 "manufacturer": "Seneca",
 "manufacturer_slug": "seneca",
 "model": "Z-D-IN 5-channel digital input / counter module (Modbus RTU)",
 "model_slug": "z-d-in",
 "short_model": "Z-D-IN",
 "aliases": [
  "ZDIN",
  "Z D IN",
  "Seneca Z-D-IN"
 ],
 "equipment_type": "Sensor (digital input / counter I/O module)",
 "applies_to": "Z-D-IN DIN-rail module, user manual MI00252-3-EN (revision 3, 13/01/2022).",
 "summary": "The Z-D-IN is a DIN-rail module with five digital inputs, each feeding a counter, on an RS-485 Modbus RTU port. Address and baud rate come from DIP switches or from EEPROM. This map covers input states, the five counters (IN5 can run as a 32-bit counter), filter, configuration flags and the save/reset command register.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": 1,
  "baud": 38400,
  "parity": "None",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "Modicon",
  "note": "The table prints both the Modbus address (40001 = first register) and the offset address (0). The offset is what goes on the wire."
 },
 "default_word_order": "CDAB",
 "firmware": null,
 "source": {
  "title": "User Manual Z-D-IN",
  "doc_number": "MI00252-3-EN",
  "revision_date": "2022-01-13",
  "url": "https://www.seneca.it/media/2495/mi00252-3-en.pdf",
  "pages": "DIP switches p. 8; Modbus rules p. 9; register table pp. 10-13"
 },
 "notes": [
  "All registers are holding registers; functions 03, 06 and 16 are supported.",
  "The only 32-bit value, the IN5 32-bit counter, is stored LSW at 40019 and MSW at 40020 (CDAB), as printed in the table.",
  "Register 40010 holds node address and baud rate together. Its bit description is self-contradictory (it gives bits 0-7 to both the baud code and the node address), so it is left out; set these with the DIP switches or Easy Setup.",
  "R/W(*) registers (40008-40010) only reach EEPROM after bit 0 of the command register (40011) is set.",
  "Default serial settings from the manual: 38400 baud, 8 data bits, no parity, 1 stop bit, address 1."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 0,
   "documented": "40001",
   "name": "Machine ID",
   "description": "Module identification code.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1,
   "documented": "40002",
   "name": "Input status and counter overflows",
   "description": "Overflow bits can be written to 0 to clear them.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "IN1 state",
    "1": "IN2 state",
    "2": "IN3 state",
    "3": "IN4 state",
    "4": "IN5 state",
    "8": "Counter 1 overflow/underflow",
    "9": "Counter 2 overflow/underflow",
    "10": "Counter 3 overflow/underflow",
    "11": "Counter 4 overflow/underflow",
    "12": "Counter 5 overflow/underflow"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "40003",
   "name": "Counter 1",
   "description": "16-bit counter (0-65535) kept in FeRAM; writable.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3,
   "documented": "40004",
   "name": "Counter 2",
   "description": "16-bit counter (0-65535) kept in FeRAM; writable.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4,
   "documented": "40005",
   "name": "Counter 3",
   "description": "16-bit counter (0-65535) kept in FeRAM; writable.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5,
   "documented": "40006",
   "name": "Counter 4",
   "description": "16-bit counter (0-65535) kept in FeRAM; writable.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6,
   "documented": "40007",
   "name": "Counter 5 (16-bit mode)",
   "description": "16-bit counter (0-65535) kept in FeRAM; writable. In 32-bit mode use 18-19.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 7,
   "documented": "40008",
   "name": "Input filter",
   "description": "1-254 ms, applied to all inputs (not IN5 in 32-bit mode). Default 3.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "ms",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8,
   "documented": "40009",
   "name": "Configuration flags",
   "description": "Saved to EEPROM only after the save command bit.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Input logic: 0 direct, 1 inverted",
    "1": "Count mode: 0 up, 1 down",
    "2": "RS485 reply pause: 0 none, 1 insert pause",
    "3": "Parity: 0 none, 1 on",
    "4": "Parity type: 0 even, 1 odd",
    "7": "IN5 32-bit mode (filter off, up to 10 kHz)"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10,
   "documented": "40011",
   "name": "Bit command register",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Write 1: save 40008-40010 to EEPROM",
    "1": "Write 1: reset module"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 12,
   "documented": "40013",
   "name": "Firmware revision",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14,
   "documented": "40015",
   "name": "Counter 1 copy",
   "description": "16-bit counter (0-65535) kept in FeRAM; writable.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 15,
   "documented": "40016",
   "name": "Counter 2 copy",
   "description": "16-bit counter (0-65535) kept in FeRAM; writable.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16,
   "documented": "40017",
   "name": "Counter 3 copy",
   "description": "16-bit counter (0-65535) kept in FeRAM; writable.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 17,
   "documented": "40018",
   "name": "Counter 4 copy",
   "description": "16-bit counter (0-65535) kept in FeRAM; writable.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 18,
   "documented": "40019 (LSW) / 40020 (MSW)",
   "name": "Counter 5 (32-bit mode)",
   "description": "32-bit counter used when IN5 32-bit mode is on; LSW first.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Read holding registers 0-6 (function 03) for the input states and the five counters. Write a counter register to preset or clear it.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 1,
    "why": "Input states and overflow flags"
   },
   {
    "table": "holding_register",
    "address": 2,
    "why": "Counter 1"
   },
   {
    "table": "holding_register",
    "address": 3,
    "why": "Counter 2"
   },
   {
    "table": "holding_register",
    "address": 4,
    "why": "Counter 3"
   },
   {
    "table": "holding_register",
    "address": 5,
    "why": "Counter 4"
   },
   {
    "table": "holding_register",
    "address": 6,
    "why": "Counter 5"
   }
  ],
  "enable": "Modbus RTU is always on. DIP switches 3-8 set the address (all off = take address and baud from EEPROM), 1-2 the baud rate, 9-10 the RS-485 terminator.",
  "watchdog": null,
  "quirks": [
   "Offset address is the wire address.",
   "The 32-bit IN5 counter is LSW first."
  ],
  "setup": [
   "Default 38400 8N1, address 1.",
   "After writing the filter or flags, set bit 0 of register 10 to save to EEPROM."
  ],
  "gotchas": [
   "Overflow flags in register 1 stay set until written back to 0."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/seneca/z-d-in",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}