 "manufacturer": "Seneca",
 "manufacturer_slug": "seneca",
 "model": "Z-3AO 3-channel analog output module",
 "model_slug": "z-3ao",
 "short_model": "Z-3AO",
 "aliases": [
  "Z-3AO"
 ],
 "equipment_type": "Actuator / valve driver (I/O module, 3 analog outputs)",
 "applies_to": "Seneca Z-3AO DIN-rail module with three voltage/current outputs and RS-485 Modbus RTU, per user manual MI00260-2-EN.",
 "summary": "The Z-3AO drives three analog outputs (voltage or current, chosen per channel by DIP switch) from normalized values written over RS-485 Modbus RTU. All registers are single 16-bit holding registers; a bus-timeout fault mode can force preset output values.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": 1,
  "baud": 38400,
  "parity": "None",
  "data_bits": 8,
  "stop_bits": null,
  "tcp_port": null
 },
 "addressing": {
  "convention": "Modicon",
  "note": "The register table prints 4xxxx numbers (40001 = first holding register), so 40005 is wire address 4."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "Z-3AO User Manual",
  "doc_number": "MI00260-2-EN",
  "revision_date": null,
  "url": "https://www.seneca.it/media/1340/mi00260-2-en.pdf",
  "pages": "RS485 register table pp. 4-7"
 },
 "notes": [
  "All registers are single 16-bit words; there are no 32-bit values.",
  "Address 1 and 38400 baud are the EEPROM defaults, used when the address DIP switches select memory mode.",
  "Command values for 40009 are listed in decimal in 'values' with the hex code in the text.",
  "The output scaling registers are signed for mV (-11000..11000) and unsigned for µA (0..22000), following the ranges in the table."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 0,
   "documented": "40001",
   "name": "Machine ID",
   "description": "High byte = module ID code (0x0F), low byte = module version.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1,
   "documented": "40002",
   "name": "Baud rate and address",
   "description": "High byte = baud code (0=4800,1=9600,2=19200,3=38400,4=57600,5=115200,6=1200,7=2400), low byte = address; EEPROM mode.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "40003",
   "name": "Communication timeout",
   "description": "0-250 (0-25 s), default 200; applies when 40004 bit 7 is set.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3,
   "documented": "40004",
   "name": "EEPROM flags",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "2": "RS-485 reply delay on",
    "3": "RS-485 parity on",
    "4": "Parity odd (0 = even)",
    "7": "On bus timeout, copy fault values 40069-40071 to the outputs",
    "12": "New Z-3AO mode (0 = old mode)"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4,
   "documented": "40005",
   "name": "OUT1 normalized value",
   "description": "-10000..10000 (voltage) or 0..10000 (current).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5,
   "documented": "40006",
   "name": "OUT2 normalized value",
   "description": "-10000..10000 (voltage) or 0..10000 (current).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6,
   "documented": "40007",
   "name": "OUT3 normalized value",
   "description": "-10000..10000 (voltage) or 0..10000 (current).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 7,
   "documented": "40008",
   "name": "Errors",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "2": "Bus communication fault (timeout)",
    "4": "EEPROM data lost"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8,
   "documented": "40009",
   "name": "Command",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "47792": "0xBAB0 save configuration to EEPROM",
    "51904": "0xCAC0 copy DIP switch state to 40010",
    "49568": "0xC1A0 reset module"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9,
   "documented": "40010",
   "name": "DIP switch state",
   "description": "Filled after writing 0xCAC0 to 40009.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "8": "OUT1 DIP set to voltage (0 = current)",
    "9": "OUT2 DIP set to voltage",
    "10": "OUT3 DIP set to voltage"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10,
   "documented": "40011",
   "name": "Firmware code",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11,
   "documented": "40012",
   "name": "OUT1 mV at normalized 0",
   "description": "-11000..11000 mV, default 0 mV (voltage outputs).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "mV",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 12,
   "documented": "40013",
   "name": "OUT1 mV at normalized 10000",
   "description": "Electrical end scale, default 10000 mV.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "mV",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 13,
   "documented": "40014",
   "name": "OUT2 mV at normalized 0",
   "description": "-11000..11000 mV, default 0 mV (voltage outputs).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "mV",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14,
   "documented": "40015",
   "name": "OUT2 mV at normalized 10000",
   "description": "Electrical end scale, default 10000 mV.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "mV",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 15,
   "documented": "40016",
   "name": "OUT3 mV at normalized 0",
   "description": "-11000..11000 mV, default 0 mV (voltage outputs).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "mV",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16,
   "documented": "40017",
   "name": "OUT3 mV at normalized 10000",
   "description": "Electrical end scale, default 10000 mV.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "mV",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 17,
   "documented": "40018",
   "name": "OUT1 µA at normalized 0",
   "description": "0..22000 µA, default 4000 µA (current outputs).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "µA",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 18,
   "documented": "40019",
   "name": "OUT1 µA at normalized 10000",
   "description": "Electrical end scale, default 20000 µA.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "µA",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 19,
   "documented": "40020",
   "name": "OUT2 µA at normalized 0",
   "description": "0..22000 µA, default 4000 µA (current outputs).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "µA",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 20,
   "documented": "40021",
   "name": "OUT2 µA at normalized 10000",
   "description": "Electrical end scale, default 20000 µA.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "µA",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 21,
   "documented": "40022",
   "name": "OUT3 µA at normalized 0",
   "description": "0..22000 µA, default 4000 µA (current outputs).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "µA",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 22,
   "documented": "40023",
   "name": "OUT3 µA at normalized 10000",
   "description": "Electrical end scale, default 20000 µA.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "µA",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 68,
   "documented": "40069",
   "name": "OUT1 fault value",
   "description": "Normalized value applied on bus timeout when fault mode is on.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 69,
   "documented": "40070",
   "name": "OUT2 fault value",
   "description": "Normalized value applied on bus timeout when fault mode is on.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 70,
   "documented": "40071",
   "name": "OUT3 fault value",
   "description": "Normalized value applied on bus timeout when fault mode is on.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Write normalized values to 40005-40007 (wire 4-6): 0-10000 maps to the electrical start/end scale of each output.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 4,
    "why": "OUT1 setpoint"
   },
   {
    "table": "holding_register",
    "address": 5,
    "why": "OUT2 setpoint"
   },
   {
    "table": "holding_register",
    "address": 6,
    "why": "OUT3 setpoint"
   },
   {
    "table": "holding_register",
    "address": 7,
    "why": "Error bits"
   },
   {
    "table": "holding_register",
    "address": 2,
    "why": "Bus timeout"
   }
  ],
  "enable": "Set the baud rate with DIP switches 1-2 and the address with switches 3-8, or set switches 3-8 OFF to use the EEPROM values in 40002/40004.",
  "watchdog": "With 40004 bit 7 set, if no bus traffic arrives for the time in 40003 (0.1 s units, default 20 s) the module sets 40008 bit 2 and copies 40069-40071 to the outputs.",
  "quirks": [
   "40002 packs baud code and address into one register.",
   "Output type follows the per-channel DIP switch."
  ],
  "setup": [
   "Write 0xBAB0 to 40009 to store settings in EEPROM."
  ],
  "gotchas": [
   "Bit 12 of 40004 selects old or new Z-3AO behaviour."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/seneca/z-3ao",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}