 "manufacturer": "Seneca",
 "manufacturer_slug": "seneca",
 "model": "Z-4AI 4-channel analog input module",
 "model_slug": "z-4ai",
 "short_model": "Z-4AI",
 "aliases": [
  "Z-4AI"
 ],
 "equipment_type": "Sensor (I/O module, 4 analog inputs)",
 "applies_to": "Seneca Z-4AI DIN-rail module with 4 voltage/current inputs and RS-485 Modbus RTU, per user manual MI002572-E.",
 "summary": "The Z-4AI converts four ±10 V / ±20 mA single-ended inputs to normalized 16-bit values readable over RS-485 Modbus RTU. Everything is in single 16-bit holding registers: comms settings, per-channel filters and scaling, the four measurements and, from firmware 737, channel differences.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": 1,
  "baud": 38400,
  "parity": "None",
  "data_bits": 8,
  "stop_bits": null,
  "tcp_port": null
 },
 "addressing": {
  "convention": "Modicon",
  "note": "The table prints both the 4x number and the offset (40001 = offset 0); the offset is the wire address."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "Z-4AI User Manual",
  "doc_number": "MI002572-E",
  "revision_date": null,
  "url": "https://www.seneca.it/media/1329/mi00257-2-en.pdf",
  "pages": "DIP switches p. 9; register table pp. 10-15"
 },
 "notes": [
  "All registers are single 16-bit words; there are no 32-bit values.",
  "Address 1 and 38400 baud are the EEPROM defaults, used only when the address DIP switches are all OFF; otherwise DIP switches set address (1-63) and baud (9600-57600).",
  "Bit 0 of 40003 selects Z-4AI-0 compatibility, in which the measurement is fixed to 0-10000.",
  "Left out: 40036, labelled 'Errors' but printed with the same parity/delay/sampling bit list as 40003, so its real content is unclear."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 0,
   "documented": "40001",
   "name": "Machine ID",
   "description": "High byte = module ID code (default 0x07), low byte = module version.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1,
   "documented": "40002",
   "name": "Baud rate and address",
   "description": "High byte = baud code (0=4800,1=9600,2=19200,3=38400,4=57600,5=115200,6=1200,7=2400), low byte = address; EEPROM mode.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "40003",
   "name": "EEPROM flags",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Compatibility: 1 = Z-4AI-1, 0 = Z-4AI-0",
    "1": "Sampling time: 1 = 60 ms, 0 = 120 ms",
    "2": "RS-485 reply delay on",
    "3": "RS-485 parity on",
    "4": "Parity odd (0 = even)"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3,
   "documented": "40004",
   "name": "IN1 filter",
   "description": "Input filter level 0 (off) to 6 (strongest).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4,
   "documented": "40005",
   "name": "IN2 filter",
   "description": "Input filter level 0 (off) to 6 (strongest).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5,
   "documented": "40006",
   "name": "IN3 filter",
   "description": "Input filter level 0 (off) to 6 (strongest).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6,
   "documented": "40007",
   "name": "IN4 filter",
   "description": "Input filter level 0 (off) to 6 (strongest).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 7,
   "documented": "40008",
   "name": "IN1 electrical end scale",
   "description": "±10000 mV (voltage) or ±20000 µA (current); default 10000 mV.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "mV/µA",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8,
   "documented": "40009",
   "name": "IN2 electrical end scale",
   "description": "±10000 mV (voltage) or ±20000 µA (current); default 10000 mV.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "mV/µA",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9,
   "documented": "40010",
   "name": "IN3 electrical end scale",
   "description": "±10000 mV (voltage) or ±20000 µA (current); default 10000 mV.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "mV/µA",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10,
   "documented": "40011",
   "name": "IN4 electrical end scale",
   "description": "±10000 mV (voltage) or ±20000 µA (current); default 10000 mV.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "mV/µA",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11,
   "documented": "40012",
   "name": "IN1 electrical start scale",
   "description": "Default 0 mV.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "mV/µA",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 12,
   "documented": "40013",
   "name": "IN2 electrical start scale",
   "description": "Default 0 mV.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "mV/µA",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 13,
   "documented": "40014",
   "name": "IN3 electrical start scale",
   "description": "Default 0 mV.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "mV/µA",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14,
   "documented": "40015",
   "name": "IN4 electrical start scale",
   "description": "Default 0 mV.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "mV/µA",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 15,
   "documented": "40016",
   "name": "Status",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Reset module (write 1)",
    "1": "Reset filter (write 1)",
    "7": "Save configuration to EEPROM (write 1)",
    "8": "IN1 overflow",
    "9": "IN1 underflow",
    "10": "IN2 overflow",
    "11": "IN2 underflow",
    "12": "IN3 overflow",
    "13": "IN3 underflow",
    "14": "IN4 overflow",
    "15": "IN4 underflow"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16,
   "documented": "40017",
   "name": "IN1 normalized value",
   "description": "Scaled between NSS and NES (fixed 0-10000 in Z-4AI-0 mode).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 17,
   "documented": "40018",
   "name": "IN2 normalized value",
   "description": "Scaled between NSS and NES (fixed 0-10000 in Z-4AI-0 mode).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 18,
   "documented": "40019",
   "name": "IN3 normalized value",
   "description": "Scaled between NSS and NES (fixed 0-10000 in Z-4AI-0 mode).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 19,
   "documented": "40020",
   "name": "IN4 normalized value",
   "description": "Scaled between NSS and NES (fixed 0-10000 in Z-4AI-0 mode).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 24,
   "documented": "40025",
   "name": "Input types",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "IN1 current (0 = voltage)",
    "1": "IN2 current",
    "2": "IN3 current",
    "3": "IN4 current"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 25,
   "documented": "40026",
   "name": "IN1 normalized end scale",
   "description": "±32000, default 10000.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 26,
   "documented": "40027",
   "name": "IN2 normalized end scale",
   "description": "±32000, default 10000.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 27,
   "documented": "40028",
   "name": "IN3 normalized end scale",
   "description": "±32000, default 10000.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 28,
   "documented": "40029",
   "name": "IN4 normalized end scale",
   "description": "±32000, default 10000.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 29,
   "documented": "40030",
   "name": "IN1 normalized start scale",
   "description": "±32000, default 0.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 30,
   "documented": "40031",
   "name": "IN2 normalized start scale",
   "description": "±32000, default 0.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 31,
   "documented": "40032",
   "name": "IN3 normalized start scale",
   "description": "±32000, default 0.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 32,
   "documented": "40033",
   "name": "IN4 normalized start scale",
   "description": "±32000, default 0.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 34,
   "documented": "40035",
   "name": "Firmware code",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 54,
   "documented": "40055",
   "name": "Difference IN2 - IN1",
   "description": "Channel difference; firmware revision 737 or later.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 55,
   "documented": "40056",
   "name": "Difference IN1 - IN2",
   "description": "Channel difference; firmware revision 737 or later.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 56,
   "documented": "40057",
   "name": "Difference IN4 - IN3",
   "description": "Channel difference; firmware revision 737 or later.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 57,
   "documented": "40058",
   "name": "Difference IN3 - IN4",
   "description": "Channel difference; firmware revision 737 or later.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Read holding registers 40017-40020 (wire 16-19) for the four normalized inputs and 40016 for over/underflow bits.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 16,
    "why": "IN1"
   },
   {
    "table": "holding_register",
    "address": 17,
    "why": "IN2"
   },
   {
    "table": "holding_register",
    "address": 18,
    "why": "IN3"
   },
   {
    "table": "holding_register",
    "address": 19,
    "why": "IN4"
   },
   {
    "table": "holding_register",
    "address": 15,
    "why": "Status and over/underflow"
   }
  ],
  "enable": "Set address and baud with the SW1 DIP switches, or set all address switches OFF to use the values stored in 40002/40003.",
  "watchdog": null,
  "quirks": [
   "40002 packs baud code and address into one register.",
   "Input type must match the SW2 DIP switch for each channel."
  ],
  "setup": [
   "SW1 switches 9-10 enable the RS-485 terminator.",
   "Write bit 7 of 40016 to store settings in EEPROM."
  ],
  "gotchas": [
   "Difference registers 40055-40058 exist only from firmware revision 737."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/seneca/z-4ai",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}