 "manufacturer": "Sensirion",
 "manufacturer_slug": "sensirion",
 "model": "SCD30 CO2, humidity and temperature sensor module",
 "model_slug": "scd30",
 "short_model": "SCD30",
 "aliases": [
  "SCD30"
 ],
 "equipment_type": "Sensor (CO2, humidity, temperature module)",
 "applies_to": "Sensirion SCD30 sensor module with the SEL pin pulled high at power-up (Modbus mode), per interface description version 1.0.",
 "summary": "The SCD30 is an NDIR CO2 module with on-board humidity and temperature sensing. With the SEL pin tied to VDD it speaks Modbus RTU (UART level) at a fixed address and baud rate. Measurements are big-endian IEEE-754 floats; configuration commands are single 16-bit register writes.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": 97,
  "baud": 19200,
  "parity": "None",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "hex 0-based",
  "note": "Addresses are given in hex exactly as they appear in the request frames (for example 0x61 0x03 0x00 0x28 reads from 0x0028), so they are wire addresses."
 },
 "default_word_order": "ABCD",
 "firmware": null,
 "source": {
  "title": "Interface Description Sensirion SCD30 Sensor Module",
  "doc_number": "Version 1.0 - D1",
  "revision_date": "2020-05",
  "url": "https://sensirion.com/media/documents/D7CEEF4A/6165372F/Sensirion_CO2_Sensors_SCD30_Interface_Description.pdf",
  "pages": "Modbus settings p. 6; command set pp. 7-15; read measurement example p. 11; firmware p. 14; soft reset p. 15"
 },
 "notes": [
  "The read-measurement example returns 43 DB 8C 2E (439 ppm), 41 D9 E7 FF (27.2 °C) and 42 43 3A 1B (48.8 %RH), and the document states the values are big-endian floats, so all three are high word first.",
  "The sensor accepts function codes 3, 4 and 6 only; there is no multi-register write.",
  "The Modbus address 0x61 (97) and 19200 8N1 are fixed in this document; no command to change them is listed.",
  "The UART pins are at logic level; an RS-485 transceiver is needed to put the module on a bus."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 32,
   "documented": "0x0020",
   "name": "Firmware version",
   "description": "High byte = major, low byte = minor.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 37,
   "documented": "0x0025",
   "name": "Measurement interval",
   "description": "Continuous measurement interval, 2 to 1800 s (default 2 s).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 39,
   "documented": "0x0027",
   "name": "Data ready status",
   "description": "1 when a new measurement can be read.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No new data",
    "1": "Data ready"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 40,
   "documented": "0x0028-0x0029",
   "name": "CO2 concentration",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "ppm",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 42,
   "documented": "0x002A-0x002B",
   "name": "Temperature",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 44,
   "documented": "0x002C-0x002D",
   "name": "Relative humidity",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 52,
   "documented": "0x0034",
   "name": "Soft reset",
   "description": "Write 1 to restart the sensor.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 54,
   "documented": "0x0036",
   "name": "Start continuous measurement",
   "description": "Write ambient pressure 700-1400 mbar, or 0 to start without pressure compensation.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "mbar",
   "access": "W",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 55,
   "documented": "0x0037",
   "name": "Stop continuous measurement",
   "description": "Write 1 to stop measuring.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 56,
   "documented": "0x0038",
   "name": "Altitude compensation",
   "description": "Height above sea level in metres.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "m",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 57,
   "documented": "0x0039",
   "name": "Forced recalibration reference",
   "description": "Reference CO2 concentration 400-2000 ppm for forced recalibration.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "ppm",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 58,
   "documented": "0x003A",
   "name": "Automatic self-calibration",
   "description": "Off by default.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 59,
   "documented": "0x003B",
   "name": "Temperature offset",
   "description": "Offset for the on-board RH/T sensor in 0.01 °C steps.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Write 0 (or the ambient pressure in mbar) to 0x0036 once to start measuring; the setting survives power cycles. Then poll 0x0027 for data ready and read six registers from 0x0028 for CO2, temperature and humidity.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 54,
    "why": "Start continuous measurement"
   },
   {
    "table": "holding_register",
    "address": 39,
    "why": "Data ready"
   },
   {
    "table": "holding_register",
    "address": 40,
    "why": "CO2"
   },
   {
    "table": "holding_register",
    "address": 42,
    "why": "Temperature"
   },
   {
    "table": "holding_register",
    "address": 44,
    "why": "Humidity"
   }
  ],
  "enable": "Pull the SEL pin to VDD during power-up to select Modbus instead of I2C.",
  "watchdog": null,
  "quirks": [
   "Address 0x61 and 19200 8N1 are fixed.",
   "The manual's read example fetches all six measurement registers from 0x0028 in one request (CO2, temperature, humidity, each high word first)."
  ],
  "setup": [
   "Power up with SEL high, connect TX/RX through a suitable transceiver, then send the start command."
  ],
  "gotchas": [
   "Continuous measurement and ASC states are stored in non-volatile memory and resume after power-up."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/sensirion/scd30",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}