 "manufacturer": "Seneca",
 "manufacturer_slug": "seneca",
 "model": "R203 three-phase power analyzer (Ethernet + RS-485)",
 "model_slug": "r203",
 "short_model": "R203",
 "aliases": [
  "R203-1",
  "R203-2",
  "Seneca R203"
 ],
 "equipment_type": "Power meter (three-phase network analyzer)",
 "applies_to": "R203-1 and R203-2 as covered by user manual MI-00591-4-EN.",
 "summary": "The Seneca R203 is a DIN-rail three-phase network analyzer with harmonic analysis, digital I/O and a data logger. It serves Modbus TCP on Ethernet and Modbus RTU on RS-485 from one holding-register table. This map covers identity and status, instantaneous electrical values, THD, fundamentals, 64-bit energy counters, system values and the two pulse counters.",
 "transport": [
  "TCP",
  "RTU"
 ],
 "defaults": {
  "unit_id": 1,
  "baud": 38400,
  "parity": "None",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": 502
 },
 "addressing": {
  "convention": "Modicon",
  "note": "Each table row prints the 4x number (40001) beside a 0-based ADDRESS OFFSET (0); the manual's addressing chapter says the offset is the 0-based address. Request the offset on the wire."
 },
 "default_word_order": "ABCD",
 "firmware": null,
 "source": {
  "title": "User Manual R203-1 / R203-2",
  "doc_number": "MI-00591-4-EN (rev 4)",
  "revision_date": "2023-02-16",
  "url": "https://www.seneca.it/media/6849393/mi00591-4-en.pdf",
  "pages": "Modbus conventions pp. 24-28; register table pp. 29-113 (instantaneous pp. 31-34, fundamentals p. 47, energies pp. 104-110, system values and counters pp. 112-113)"
 },
 "notes": [
  "Only function codes 03, 06 and 16 are supported; everything is a holding register.",
  "Every 32-bit row is marked MSW at the lower address and every 64-bit energy is marked MMSW first, so the map uses ABCD. The manual says the two words can be swapped when reading; this map follows the order printed in the tables.",
  "Energy totals are in Wh / VARh / VAh as unsigned or signed 64-bit integers as printed.",
  "Left out: the per-harmonic voltage and current tables, the averaged and min/max values from 41497 upward, and the L1 net active energy (41843), which is typed UNSIGNED64 while its L2/L3 siblings are SIGNED64.",
  "Left out: the per-phase apparent energy rows 41867-41878, whose register name says reactive energy while the description says apparent energy.",
  "Factory network settings: static IP 192.168.90.101, gateway 192.168.90.1, Modbus TCP port 502, TCP station address 1; RS-485 38400 baud 8N1.",
  "RW* registers live in flash and tolerate about 10,000 writes.",
  "Left out: the demand averaging time (45075), typed 32-bit but printed as a single row with no MSW/LSW marking."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 0,
   "documented": "40001",
   "name": "Machine ID",
   "description": "Device identification code.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1,
   "documented": "40002",
   "name": "Firmware revision (major/minor)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "40003",
   "name": "Firmware revision (fix/build)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3,
   "documented": "40004",
   "name": "Firmware code",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6,
   "documented": "40007",
   "name": "Board ID",
   "description": "Hardware revision.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16,
   "documented": "40017",
   "name": "Command",
   "description": "Write 49568 to reboot the meter.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "49568": "Reboot"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 17,
   "documented": "40018",
   "name": "Status",
   "description": "Wiring, alarm and digital I/O status flags.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Cyclic phase sequence error",
    "1": "Alarm active",
    "2": "DOUT1 active",
    "3": "DOUT2 active",
    "4": "DIN1 high",
    "5": "DIN2 high",
    "6": "Current cutoff active",
    "7": "L1 CT connected reversed",
    "8": "L2 CT connected reversed",
    "9": "L3 CT connected reversed",
    "10": "Line 1 voltage/current connection error",
    "11": "Line 2 voltage/current connection error",
    "12": "Line 3 voltage/current connection error"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 21,
   "documented": "40022",
   "name": "Digital inputs",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Input 1",
    "1": "Input 2"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 22,
   "documented": "40023",
   "name": "Digital outputs",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Output 1",
    "1": "Output 2"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 26,
   "documented": "40027",
   "name": "Analog output manual value",
   "description": "Output level in manual mode: 0 = 0 %, 8190 = 100 %.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 100,
   "documented": "40101",
   "name": "Voltage L1-L2",
   "description": "RMS line-to-line voltage.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 102,
   "documented": "40103",
   "name": "Voltage L2-L3",
   "description": "RMS line-to-line voltage.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 104,
   "documented": "40105",
   "name": "Voltage L3-L1",
   "description": "RMS line-to-line voltage.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 106,
   "documented": "40107",
   "name": "Current L1",
   "description": "RMS current.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 108,
   "documented": "40109",
   "name": "Current L2",
   "description": "RMS current.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 110,
   "documented": "40111",
   "name": "Current L3",
   "description": "RMS current.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 112,
   "documented": "40113",
   "name": "Current N",
   "description": "RMS current.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 114,
   "documented": "40115",
   "name": "V-I phase angle L1",
   "description": "Angle between voltage and current.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "°",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 116,
   "documented": "40117",
   "name": "V-I phase angle L2",
   "description": "Angle between voltage and current.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "°",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 118,
   "documented": "40119",
   "name": "V-I phase angle L3",
   "description": "Angle between voltage and current.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "°",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 120,
   "documented": "40121",
   "name": "Active power L1",
   "description": "Positive = absorbed, negative = generated.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 122,
   "documented": "40123",
   "name": "Active power L2",
   "description": "Positive = absorbed, negative = generated.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 124,
   "documented": "40125",
   "name": "Active power L3",
   "description": "Positive = absorbed, negative = generated.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 126,
   "documented": "40127",
   "name": "Reactive power L1",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VAR",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 128,
   "documented": "40129",
   "name": "Reactive power L2",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VAR",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 130,
   "documented": "40131",
   "name": "Reactive power L3",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VAR",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 132,
   "documented": "40133",
   "name": "Apparent power L1",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 134,
   "documented": "40135",
   "name": "Apparent power L2",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 136,
   "documented": "40137",
   "name": "Apparent power L3",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 138,
   "documented": "40139",
   "name": "Power factor L1",
   "description": "Positive = load (user), negative = generator.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 140,
   "documented": "40141",
   "name": "Power factor L2",
   "description": "Positive = load (user), negative = generator.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 142,
   "documented": "40143",
   "name": "Power factor L3",
   "description": "Positive = load (user), negative = generator.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 144,
   "documented": "40145",
   "name": "Frequency L1",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 146,
   "documented": "40147",
   "name": "Frequency L2",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 148,
   "documented": "40149",
   "name": "Frequency L3",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 150,
   "documented": "40151",
   "name": "Period L1",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 152,
   "documented": "40153",
   "name": "Period L2",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 154,
   "documented": "40155",
   "name": "Period L3",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 156,
   "documented": "40157",
   "name": "V-V phase angle L1-L2",
   "description": "Angle between two line voltages.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "°",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 158,
   "documented": "40159",
   "name": "V-V phase angle L2-L3",
   "description": "Angle between two line voltages.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "°",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 160,
   "documented": "40161",
   "name": "V-V phase angle L3-L1",
   "description": "Angle between two line voltages.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "°",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 162,
   "documented": "40163",
   "name": "Voltage L1-N",
   "description": "RMS phase-to-neutral voltage.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 164,
   "documented": "40165",
   "name": "Voltage L2-N",
   "description": "RMS phase-to-neutral voltage.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 166,
   "documented": "40167",
   "name": "Voltage L3-N",
   "description": "RMS phase-to-neutral voltage.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 168,
   "documented": "40169",
   "name": "Active power total",
   "description": "Positive = absorbed, negative = generated.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 170,
   "documented": "40171",
   "name": "Reactive power total",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VAR",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 172,
   "documented": "40173",
   "name": "Apparent power total",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 174,
   "documented": "40175",
   "name": "Power factor total",
   "description": "Positive = load (user), negative = generator.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 176,
   "documented": "40177",
   "name": "Voltage THD L1",
   "description": "Total harmonic distortion relative to the fundamental.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 178,
   "documented": "40179",
   "name": "Voltage THD L2",
   "description": "Total harmonic distortion relative to the fundamental.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 180,
   "documented": "40181",
   "name": "Voltage THD L3",
   "description": "Total harmonic distortion relative to the fundamental.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 182,
   "documented": "40183",
   "name": "Current THD L1",
   "description": "Total harmonic distortion relative to the fundamental.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 184,
   "documented": "40185",
   "name": "Current THD L2",
   "description": "Total harmonic distortion relative to the fundamental.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 186,
   "documented": "40187",
   "name": "Current THD L3",
   "description": "Total harmonic distortion relative to the fundamental.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 188,
   "documented": "40189",
   "name": "Fundamental voltage L1-N",
   "description": "RMS of the fundamental only.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 190,
   "documented": "40191",
   "name": "Fundamental voltage L2-N",
   "description": "RMS of the fundamental only.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 192,
   "documented": "40193",
   "name": "Fundamental voltage L3-N",
   "description": "RMS of the fundamental only.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 518,
   "documented": "40519",
   "name": "Fundamental current L1",
   "description": "RMS of the fundamental only.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 520,
   "documented": "40521",
   "name": "Fundamental current L2",
   "description": "RMS of the fundamental only.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 522,
   "documented": "40523",
   "name": "Fundamental current L3",
   "description": "RMS of the fundamental only.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1746,
   "documented": "41747",
   "name": "Active energy imported L1",
   "description": "Import only (Q1/Q4).",
   "data_type": "UINT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "Wh",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1750,
   "documented": "41751",
   "name": "Active energy imported L2",
   "description": "Import only (Q1/Q4).",
   "data_type": "UINT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "Wh",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1754,
   "documented": "41755",
   "name": "Active energy imported L3",
   "description": "Import only (Q1/Q4).",
   "data_type": "UINT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "Wh",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1758,
   "documented": "41759",
   "name": "Active energy exported L1",
   "description": "Export only (Q2/Q3).",
   "data_type": "UINT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "Wh",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1762,
   "documented": "41763",
   "name": "Active energy exported L2",
   "description": "Export only (Q2/Q3).",
   "data_type": "UINT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "Wh",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1766,
   "documented": "41767",
   "name": "Active energy exported L3",
   "description": "Export only (Q2/Q3).",
   "data_type": "UINT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "Wh",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1770,
   "documented": "41771",
   "name": "Reactive energy positive L1",
   "description": "Q1 + Q2.",
   "data_type": "UINT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VARh",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1774,
   "documented": "41775",
   "name": "Reactive energy positive L2",
   "description": "Q1 + Q2.",
   "data_type": "UINT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VARh",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1778,
   "documented": "41779",
   "name": "Reactive energy positive L3",
   "description": "Q1 + Q2.",
   "data_type": "UINT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VARh",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1782,
   "documented": "41783",
   "name": "Reactive energy negative L1",
   "description": "Q3 + Q4.",
   "data_type": "UINT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VARh",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1786,
   "documented": "41787",
   "name": "Reactive energy negative L2",
   "description": "Q3 + Q4.",
   "data_type": "UINT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VARh",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1790,
   "documented": "41791",
   "name": "Reactive energy negative L3",
   "description": "Q3 + Q4.",
   "data_type": "UINT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VARh",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1846,
   "documented": "41847",
   "name": "Active energy net L2",
   "description": "Signed import/export balance.",
   "data_type": "INT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "Wh",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1850,
   "documented": "41851",
   "name": "Active energy net L3",
   "description": "Signed import/export balance.",
   "data_type": "INT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "Wh",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1854,
   "documented": "41855",
   "name": "Reactive energy net L1",
   "description": "Signed balance.",
   "data_type": "INT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VARh",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1858,
   "documented": "41859",
   "name": "Reactive energy net L2",
   "description": "Signed balance.",
   "data_type": "INT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VARh",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1862,
   "documented": "41863",
   "name": "Reactive energy net L3",
   "description": "Signed balance.",
   "data_type": "INT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VARh",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1878,
   "documented": "41879",
   "name": "Active energy imported total",
   "description": "Three-phase, import only (Q1/Q4).",
   "data_type": "UINT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "Wh",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1882,
   "documented": "41883",
   "name": "Active energy exported total",
   "description": "Three-phase, export only (Q2/Q3).",
   "data_type": "UINT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "Wh",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1886,
   "documented": "41887",
   "name": "Reactive energy positive total",
   "description": "Three-phase, Q1 + Q2.",
   "data_type": "UINT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VARh",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1890,
   "documented": "41891",
   "name": "Reactive energy negative total",
   "description": "Three-phase, Q3 + Q4.",
   "data_type": "UINT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VARh",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1894,
   "documented": "41895",
   "name": "Active energy net total",
   "description": "Three-phase signed balance.",
   "data_type": "INT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "Wh",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1898,
   "documented": "41899",
   "name": "Reactive energy net total",
   "description": "Three-phase signed balance.",
   "data_type": "INT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VARh",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1902,
   "documented": "41903",
   "name": "Apparent energy total",
   "description": "Three-phase apparent energy.",
   "data_type": "INT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VAh",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1994,
   "documented": "41995",
   "name": "System voltage",
   "description": "Average of the three phase voltages.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "V",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1996,
   "documented": "41997",
   "name": "System current",
   "description": "System current value as labelled in the table.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "A",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2018,
   "documented": "42019",
   "name": "Digital input 1 counter",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2020,
   "documented": "42021",
   "name": "Digital input 2 counter",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Read the instantaneous float block 100-187 in one or two requests, and the three-phase 64-bit energy totals at 1878-1905. Status at 17 flags reversed CTs and wiring errors during commissioning.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 100,
    "why": "Line voltage L1-L2"
   },
   {
    "table": "holding_register",
    "address": 106,
    "why": "Current L1"
   },
   {
    "table": "holding_register",
    "address": 168,
    "why": "Total active power"
   },
   {
    "table": "holding_register",
    "address": 174,
    "why": "Total power factor"
   },
   {
    "table": "holding_register",
    "address": 144,
    "why": "Frequency"
   },
   {
    "table": "holding_register",
    "address": 1878,
    "why": "Imported active energy total"
   },
   {
    "table": "holding_register",
    "address": 1882,
    "why": "Exported active energy total"
   },
   {
    "table": "holding_register",
    "address": 17,
    "why": "Status and wiring error flags"
   }
  ],
  "enable": "The Modbus TCP server and RTU slave are active by default. Network and serial parameters are set with the Easy Setup 2 software or the web server.",
  "watchdog": "The manual documents a Modbus TCP connection timeout (default 60 s) that closes idle client connections; no output watchdog is described.",
  "quirks": [
   "Table offsets are the wire addresses; 4x numbers are offset + 40001.",
   "32-bit floats are MSW first and 64-bit energies MMSW first as printed in the tables."
  ],
  "setup": [
   "Factory IP is 192.168.90.101: change it before putting a second unit on the same network.",
   "RS-485 defaults to 38400 baud, 8 data bits, no parity, 1 stop bit; the manual does not print a default RTU station address."
  ],
  "gotchas": [
   "Check status bits 7-12 after wiring: reversed CTs and voltage/current mismatches are flagged there.",
   "Power sign follows the quadrant convention: negative active power means generation."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/seneca/r203",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}