 "manufacturer": "Seneca",
 "manufacturer_slug": "seneca",
 "model": "R-4RTD-8DIDO Ethernet I/O (4 RTD inputs, 8 digital I/O)",
 "model_slug": "r-4rtd-8dido",
 "short_model": "R-4RTD-8DIDO",
 "aliases": [
  "R4RTD8DIDO",
  "R-4RTD-8DIDO",
  "Seneca R series 4RTD"
 ],
 "equipment_type": "Sensor (remote I/O module, RTD inputs)",
 "applies_to": "R-4RTD-8DIDO in the Series R I/O manual MI-00604-29-EN.",
 "summary": "The R-4RTD-8DIDO is a Seneca R-series remote I/O with four RTD temperature inputs and eight digital channels that can be inputs or outputs, plus eight 32-bit counters. It serves Modbus TCP on a two-port Ethernet switch and Modbus RTU on RS-485. This map covers temperatures, resistances, engineering values, status flags, digital I/O and counters.",
 "transport": [
  "TCP",
  "RTU"
 ],
 "defaults": {
  "unit_id": 1,
  "baud": 38400,
  "parity": "None",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": 502
 },
 "addressing": {
  "convention": "Modicon",
  "note": "Holding-register tables print the 4x number (40001) and the 0-based offset (0); coils print 1 / offset 0 and discrete inputs 10001 / offset 0. The offset is the wire address."
 },
 "default_word_order": "ABCD",
 "firmware": null,
 "source": {
  "title": "Series R I/O with protocol - User Manual",
  "doc_number": "MI-00604-29-EN",
  "revision_date": "2026-09-03",
  "url": "https://www.seneca.it/media/6848135/mi00604-29-en.pdf",
  "pages": "Modbus conventions pp. 95-100; R-4RTD-8DIDO tables pp. 203-208; defaults in the web-server chapter pp. 73-81"
 },
 "notes": [
  "The protocol page lists function codes 01, 03, 05, 06, 15 and 16; the tables also give the digital inputs as 1x input status read with function 02. Modbus RTU runs on RS-485 and Modbus TCP serves up to 8 clients.",
  "32-bit values are printed MSW at the lower address (ABCD).",
  "Factory settings from the manual: static IP 192.168.90.101/24, gateway 192.168.90.1, Modbus TCP port 502, station address 1; RS-485 38400 baud, 8 data bits, no parity, 1 stop bit, address 1.",
  "RW* registers are stored in flash and survive about 10,000 writes.",
  "Temperature floats are in the unit chosen per channel in the web server (°C, K, °F or Ohm).",
  "Left out: the signed 16-bit temperature copies at 40057-40060, because the table gives no scale for them.",
  "The table prints the reserved range as 40014..40029 / offset 13..39; the offset end looks like a typo and is not used here."
 ],
 "registers": [
  {
   "table": "coil",
   "address": 0,
   "documented": "1",
   "name": "Digital I/O 1",
   "description": "Same channel as the digital I/O word.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 1,
   "documented": "2",
   "name": "Digital I/O 2",
   "description": "Same channel as the digital I/O word.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 2,
   "documented": "3",
   "name": "Digital I/O 3",
   "description": "Same channel as the digital I/O word.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 3,
   "documented": "4",
   "name": "Digital I/O 4",
   "description": "Same channel as the digital I/O word.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 4,
   "documented": "5",
   "name": "Digital I/O 5",
   "description": "Same channel as the digital I/O word.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 5,
   "documented": "6",
   "name": "Digital I/O 6",
   "description": "Same channel as the digital I/O word.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 6,
   "documented": "7",
   "name": "Digital I/O 7",
   "description": "Same channel as the digital I/O word.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 7,
   "documented": "8",
   "name": "Digital I/O 8",
   "description": "Same channel as the digital I/O word.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 0,
   "documented": "10001",
   "name": "Digital input 1",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 1,
   "documented": "10002",
   "name": "Digital input 2",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 2,
   "documented": "10003",
   "name": "Digital input 3",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 3,
   "documented": "10004",
   "name": "Digital input 4",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 4,
   "documented": "10005",
   "name": "Digital input 5",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 5,
   "documented": "10006",
   "name": "Digital input 6",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 6,
   "documented": "10007",
   "name": "Digital input 7",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 7,
   "documented": "10008",
   "name": "Digital input 8",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 0,
   "documented": "40001",
   "name": "Machine ID",
   "description": "Device identification code.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1,
   "documented": "40002",
   "name": "Firmware revision (major/minor)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "40003",
   "name": "Firmware revision (fix/build)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3,
   "documented": "40004",
   "name": "Firmware code",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4,
   "documented": "40005",
   "name": "Board ID",
   "description": "Hardware revision.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5,
   "documented": "40006",
   "name": "Modbus ID",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 12,
   "documented": "40013",
   "name": "Command register",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "49568": "Reset device (0xC1A0)",
    "256": "Set factory default (0x0100)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 29,
   "documented": "40030",
   "name": "Status",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "RTD1 over-range",
    "1": "RTD2 over-range",
    "2": "RTD3 over-range",
    "3": "RTD4 over-range",
    "4": "RTD1 burnout",
    "5": "RTD2 burnout",
    "6": "RTD3 burnout",
    "7": "RTD4 burnout",
    "15": "Fail"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 30,
   "documented": "40031",
   "name": "Digital outputs",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Output 1",
    "1": "Output 2",
    "2": "Output 3",
    "3": "Output 4",
    "4": "Output 5",
    "5": "Output 6",
    "6": "Output 7",
    "7": "Output 8"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 31,
   "documented": "40032",
   "name": "Digital inputs",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Input 1",
    "1": "Input 2",
    "2": "Input 3",
    "3": "Input 4",
    "4": "Input 5",
    "5": "Input 6",
    "6": "Input 7",
    "7": "Input 8"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 32,
   "documented": "40033",
   "name": "RTD1 temperature",
   "description": "In the unit chosen for the channel (°C, K, °F or Ohm).",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 34,
   "documented": "40035",
   "name": "RTD2 temperature",
   "description": "In the unit chosen for the channel (°C, K, °F or Ohm).",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 36,
   "documented": "40037",
   "name": "RTD3 temperature",
   "description": "In the unit chosen for the channel (°C, K, °F or Ohm).",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 38,
   "documented": "40039",
   "name": "RTD4 temperature",
   "description": "In the unit chosen for the channel (°C, K, °F or Ohm).",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 40,
   "documented": "40041",
   "name": "RTD1 resistance",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "Ohm",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 42,
   "documented": "40043",
   "name": "RTD2 resistance",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "Ohm",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 44,
   "documented": "40045",
   "name": "RTD3 resistance",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "Ohm",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 46,
   "documented": "40047",
   "name": "RTD4 resistance",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "Ohm",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 48,
   "documented": "40049",
   "name": "RTD1 engineering value",
   "description": "Scaled per the channel engineering start/stop scale.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 50,
   "documented": "40051",
   "name": "RTD2 engineering value",
   "description": "Scaled per the channel engineering start/stop scale.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 52,
   "documented": "40053",
   "name": "RTD3 engineering value",
   "description": "Scaled per the channel engineering start/stop scale.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 54,
   "documented": "40055",
   "name": "RTD4 engineering value",
   "description": "Scaled per the channel engineering start/stop scale.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 60,
   "documented": "40061",
   "name": "RTD1 ADC raw value",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 62,
   "documented": "40063",
   "name": "RTD2 ADC raw value",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64,
   "documented": "40065",
   "name": "RTD3 ADC raw value",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 66,
   "documented": "40067",
   "name": "RTD4 ADC raw value",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1843,
   "documented": "41844",
   "name": "Counter 1",
   "description": "Digital input counter.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1845,
   "documented": "41846",
   "name": "Counter 2",
   "description": "Digital input counter.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1847,
   "documented": "41848",
   "name": "Counter 3",
   "description": "Digital input counter.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1849,
   "documented": "41850",
   "name": "Counter 4",
   "description": "Digital input counter.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1851,
   "documented": "41852",
   "name": "Counter 5",
   "description": "Digital input counter.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1853,
   "documented": "41854",
   "name": "Counter 6",
   "description": "Digital input counter.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1855,
   "documented": "41856",
   "name": "Counter 7",
   "description": "Digital input counter.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1857,
   "documented": "41858",
   "name": "Counter 8",
   "description": "Digital input counter.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Read holding registers 29-55 in one block: status flags, digital I/O, then temperature, resistance and engineering floats. Counters live high at 1843-1858.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 29,
    "why": "Over-range / burnout flags"
   },
   {
    "table": "holding_register",
    "address": 32,
    "why": "RTD1 temperature"
   },
   {
    "table": "holding_register",
    "address": 34,
    "why": "RTD2 temperature"
   },
   {
    "table": "holding_register",
    "address": 36,
    "why": "RTD3 temperature"
   },
   {
    "table": "holding_register",
    "address": 38,
    "why": "RTD4 temperature"
   },
   {
    "table": "holding_register",
    "address": 31,
    "why": "Digital inputs"
   }
  ],
  "enable": "Modbus TCP server and RTU slave are on by default; configure through the web server or Seneca Discovery Device.",
  "watchdog": "Per the web-server chapter, digital outputs have an optional watchdog (default disabled, timeout default 100 s) on Modbus traffic or on output writes.",
  "quirks": [
   "Offset is the wire address.",
   "Counters are at offsets 1843-1858, far from the measurement block."
  ],
  "setup": [
   "Factory IP is 192.168.90.101; change it before adding a second unit."
  ],
  "gotchas": [
   "Check the burnout bits before trusting a temperature."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/seneca/r-4rtd-8dido",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}