 "manufacturer": "Seneca",
 "manufacturer_slug": "seneca",
 "model": "Z-8AI 8-channel analog input module",
 "model_slug": "z-8ai",
 "short_model": "Z-8AI",
 "aliases": [
  "Z-8AI"
 ],
 "equipment_type": "Sensor (I/O module, 8 analog inputs)",
 "applies_to": "Seneca Z-8AI DIN-rail module with 8 voltage/current inputs and RS-485 Modbus RTU, per user manual MI00259-3-EN.",
 "summary": "The Z-8AI reads eight ±10 V / ±20 mA analog inputs and reports each as a normalized 16-bit value over RS-485 Modbus RTU. All data are single 16-bit holding registers; each channel has electrical and normalized start/end scale settings and a flag word.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": 1,
  "baud": 38400,
  "parity": "None",
  "data_bits": 8,
  "stop_bits": null,
  "tcp_port": null
 },
 "addressing": {
  "convention": "Modicon",
  "note": "The register table prints 4xxxx numbers (40001 = first holding register), so 40003 is wire address 2."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "Z-8AI User Manual",
  "doc_number": "MI00259-3-EN",
  "revision_date": null,
  "url": "https://www.seneca.it/media/6849154/mi00259-3-en.pdf",
  "pages": "DIP-switch tables p. 5; RS485 register table pp. 6-9"
 },
 "notes": [
  "Every register is a single 16-bit word; there are no 32-bit values in this map.",
  "Address 1, 38400 baud and no parity are the EEPROM defaults; they apply only when the address DIP switches select 'from memory'. Otherwise the DIP switches set address and baud.",
  "The table has no registers 40011, 40018, 40024, 40030, 40036, 40042, 40048, 40054 or 40060; they are not listed.",
  "Scale units for the electrical start/end registers are mV for a voltage input and µA for a current input, set by the channel flag and DIP switches."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 0,
   "documented": "40001",
   "name": "Machine ID",
   "description": "High byte = module ID code (0x0E), low byte = module version.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1,
   "documented": "40002",
   "name": "Status",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "8": "Reset module (write 1)",
    "12": "Save configuration to EEPROM (write 1)",
    "13": "EEPROM memory error",
    "14": "Configuration error",
    "15": "Generic error"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "40003",
   "name": "IN1 normalized value",
   "description": "Input 1 scaled between its NSS and NES settings.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3,
   "documented": "40004",
   "name": "IN2 normalized value",
   "description": "Input 2 scaled between its NSS and NES settings.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4,
   "documented": "40005",
   "name": "IN3 normalized value",
   "description": "Input 3 scaled between its NSS and NES settings.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5,
   "documented": "40006",
   "name": "IN4 normalized value",
   "description": "Input 4 scaled between its NSS and NES settings.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6,
   "documented": "40007",
   "name": "IN5 normalized value",
   "description": "Input 5 scaled between its NSS and NES settings.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 7,
   "documented": "40008",
   "name": "IN6 normalized value",
   "description": "Input 6 scaled between its NSS and NES settings.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8,
   "documented": "40009",
   "name": "IN7 normalized value",
   "description": "Input 7 scaled between its NSS and NES settings.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9,
   "documented": "40010",
   "name": "IN8 normalized value",
   "description": "Input 8 scaled between its NSS and NES settings.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11,
   "documented": "40012",
   "name": "RS485 address and parity",
   "description": "High byte = node address 1-255; low byte = parity (0 none, 1 even, 2 odd).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 12,
   "documented": "40013",
   "name": "RS485 baud rate and delay",
   "description": "High byte = baud code (0=4800,1=9600,2=19200,3=38400,4=57600,5=115200,6=1200,7=2400), low byte = reply delay.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 13,
   "documented": "40014",
   "name": "IN1 electrical start scale",
   "description": "±10000 mV for voltage, ±20000 µA for current; default 0 mV.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "mV/µA",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14,
   "documented": "40015",
   "name": "IN1 electrical end scale",
   "description": "Default 10000 mV.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "mV/µA",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 15,
   "documented": "40016",
   "name": "IN1 normalized start scale",
   "description": "±32000, default 0.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16,
   "documented": "40017",
   "name": "IN1 normalized end scale",
   "description": "±32000, default 10000.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 18,
   "documented": "40019",
   "name": "IN1 flags",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Input type: 1 = current, 0 = voltage",
    "2": "Sampling time bit 0 (00=10 ms, 01=30 ms, 10=40 ms, 11=120 ms)",
    "3": "Sampling time bit 1",
    "7": "Input enabled"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 19,
   "documented": "40020",
   "name": "IN2 electrical start scale",
   "description": "±10000 mV for voltage, ±20000 µA for current; default 0 mV.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "mV/µA",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 20,
   "documented": "40021",
   "name": "IN2 electrical end scale",
   "description": "Default 10000 mV.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "mV/µA",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 21,
   "documented": "40022",
   "name": "IN2 normalized start scale",
   "description": "±32000, default 0.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 22,
   "documented": "40023",
   "name": "IN2 normalized end scale",
   "description": "±32000, default 10000.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 24,
   "documented": "40025",
   "name": "IN2 flags",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Input type: 1 = current, 0 = voltage",
    "2": "Sampling time bit 0 (00=10 ms, 01=30 ms, 10=40 ms, 11=120 ms)",
    "3": "Sampling time bit 1",
    "7": "Input enabled"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 25,
   "documented": "40026",
   "name": "IN3 electrical start scale",
   "description": "±10000 mV for voltage, ±20000 µA for current; default 0 mV.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "mV/µA",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 26,
   "documented": "40027",
   "name": "IN3 electrical end scale",
   "description": "Default 10000 mV.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "mV/µA",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 27,
   "documented": "40028",
   "name": "IN3 normalized start scale",
   "description": "±32000, default 0.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 28,
   "documented": "40029",
   "name": "IN3 normalized end scale",
   "description": "±32000, default 10000.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 30,
   "documented": "40031",
   "name": "IN3 flags",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Input type: 1 = current, 0 = voltage",
    "2": "Sampling time bit 0 (00=10 ms, 01=30 ms, 10=40 ms, 11=120 ms)",
    "3": "Sampling time bit 1",
    "7": "Input enabled"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 31,
   "documented": "40032",
   "name": "IN4 electrical start scale",
   "description": "±10000 mV for voltage, ±20000 µA for current; default 0 mV.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "mV/µA",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 32,
   "documented": "40033",
   "name": "IN4 electrical end scale",
   "description": "Default 10000 mV.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "mV/µA",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 33,
   "documented": "40034",
   "name": "IN4 normalized start scale",
   "description": "±32000, default 0.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 34,
   "documented": "40035",
   "name": "IN4 normalized end scale",
   "description": "±32000, default 10000.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 36,
   "documented": "40037",
   "name": "IN4 flags",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Input type: 1 = current, 0 = voltage",
    "2": "Sampling time bit 0 (00=10 ms, 01=30 ms, 10=40 ms, 11=120 ms)",
    "3": "Sampling time bit 1",
    "7": "Input enabled"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 37,
   "documented": "40038",
   "name": "IN5 electrical start scale",
   "description": "±10000 mV for voltage, ±20000 µA for current; default 0 mV.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "mV/µA",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 38,
   "documented": "40039",
   "name": "IN5 electrical end scale",
   "description": "Default 10000 mV.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "mV/µA",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 39,
   "documented": "40040",
   "name": "IN5 normalized start scale",
   "description": "±32000, default 0.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 40,
   "documented": "40041",
   "name": "IN5 normalized end scale",
   "description": "±32000, default 10000.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 42,
   "documented": "40043",
   "name": "IN5 flags",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Input type: 1 = current, 0 = voltage",
    "2": "Sampling time bit 0 (00=10 ms, 01=30 ms, 10=40 ms, 11=120 ms)",
    "3": "Sampling time bit 1",
    "7": "Input enabled"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 43,
   "documented": "40044",
   "name": "IN6 electrical start scale",
   "description": "±10000 mV for voltage, ±20000 µA for current; default 0 mV.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "mV/µA",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 44,
   "documented": "40045",
   "name": "IN6 electrical end scale",
   "description": "Default 10000 mV.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "mV/µA",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 45,
   "documented": "40046",
   "name": "IN6 normalized start scale",
   "description": "±32000, default 0.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 46,
   "documented": "40047",
   "name": "IN6 normalized end scale",
   "description": "±32000, default 10000.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 48,
   "documented": "40049",
   "name": "IN6 flags",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Input type: 1 = current, 0 = voltage",
    "2": "Sampling time bit 0 (00=10 ms, 01=30 ms, 10=40 ms, 11=120 ms)",
    "3": "Sampling time bit 1",
    "7": "Input enabled"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 49,
   "documented": "40050",
   "name": "IN7 electrical start scale",
   "description": "±10000 mV for voltage, ±20000 µA for current; default 0 mV.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "mV/µA",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 50,
   "documented": "40051",
   "name": "IN7 electrical end scale",
   "description": "Default 10000 mV.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "mV/µA",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 51,
   "documented": "40052",
   "name": "IN7 normalized start scale",
   "description": "±32000, default 0.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 52,
   "documented": "40053",
   "name": "IN7 normalized end scale",
   "description": "±32000, default 10000.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 54,
   "documented": "40055",
   "name": "IN7 flags",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Input type: 1 = current, 0 = voltage",
    "2": "Sampling time bit 0 (00=10 ms, 01=30 ms, 10=40 ms, 11=120 ms)",
    "3": "Sampling time bit 1",
    "7": "Input enabled"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 55,
   "documented": "40056",
   "name": "IN8 electrical start scale",
   "description": "±10000 mV for voltage, ±20000 µA for current; default 0 mV.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "mV/µA",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 56,
   "documented": "40057",
   "name": "IN8 electrical end scale",
   "description": "Default 10000 mV.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "mV/µA",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 57,
   "documented": "40058",
   "name": "IN8 normalized start scale",
   "description": "±32000, default 0.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 58,
   "documented": "40059",
   "name": "IN8 normalized end scale",
   "description": "±32000, default 10000.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 60,
   "documented": "40061",
   "name": "IN8 flags",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Input type: 1 = current, 0 = voltage",
    "2": "Sampling time bit 0 (00=10 ms, 01=30 ms, 10=40 ms, 11=120 ms)",
    "3": "Sampling time bit 1",
    "7": "Input enabled"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 61,
   "documented": "40062",
   "name": "Firmware code",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 62,
   "documented": "40063",
   "name": "Errors",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "ADC error",
    "8": "Calibration error in memory",
    "9": "Setting error in memory"
   },
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Read holding registers 40003-40010 (wire 2-9) in one request for the eight normalized inputs; by default 0-10 V maps to 0-10000.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 2,
    "why": "IN1"
   },
   {
    "table": "holding_register",
    "address": 3,
    "why": "IN2"
   },
   {
    "table": "holding_register",
    "address": 4,
    "why": "IN3"
   },
   {
    "table": "holding_register",
    "address": 5,
    "why": "IN4"
   },
   {
    "table": "holding_register",
    "address": 1,
    "why": "Status/error bits"
   },
   {
    "table": "holding_register",
    "address": 62,
    "why": "Error bits"
   }
  ],
  "enable": "Set the baud rate with DIP switches 1-2 and the address with switches 3-8; with switches 3-8 all OFF the address and baud come from EEPROM (40012/40013).",
  "watchdog": null,
  "quirks": [
   "40012 and 40013 each pack two byte-wide settings into one register.",
   "For a current input, set both the channel's input-type DIP switch (it enables the shunt) and bit 0 of the channel flags register."
  ],
  "setup": [
   "DIP switches 9-10 enable the RS-485 terminator.",
   "Set bit 12 of 40002 to store changed settings in EEPROM."
  ],
  "gotchas": [
   "Check 40002 bits 13-15 and 40063 for EEPROM, configuration and ADC errors after changing settings."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/seneca/z-8ai",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}