"
   },
   {
    "table": "holding_register",
    "address": 3059,
    "why": "Total active power"
   },
   {
    "table": "holding_register",
    "address": 3083,
    "why": "Total power factor"
   },
   {
    "table": "holding_register",
    "address": 3203,
    "why": "Total active energy (not resettable)"
   },
   {
    "table": "holding_register",
    "address": 3211,
    "why": "Total active energy received"
   }
  ],
  "enable": "Modbus TCP is on by default on the gateway. The gateway gives each paired wireless device a Modbus address (1-247), which can be changed on its web pages.",
  "watchdog": null,
  "quirks": [
   "Unit ID selects the sensor, not the gateway; 255 addresses the gateway itself.",
   "Energy is in Wh/VARh/VAh as signed 64-bit integers.",
   "Not every register is filled by every sensor type."
  ],
  "setup": [
   "The gateway takes its IP address by DHCP by default; a static IPv4 address can be set on its web pages.",
   "Check or edit each wireless device's Modbus address in that device's parameters on the web pages."
  ],
  "gotchas": [
   "The gateway flags a communication-loss alarm when it hears nothing from a device for 6 times that device's communication period.",
   "The guide lists two misprinted hex addresses; trust the decimal register numbers."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/schneider-electric/powertag-energy-powertag-link",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}