 "manufacturer": "Schneider Electric",
 "manufacturer_slug": "schneider-electric",
 "model": "TeSys T LTMR motor management controller (Modbus RTU)",
 "model_slug": "tesys-t-ltmr-modbus",
 "short_model": "TeSys T LTMR",
 "aliases": [
  "TeSys T",
  "LTMR",
  "LTMR08MBD",
  "LTMR27MBD",
  "LTMR100MBD",
  "LTMR08MFM",
  "LTMR27MFM",
  "LTMR100MFM",
  "LTMR..M",
  "LTMEV40"
 ],
 "equipment_type": "Motor management and protection relay",
 "applies_to": "TeSys T LTMR Modbus controllers (LTMR..M..), with or without the LTMEV40 expansion module, per DOCA0130EN-03 (02/2024).",
 "summary": "The TeSys T LTMR protects and controls a motor and talks Modbus RTU on its network port. Registers are grouped by number: monitoring at 450-539 (trips, status, alarms, currents, voltage and power), configuration at 540-699 and commands at 704-705. Most values are 16-bit; phase currents are 32-bit with a selectable word order.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": null,
  "baud": null,
  "parity": null,
  "data_bits": null,
  "stop_bits": null,
  "tcp_port": null
 },
 "addressing": {
  "convention": "0-based",
  "note": "The guide numbers registers from 0 (identification block 0-99), calls each number an 'address', and its PLC examples read 'address 455' and write 'address 704' directly, so the printed number is the wire address."
 },
 "default_word_order": "ABCD",
 "firmware": null,
 "source": {
  "title": "TeSys T LTMR Motor Management Controller Modbus Communication Guide",
  "doc_number": "DOCA0130EN-03",
  "revision_date": "2024-02",
  "url": "https://download.se.com/files?p_Doc_Ref=DOCA0130EN",
  "pages": "Port settings pp. 22-23; functions and examples pp. 25-27; register groups and formats pp. 29-31; data types pp. 34-37; monitoring pp. 45-52; configuration/settings pp. 52-60; commands p. 61"
 },
 "notes": [
  "32-bit values (UDInt) follow the 'Network port endian setting' (bit 10 of register 602): 1 = most significant word first (factory setting), 0 = least significant word first. The map assumes the factory setting.",
  "Registers marked note 1 (voltage, power, power factor, voltage trip/alarm bits, extra I/O) exist only with the LTMEV40 expansion module. Frequency (474) is always present but reads 0 without it.",
  "Factory network settings: address 1 (treated as undefined), baud and parity on autodetection (19200 and even tried first). Parity none uses 2 stop bits, even/odd use 1.",
  "Left out: identification and statistics blocks (0-449), trip history, the full configuration area, user map 800-999 and custom logic registers.",
  "At most 100 registers per request; functions 03, 06, 16 and 43 are supported."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 450,
   "documented": "450",
   "name": "Minimum wait time",
   "description": "Wait before a reset is allowed.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 451,
   "documented": "451",
   "name": "Trip code",
   "description": "Last trip, or the trip with priority.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No error",
    "3": "Ground current",
    "4": "Thermal overload",
    "5": "Long start",
    "6": "Jam",
    "7": "Current phase imbalance",
    "8": "Undercurrent",
    "10": "Test",
    "11": "HMI port error",
    "12": "HMI port comm loss",
    "13": "HMI network port internal error",
    "16": "External trip",
    "18": "On-Off diagnostic",
    "19": "Wiring diagnostic",
    "20": "Overcurrent",
    "21": "Current phase loss",
    "22": "Current phase reversal",
    "23": "Motor temp sensor",
    "24": "Voltage phase imbalance",
    "25": "Voltage phase loss",
    "26": "Voltage phase reversal",
    "27": "Undervoltage",
    "28": "Overvoltage",
    "29": "Underpower",
    "30": "Overpower",
    "31": "Under power factor",
    "32": "Over power factor",
    "33": "LTME configuration",
    "34": "Temperature sensor short-circuit",
    "35": "Temperature sensor open-circuit",
    "36": "CT reversal",
    "37": "Out of boundary CT ratio",
    "46": "Start check",
    "47": "Run checkback",
    "48": "Stop check",
    "49": "Stop checkback",
    "51": "Controller internal temperature",
    "55": "Internal error (stack overflow)",
    "56": "Internal error (RAM)",
    "57": "Internal error (RAM checksum)",
    "58": "Internal error (hardware watchdog)",
    "60": "L2 current in single-phase mode",
    "64": "Non-volatile memory error",
    "65": "Expansion module comm error",
    "66": "Stuck reset button",
    "67": "Logic function error",
    "100": "Network port internal error",
    "101": "Network port internal error",
    "102": "Network port internal error",
    "103": "Network port internal error",
    "104": "Network port internal error",
    "109": "Network port comm error",
    "111": "Fast device replacement trip",
    "555": "Network port configuration error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 452,
   "documented": "452",
   "name": "Trip register 1",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "2": "Ground current trip",
    "3": "Thermal overload trip",
    "4": "Long start trip",
    "5": "Jam trip",
    "6": "Current phase imbalance trip",
    "7": "Undercurrent trip",
    "9": "Test trip",
    "10": "HMI port trip",
    "11": "Controller internal trip",
    "12": "Internal port trip",
    "14": "Network port config trip",
    "15": "Network port trip"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 453,
   "documented": "453",
   "name": "Trip register 2",
   "description": "Bits 6-15 need the LTMEV40 module.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "External system trip",
    "1": "Diagnostic trip",
    "2": "Wiring trip",
    "3": "Overcurrent trip",
    "4": "Current phase loss trip",
    "5": "Current phase reversal trip",
    "6": "Motor temperature sensor trip",
    "7": "Voltage phase imbalance trip",
    "8": "Voltage phase loss trip",
    "9": "Voltage phase reversal trip",
    "10": "Undervoltage trip",
    "11": "Overvoltage trip",
    "12": "Underpower trip",
    "13": "Overpower trip",
    "14": "Under power factor trip",
    "15": "Over power factor trip"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 455,
   "documented": "455",
   "name": "System status register 1",
   "description": "Bits 8-13 hold the average current ratio (32 = 100 % FLC, 63 = 200 % FLC).",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "System ready",
    "1": "System on",
    "2": "System trip",
    "3": "System alarm",
    "4": "System tripped",
    "5": "Trip reset authorized",
    "6": "Controller power",
    "7": "Motor running (current above 10 % FLC)",
    "8-13": "Motor average current ratio",
    "14": "In remote",
    "15": "Motor starting"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 456,
   "documented": "456",
   "name": "System status register 2",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Auto-reset active",
    "2": "Trip power cycle requested",
    "3": "Motor restart time undefined",
    "4": "Rapid cycle lockout",
    "5": "Load shedding",
    "6": "Motor speed: 0 = FLC1, 1 = FLC2",
    "7": "HMI port comm loss",
    "8": "Network port comm loss",
    "9": "Motor transition lockout"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 457,
   "documented": "457",
   "name": "Logic inputs status",
   "description": "Bit n-1 = logic input n; inputs 7-16 need the LTMEV40.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Logic input 1",
    "1": "Logic input 2",
    "2": "Logic input 3",
    "3": "Logic input 4",
    "4": "Logic input 5",
    "5": "Logic input 6",
    "6": "Logic input 7",
    "7": "Logic input 8",
    "8": "Logic input 9",
    "9": "Logic input 10",
    "10": "Logic input 11",
    "11": "Logic input 12",
    "12": "Logic input 13",
    "13": "Logic input 14",
    "14": "Logic input 15",
    "15": "Logic input 16"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 458,
   "documented": "458",
   "name": "Logic outputs status",
   "description": "Bit n-1 = logic output n; outputs 5-8 need the LTMEV40.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Logic output 1",
    "1": "Logic output 2",
    "2": "Logic output 3",
    "3": "Logic output 4",
    "4": "Logic output 5",
    "5": "Logic output 6",
    "6": "Logic output 7",
    "7": "Logic output 8"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 460,
   "documented": "460",
   "name": "Alarm code",
   "description": "Code of the active alarm; 0 = none.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 461,
   "documented": "461",
   "name": "Alarm register 1",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "2": "Ground current alarm",
    "3": "Thermal overload alarm",
    "5": "Jam alarm",
    "6": "Current phase imbalance alarm",
    "7": "Undercurrent alarm",
    "10": "HMI port alarm",
    "11": "Controller internal temperature alarm",
    "15": "Network port alarm"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 462,
   "documented": "462",
   "name": "Alarm register 2",
   "description": "Bits 7-15 need the LTMEV40 module.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "1": "Diagnostic alarm",
    "3": "Overcurrent alarm",
    "4": "Current phase loss alarm",
    "5": "Current phase reversal alarm",
    "6": "Motor temperature sensor alarm",
    "7": "Voltage phase imbalance alarm",
    "8": "Voltage phase loss alarm",
    "10": "Undervoltage alarm",
    "11": "Overvoltage alarm",
    "12": "Underpower alarm",
    "13": "Overpower alarm",
    "14": "Under power factor alarm",
    "15": "Over power factor alarm"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 464,
   "documented": "464",
   "name": "Motor temperature sensor degree",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 465,
   "documented": "465",
   "name": "Thermal capacity level",
   "description": "Percent of the trip level.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 466,
   "documented": "466",
   "name": "Average current ratio",
   "description": "Percent of FLC.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 467,
   "documented": "467",
   "name": "L1 current ratio",
   "description": "Percent of FLC.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 468,
   "documented": "468",
   "name": "L2 current ratio",
   "description": "Percent of FLC.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 469,
   "documented": "469",
   "name": "L3 current ratio",
   "description": "Percent of FLC.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 470,
   "documented": "470",
   "name": "Ground current ratio",
   "description": "Units of 0.1 % of FLC min.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 471,
   "documented": "471",
   "name": "Current phase imbalance",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 472,
   "documented": "472",
   "name": "Controller internal temperature",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 474,
   "documented": "474",
   "name": "Frequency",
   "description": "Always present; 0 without the LTMEV40.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 475,
   "documented": "475",
   "name": "Motor temperature sensor resistance",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "Ω",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 476,
   "documented": "476",
   "name": "Average voltage",
   "description": "Needs the LTMEV40 voltage expansion module.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 477,
   "documented": "477",
   "name": "L3-L1 voltage",
   "description": "Needs the LTMEV40 voltage expansion module.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 478,
   "documented": "478",
   "name": "L1-L2 voltage",
   "description": "Needs the LTMEV40 voltage expansion module.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 479,
   "documented": "479",
   "name": "L2-L3 voltage",
   "description": "Needs the LTMEV40 voltage expansion module.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 480,
   "documented": "480",
   "name": "Voltage phase imbalance",
   "description": "Needs the LTMEV40 voltage expansion module.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 481,
   "documented": "481",
   "name": "Power factor",
   "description": "Needs the LTMEV40 voltage expansion module.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 482,
   "documented": "482",
   "name": "Active power",
   "description": "Needs the LTMEV40 voltage expansion module.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "kW",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 483,
   "documented": "483",
   "name": "Reactive power",
   "description": "Needs the LTMEV40 voltage expansion module.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "kVAR",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 490,
   "documented": "490",
   "name": "Network port monitoring",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Network port monitoring",
    "1": "Network port connected",
    "2": "Network port self-testing",
    "3": "Network port self-detecting",
    "4": "Network port bad config"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 491,
   "documented": "491",
   "name": "Network port baud rate",
   "description": "Actual baud rate in use.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "1200": "1200",
    "2400": "2400",
    "4800": "4800",
    "9600": "9600",
    "19200": "19200",
    "65535": "Autodetection"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 493,
   "documented": "493",
   "name": "Network port parity",
   "description": "Actual parity in use.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "None",
    "1": "Even",
    "2": "Odd"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 500,
   "documented": "500-501",
   "name": "Average current",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 502,
   "documented": "502-503",
   "name": "L1 current",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 504,
   "documented": "504-505",
   "name": "L2 current",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 506,
   "documented": "506-507",
   "name": "L3 current",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 508,
   "documented": "508-509",
   "name": "Ground current",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "mA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 511,
   "documented": "511",
   "name": "Time to trip",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 512,
   "documented": "512",
   "name": "Motor last start current ratio",
   "description": "Percent of FLC.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 513,
   "documented": "513",
   "name": "Motor last start duration",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 514,
   "documented": "514",
   "name": "Motor starts per hour count",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 540,
   "documented": "540",
   "name": "Motor operating mode",
   "description": "Writable only in configuration mode; 256-511 = custom logic program 0-255.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "2": "2-wire overload",
    "3": "3-wire overload",
    "4": "2-wire independent",
    "5": "3-wire independent",
    "6": "2-wire reverser",
    "7": "3-wire reverser",
    "8": "2-wire 2-step",
    "9": "3-wire 2-step",
    "10": "2-wire 2-speed",
    "11": "3-wire 2-speed"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 682,
   "documented": "682",
   "name": "Network port fallback setting",
   "description": "Output state on loss of communication.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Hold LO1 LO2",
    "1": "Run (2-step mode only)",
    "2": "LO1, LO2 off",
    "3": "LO1, LO2 on",
    "4": "LO1 on",
    "5": "LO2 on"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 693,
   "documented": "693",
   "name": "Network port comm loss timeout",
   "description": "Modbus only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 694,
   "documented": "694",
   "name": "Network port parity setting",
   "description": "Modbus only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "None",
    "1": "Even",
    "2": "Odd"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 695,
   "documented": "695",
   "name": "Network port baud rate setting",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1200": "1200",
    "2400": "2400",
    "4800": "4800",
    "9600": "9600",
    "19200": "19200",
    "65535": "Autodetection (factory setting)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 696,
   "documented": "696",
   "name": "Network port address setting",
   "description": "1-247.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 704,
   "documented": "704",
   "name": "Control register 1",
   "description": "Run commands from the network.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Motor run forward command",
    "1": "Motor run reverse command",
    "3": "Trip reset command",
    "5": "Self test command",
    "6": "Motor low speed command"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 705,
   "documented": "705",
   "name": "Control register 2",
   "description": "Clear commands.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Clear all",
    "1": "Clear statistics",
    "2": "Clear thermal capacity level",
    "3": "Clear controller settings",
    "4": "Clear network port settings"
   },
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Read 450-515 for trips, status, alarms and measurements, and write bits in 704 to run, reverse or reset. Register 455 bit 14 shows whether the controller is in remote (network) control.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 455,
    "why": "Ready / on / trip / remote status"
   },
   {
    "table": "holding_register",
    "address": 451,
    "why": "Trip code"
   },
   {
    "table": "holding_register",
    "address": 465,
    "why": "Thermal capacity used"
   },
   {
    "table": "holding_register",
    "address": 500,
    "why": "Average current"
   },
   {
    "table": "holding_register",
    "address": 704,
    "why": "Run / reverse / reset commands"
   },
   {
    "table": "holding_register",
    "address": 460,
    "why": "Alarm code"
   }
  ],
  "enable": "Set the network port address (696), baud (695) and parity (694) via the HMI or SoMove with the TeSys T DTM before communicating. Write run, reverse and reset bits in 704; 455 bit 14 shows whether the controller is in remote control. The guide warns that switching to network control can restart the motor from the last PLC command.",
  "watchdog": "Network port comm loss timeout (693, 0.01 s units) with the fallback action set in 682 (hold, run, outputs off/on).",
  "quirks": [
   "Printed register numbers are wire addresses (numbering starts at 0).",
   "Word order of 32-bit currents depends on register 602 bit 10.",
   "Some bit writes are silently ignored outside configuration mode."
  ],
  "setup": [
   "Address 1-247 (1 = undefined at the factory).",
   "Autodetection tries 19200 baud, even parity first.",
   "Check the PLC Comm (yellow) and Fallback (red) LEDs."
  ],
  "gotchas": [
   "Broadcast writes can change configuration; avoid broadcast.",
   "A reserved register written with a non-zero value returns exception 03."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/schneider-electric/tesys-t-ltmr-modbus",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}