 "manufacturer": "Seneca",
 "manufacturer_slug": "seneca",
 "model": "R-SG3 Ethernet load cell converter",
 "model_slug": "r-sg3",
 "short_model": "R-SG3",
 "aliases": [
  "RSG3",
  "R-SG3",
  "Seneca R series strain gauge"
 ],
 "equipment_type": "Sensor (load cell / strain gauge converter)",
 "applies_to": "R-SG3 in the Series R I/O manual MI-00604-29-EN.",
 "summary": "The R-SG3 is a Seneca R-series converter for 4- or 6-wire strain-gauge load cells with two digital outputs. It serves Modbus TCP on one Ethernet port and Modbus RTU as a slave. This map covers net/gross/tare weight, status, the command register used for tare and calibration, thresholds and filter setup.",
 "transport": [
  "TCP",
  "RTU"
 ],
 "defaults": {
  "unit_id": 1,
  "baud": 38400,
  "parity": "None",
  "data_bits": null,
  "stop_bits": 1,
  "tcp_port": 502
 },
 "addressing": {
  "convention": "Modicon",
  "note": "The R-SG3 table prints the 4x number (40001) and a 0-based offset (0) on every row; the manual's numbering chapter says the offset is the 0-based address to put on the wire."
 },
 "default_word_order": "ABCD",
 "firmware": null,
 "source": {
  "title": "Series R I/O with protocol - User Manual",
  "doc_number": "MI-00604-29-EN",
  "revision_date": "2026-09-03",
  "url": "https://www.seneca.it/media/6848135/mi00604-29-en.pdf",
  "pages": "R-SG3 description p. 15; DIP switches p. 24; Modbus conventions pp. 95-100; R-SG3 table pp. 180-197; calibration via Modbus p. 213"
 },
 "notes": [
  "Every 32-bit row in the R-SG3 table marks the first register MSW and the second LSW, so the map uses ABCD.",
  "Weight values are IEEE floats in the unit chosen at 40003.",
  "Left out: the signed 32-bit integer weights (40070-40075), because the manual does not say how they are scaled; the analog output settings 40005 and 40022-40029, which apply to the Z-SG3 / ZE-SG3 only; the digital input register 40006, whose text is cut off in the table; reserved and password registers.",
  "Factory settings in the R-SG3 web-server chapter: static IP 192.168.90.101, Modbus TCP port 502, RTU station address 1, 38400 baud, no parity, 1 stop bit (data bits are not listed for this model).",
  "RW* registers live in flash and tolerate about 10,000 writes.",
  "Left out: the raw 24-bit ADC readings (40092-40095), which are typed unsigned 32-bit but carry no MSW/LSW marking."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 0,
   "documented": "40001",
   "name": "Machine ID",
   "description": "Device identification code.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1,
   "documented": "40002",
   "name": "Firmware revision",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "40003",
   "name": "Measurement unit",
   "description": "Engineering unit used for weight values.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "kg",
    "1": "g",
    "2": "t",
    "3": "lb",
    "4": "l",
    "5": "N",
    "6": "bar",
    "7": "atm",
    "8": "Other"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3,
   "documented": "40004",
   "name": "Unipolar mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Bipolar (compression and traction)",
    "1": "Unipolar (balance)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6,
   "documented": "40007",
   "name": "Calibration mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Factory calibration",
    "1": "Calibration with standard weight"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 13,
   "documented": "40014",
   "name": "Cell sensitivity",
   "description": "Load cell rated output.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "mV/V",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 15,
   "documented": "40016",
   "name": "Cell full scale",
   "description": "Load cell capacity in the selected unit.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "eng. units",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 17,
   "documented": "40018",
   "name": "Standard weight",
   "description": "Reference weight used for standard-weight calibration.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "eng. units",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 19,
   "documented": "40020",
   "name": "DO1 threshold",
   "description": "Alarm threshold for digital output 1.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "eng. units",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 29,
   "documented": "40030",
   "name": "Delta weight",
   "description": "Band the weight must stay within to count as stable.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "eng. units",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 31,
   "documented": "40032",
   "name": "Delta time",
   "description": "Time the weight must stay in band to count as stable.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 100,
   "units": "ms",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 32,
   "documented": "40033",
   "name": "Digital output mode",
   "description": "Bits 0-1 contact type; bits 8-11 DO1 mode, bits 12-15 DO2 mode.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "DO1 normally closed (0 = normally open)",
    "1": "DO2 normally closed (0 = normally open)"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 33,
   "documented": "40034",
   "name": "Advanced ADC speed",
   "description": "Used only at filter level 7 (advanced).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "960 Hz",
    "1": "300 Hz",
    "2": "150 Hz",
    "3": "100 Hz",
    "4": "60 Hz",
    "5": "12 Hz",
    "6": "4.7 Hz"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 34,
   "documented": "40035",
   "name": "Automatic tare reset band",
   "description": "0 disables the tare tracker; otherwise the ADC band for automatic re-tare.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "ADC points",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 36,
   "documented": "40037",
   "name": "DO1 threshold hysteresis",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "eng. units",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 38,
   "documented": "40039",
   "name": "Advanced denoise filter variation",
   "description": "Noise-only change in ADC points; filter level 7 only.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "ADC points",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 40,
   "documented": "40041",
   "name": "Advanced denoise filter response",
   "description": "0.001 (slowest) to 1 (fastest); filter level 7 only.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 42,
   "documented": "40043",
   "name": "Denoise filter level",
   "description": "Preset filter level; 7 selects the advanced parameters.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 43,
   "documented": "40044",
   "name": "Resolution mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Automatic (about 20000 points of full scale)",
    "1": "Manual (from manual resolution register)",
    "2": "Maximum (full 24-bit resolution)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 44,
   "documented": "40045",
   "name": "Denoise filter enable",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled (advanced mode enabled)",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 45,
   "documented": "40046",
   "name": "Manual resolution",
   "description": "Display resolution of the weight when manual mode is chosen.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "eng. units",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 47,
   "documented": "40048",
   "name": "Single piece weight",
   "description": "Used by the piece counter.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "eng. units",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 49,
   "documented": "40050",
   "name": "DO2 threshold",
   "description": "Alarm threshold for digital output 2.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "eng. units",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 51,
   "documented": "40052",
   "name": "DO2 threshold hysteresis",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "eng. units",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 62,
   "documented": "40063",
   "name": "ADC filtered (16-bit)",
   "description": "Filtered converter value scaled to 16 bits.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 63,
   "documented": "40064",
   "name": "Net weight",
   "description": "Net weight in the selected unit.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "eng. units",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 65,
   "documented": "40066",
   "name": "Gross weight",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "eng. units",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 67,
   "documented": "40068",
   "name": "Tare weight",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "eng. units",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 75,
   "documented": "40076",
   "name": "Factory manual tare",
   "description": "Tare entered by hand for factory-calibration mode.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "eng. units",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 77,
   "documented": "40078",
   "name": "Status",
   "description": "Weighing status; bits 5-6 drive the outputs when they are set to Modbus mode.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Threshold and stable weight, DO1",
    "1": "Cell at full scale",
    "2": "Net weight below zero",
    "3": "Threshold and stable weight, DO2",
    "4": "Stable weight",
    "5": "Digital output 2 on (Modbus mode, writable)",
    "6": "Digital output 1 on (Modbus mode, writable)",
    "7": "Threshold with hysteresis, DO1",
    "8": "Tare tracker acted",
    "9": "Threshold with hysteresis, DO2"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 79,
   "documented": "40080",
   "name": "Command",
   "description": "Write a command code; the register returns to 0 when done.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "43948": "Reboot",
    "49594": "Acquire tare in RAM (lost at reboot)",
    "49914": "Acquire tare in flash for calibration",
    "50700": "Acquire standard weight in flash",
    "50773": "Take tare from the factory manual tare register",
    "49151": "Reset maximum net weight",
    "45056": "Reset minimum net weight"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 80,
   "documented": "40081",
   "name": "Piece count",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 81,
   "documented": "40082",
   "name": "Maximum net weight",
   "description": "Highest net weight since the last reboot.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "eng. units",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 83,
   "documented": "40084",
   "name": "Minimum net weight",
   "description": "Lowest net weight since the last reboot.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "eng. units",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Poll net weight (63) and status (77); bit 4 of status says the weight is stable. Tare and calibration are done by writing codes to the command register at 79.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 63,
    "why": "Net weight"
   },
   {
    "table": "holding_register",
    "address": 65,
    "why": "Gross weight"
   },
   {
    "table": "holding_register",
    "address": 67,
    "why": "Tare weight"
   },
   {
    "table": "holding_register",
    "address": 77,
    "why": "Status (stable, full scale, negative)"
   },
   {
    "table": "holding_register",
    "address": 79,
    "why": "Command register (tare, reboot)"
   },
   {
    "table": "holding_register",
    "address": 2,
    "why": "Engineering unit in use"
   }
  ],
  "enable": "Modbus TCP and RTU are active by default; network settings are changed in the web server or Seneca's discovery tool. DIP switches 1-2 select normal operation, factory reset or web server disabled.",
  "watchdog": null,
  "quirks": [
   "Offsets are the wire addresses.",
   "Floats are MSW first.",
   "Bits 5-6 of the status register only drive the outputs when the output mode is 'from Modbus' (40033)."
  ],
  "setup": [
   "Factory IP is 192.168.90.101; change it before adding a second unit.",
   "Field tare: write 49914 to the command register with the empty platform loaded."
  ],
  "gotchas": [
   "Tare taken with code 49594 lives in RAM and is lost at reboot; use 49914 to store it in flash.",
   "Output mode codes in 40033 bits 8-11 (DO1) and 12-15 (DO2): 0 full scale, 1 threshold, 2 stable weight, 3 from Modbus, 4 threshold with hysteresis.",
   "Filter level 7 hands control to the advanced filter registers."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/seneca/r-sg3",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}