 "manufacturer": "Seneca",
 "manufacturer_slug": "seneca",
 "model": "Z-4RTD2-SI 4-channel RTD input module (Modbus RTU)",
 "model_slug": "z-4rtd2-si",
 "short_model": "Z-4RTD2-SI",
 "aliases": [
  "Z-4RTD2",
  "Z4RTD2-SI",
  "Seneca Z-4RTD2-SI"
 ],
 "equipment_type": "Sensor (RTD temperature input module)",
 "applies_to": "Z-4RTD2-SI per user manual MI00584-4-EN.",
 "summary": "The Z-4RTD2-SI reads four RTD sensors (PT100, PT500, PT1000, NI100, NI120, NI1000, CU50, CU100) in 2, 3 or 4-wire mode and serves them over Modbus RTU. Each channel is available as a scaled 16-bit integer and as a float. This map covers measurements, error flags, serial settings, per-channel configuration, fault values, offsets and the command register.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": null,
  "baud": null,
  "parity": null,
  "data_bits": null,
  "stop_bits": null,
  "tcp_port": null
 },
 "addressing": {
  "convention": "Modicon",
  "note": "The table prints the 4x number (40003) and the 0-based offset (2). The offset is the wire address."
 },
 "default_word_order": "ABCD",
 "firmware": null,
 "source": {
  "title": "Z-4RTD2-SI User Manual",
  "doc_number": "MI00584-4-EN",
  "revision_date": "2026-06-29",
  "url": "https://www.seneca.it/media/6849343/mi00584-4-en.pdf",
  "pages": "Modbus conventions pp. 14-18; register table pp. 19-25"
 },
 "notes": [
  "All values are holding registers.",
  "Floats are printed MSW at the lower address (ABCD); bit 15 of Configuration 2 (offset 40) switches them to LSW first. The manual does not state the factory value of that bit, so confirm it reads 0 before trusting ABCD. The manual also lists a word-swapped copy at +1000 (e.g. 41007); not included here.",
  "The 16-bit measures are °C/10 in temperature mode. In resistance mode they are Ohm/100 for PT100/NI100/NI120/CU50/CU100 and Ohm/10 for PT500/PT1000/NI1000, so the listed 0.1 scale only fits temperature mode.",
  "RW* registers are in flash (about 10,000 writes).",
  "The manual does not give factory defaults for address or baud rate."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 0,
   "documented": "40001",
   "name": "Machine identification",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1,
   "documented": "40002",
   "name": "Errors",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "15": "IN1 out of range",
    "14": "IN2 out of range",
    "13": "IN3 out of range",
    "12": "IN4 out of range",
    "11": "IN1 burnout",
    "10": "IN2 burnout",
    "9": "IN3 burnout",
    "8": "IN4 burnout"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "40003",
   "name": "Channel 1 measure (16-bit)",
   "description": "°C/10 in temperature mode; resistance mode uses Ohm/100 or Ohm/10 by sensor.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3,
   "documented": "40004",
   "name": "Channel 2 measure (16-bit)",
   "description": "°C/10 in temperature mode; resistance mode uses Ohm/100 or Ohm/10 by sensor.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4,
   "documented": "40005",
   "name": "Channel 3 measure (16-bit)",
   "description": "°C/10 in temperature mode; resistance mode uses Ohm/100 or Ohm/10 by sensor.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5,
   "documented": "40006",
   "name": "Channel 4 measure (16-bit)",
   "description": "°C/10 in temperature mode; resistance mode uses Ohm/100 or Ohm/10 by sensor.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6,
   "documented": "40007",
   "name": "Channel 1 measure (float)",
   "description": "°C, or Ohm in resistance mode.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8,
   "documented": "40009",
   "name": "Channel 2 measure (float)",
   "description": "°C, or Ohm in resistance mode.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10,
   "documented": "40011",
   "name": "Channel 3 measure (float)",
   "description": "°C, or Ohm in resistance mode.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 12,
   "documented": "40013",
   "name": "Channel 4 measure (float)",
   "description": "°C, or Ohm in resistance mode.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14,
   "documented": "40015",
   "name": "Firmware revision",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 34,
   "documented": "40035",
   "name": "RS485 address and parity",
   "description": "High byte = station address 1-255; low byte = parity.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "8-15": "Modbus station address (1-255)",
    "0-7": "Parity: 0 none, 1 even, 2 odd"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 35,
   "documented": "40036",
   "name": "RS485 baud rate",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "8-15": "Baud: 0=4800 1=9600 2=19200 3=38400 4=57600 5=115200 6=1200 7=2400"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 36,
   "documented": "40037",
   "name": "Channel 1 input configuration",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "9-11": "Filter: 0 off, 1 on",
    "6-8": "RTD type: 0 PT100, 1 NI100, 2 PT500, 3 PT1000, 4 CU50, 5 CU100, 6 NI120, 7 NI1000",
    "5": "Measure type: 0 temperature, 1 resistance",
    "4": "Wiring: 0 = 2/4-wire, 1 = 3-wire",
    "0-2": "Channel speed: 0 disabled, 1 25 ms, 2 50 ms, 3 100 ms, 4 200 ms, 5 400 ms"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 37,
   "documented": "40038",
   "name": "Channel 2 input configuration",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "9-11": "Filter: 0 off, 1 on",
    "6-8": "RTD type: 0 PT100, 1 NI100, 2 PT500, 3 PT1000, 4 CU50, 5 CU100, 6 NI120, 7 NI1000",
    "5": "Measure type: 0 temperature, 1 resistance",
    "4": "Wiring: 0 = 2/4-wire, 1 = 3-wire",
    "0-2": "Channel speed: 0 disabled, 1 25 ms, 2 50 ms, 3 100 ms, 4 200 ms, 5 400 ms"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 38,
   "documented": "40039",
   "name": "Channel 3 input configuration",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "9-11": "Filter: 0 off, 1 on",
    "6-8": "RTD type: 0 PT100, 1 NI100, 2 PT500, 3 PT1000, 4 CU50, 5 CU100, 6 NI120, 7 NI1000",
    "5": "Measure type: 0 temperature, 1 resistance",
    "4": "Wiring: 0 = 2/4-wire, 1 = 3-wire",
    "0-2": "Channel speed: 0 disabled, 1 25 ms, 2 50 ms, 3 100 ms, 4 200 ms, 5 400 ms"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 39,
   "documented": "40040",
   "name": "Channel 4 input configuration",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "9-11": "Filter: 0 off, 1 on",
    "6-8": "RTD type: 0 PT100, 1 NI100, 2 PT500, 3 PT1000, 4 CU50, 5 CU100, 6 NI120, 7 NI1000",
    "5": "Measure type: 0 temperature, 1 resistance",
    "4": "Wiring: 0 = 2/4-wire, 1 = 3-wire",
    "0-2": "Channel speed: 0 disabled, 1 25 ms, 2 50 ms, 3 100 ms, 4 200 ms, 5 400 ms"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 40,
   "documented": "40041",
   "name": "Configuration 2",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "15": "Float word order: 0 MSW first, 1 LSW first",
    "3": "IN1 fault: 1 load fail value, 0 keep last",
    "2": "IN2 fault: 1 load fail value, 0 keep last",
    "1": "IN3 fault: 1 load fail value, 0 keep last",
    "0": "IN4 fault: 1 load fail value, 0 keep last"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 41,
   "documented": "40042",
   "name": "Channel 1 fail value",
   "description": "Loaded on fault when fail-value behaviour is set; °C/10 or Ohm.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 42,
   "documented": "40043",
   "name": "Channel 2 fail value",
   "description": "Loaded on fault when fail-value behaviour is set; °C/10 or Ohm.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 43,
   "documented": "40044",
   "name": "Channel 3 fail value",
   "description": "Loaded on fault when fail-value behaviour is set; °C/10 or Ohm.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 44,
   "documented": "40045",
   "name": "Channel 4 fail value",
   "description": "Loaded on fault when fail-value behaviour is set; °C/10 or Ohm.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 47,
   "documented": "40048",
   "name": "Command register",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "52428": "Reboot",
    "51792": "Save configuration"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 132,
   "documented": "40133",
   "name": "Channel 1 offset",
   "description": "Offset added to the channel, °C or Ohm.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 134,
   "documented": "40135",
   "name": "Channel 2 offset",
   "description": "Offset added to the channel, °C or Ohm.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 136,
   "documented": "40137",
   "name": "Channel 3 offset",
   "description": "Offset added to the channel, °C or Ohm.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 138,
   "documented": "40139",
   "name": "Channel 4 offset",
   "description": "Offset added to the channel, °C or Ohm.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Read holding registers 1-13 (function 03): error flags, four scaled integers and four floats. Check the burnout and out-of-range bits in register 1 before trusting a value.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 1,
    "why": "Error / burnout flags"
   },
   {
    "table": "holding_register",
    "address": 6,
    "why": "Channel 1 float"
   },
   {
    "table": "holding_register",
    "address": 8,
    "why": "Channel 2 float"
   },
   {
    "table": "holding_register",
    "address": 10,
    "why": "Channel 3 float"
   },
   {
    "table": "holding_register",
    "address": 12,
    "why": "Channel 4 float"
   },
   {
    "table": "holding_register",
    "address": 2,
    "why": "Channel 1 integer"
   }
  ],
  "enable": "Modbus RTU is always on. Station address and parity are in register 34, baud rate in 35; write 51792 to register 47 to save configuration and 52428 to reboot.",
  "watchdog": null,
  "quirks": [
   "Offset is the wire address.",
   "Float word order can be flipped by Configuration 2 bit 15."
  ],
  "setup": [
   "Set sensor type, wiring and speed per channel in registers 36-39, then save (51792 to register 47)."
  ],
  "gotchas": [
   "Integer scaling changes when a channel is switched to resistance mode.",
   "While a USB cable is plugged in, the RS-485 port is disabled; unplug USB to restore it."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/seneca/z-4rtd2-si",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}